| CO Springs DRE | Original | D | 11/5/2026 | SSADLER | SSADLER | On the site plan, show the bar scale. Show the dimensions of garages and structures. show the height of both structures measured from average finished grade to the highest point of the roof. Show the required parking stall for the ADU. Fees will be due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2378717 |
| City Engr | Original | D | 11/4/2026 | JDAGNILLO | JDAGNILLO | On the Site Plan drawing, please show and call out how vehicle access will be obtained to this lot (off N. Corona St., off alley, or both). If driveway is being installed off Corona, show it on the site plan and note that it must be 12-24' wide and a minimum of 5' away from the side property line.
No geologic hazard report or waiver will be required. | | City Engr | 2378529 |
| Energy | Original | D | 11/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2378075 |
| Plumbing | Original | D | 11/3/2026 | SHANEN | SHANEN | Plumbing plans do not match the architectural floor plans. Remove all notes that do not apply to the plumbing scope. Use table E104.1 for water pipe size blocks. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2378074 |
| Stormwater | Original | N | 11/3/2026 | GHUNTLEY | GHUNTLEY | Activity does not disturb an acre or more and is not part of a larger common plan of development. | | Stormwater | 2377904 |
| Mechanical | Original | D | 11/3/2026 | QUINTONW | QUINTONW | Disapproved:Provide manufacture specifications for cooling and heating appliances being used for this design. AM&M required to use 2024 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2377903 |
| Zoning/Planning | Original | / | 11/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2377772 |
| Electrical | Original | D | 11/2/2026 | CONNERM | CONNERM | AM&M required to submit under 2024 IECC
Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so
Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Show compliance with IECC R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2377703 |
| Electronic Plan | Original | / | 11/2/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2377699 |
| Construction | Original | D | 11/2/2026 | SHELLEY | SHELLEY | Egress, eave protection, slab, IECC, trusses. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2377663 |
| Electronic Plan | Original | / | 11/2/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2377635 |
| Enumeration | Original | D | 10/22/2026 | AMY | AMY | Site plan: full legal description added and addresses to both home. If this sheet gets changed out, add this information back to site plan. Demo permit in place for main home and cottage. Q41760 Provide roof plan w/solar ready zones. B-was added to all the sheets since detached homes need a separate address. Add this back is sheets get changed out. Please provide a copy of the Waiver of Replat to Enumerations once recorded. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2374049 |
| Electronic Plan | Original | / | 10/22/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2374012 |
| | Original | / | 10/22/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/22/2026 for plan submitted 10/22/2026. Submit Date updated to now. Plan now open for review. | | | 2373887 |
| Energy | Original | / | 10/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2373879 |
| Floodplain | Original | N | 10/22/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6407402012) | | Floodplain | 2373878 |