Black Forest Fire | Original | A | 11/1/2013 | NELIDA | NELIDA | rch 10/28/13 | | Black Forest Fire | 668769 |
County Zoning | Original | A | 10/31/2013 | DSDSPAULDING | DSDSPAULDING | | | County Zoning | 668245 |
Health Dept. | Original | A | 10/28/2013 | HEALTHDEPT | HEALTHDEPT | ON0020428; Eval received; Existing owts permit on file for a 4 bedroom home; prop 4 bdrm; Approved; CJC | Chuck Cousino | Health Dept. | 667379 |
Out to Review | Original | / | 10/28/2013 | REBECCA | REBECCA | jay 439-9492 | | Out to Review | 667183 |
Finished Bin | Original | / | 10/25/2013 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 667153 |
Plan Coordinator | Original | / | 10/25/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 667150 |
Mechanical | Original | A | 10/25/2013 | RUSSELL | RUSSELL | | | Mechanical | 667149 |
Mechanical | Original | / | 10/25/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 667138 |
Mechanical | Original | / | 10/25/2013 | | REBECCA | Location = Mechanical by REBECCA | | Mechanical | 666986 |
Resubmittal 1 | Original | / | 10/25/2013 | REBECCA | REBECCA | Resubmittal #1 | | Resubmittal 1 | 666985 |
Construction | Original | A | 10/25/2013 | JIMA | JIMA | deck is on separate pages | | Construction | 666969 |
Out to Review | Original | / | 10/25/2013 | NELIDA | NELIDA | Jay 439-9492 | | Out to Review | 666957 |
Finished Bin | Original | / | 10/23/2013 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 666399 |
Plan Coordinator | Original | / | 10/23/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 666370 |
Mechanical | Original | D | 10/23/2013 | RUSSELL | RUSSELL | 6" diameter O.A. duct to be used as O.A., to be dampered per IECC requirements, not as combustion air for hi-efficiency furnace, it appears that the crawl space is un-conditioned, therefore, all ductwork to be insulated with minimum R-8, or if conditioned, coordinate with architectural drawings, combustion air requirements for the water heater in an unconditioned crawl space, need to see where the crawl space vents are located on architectural sheets, identify on main level duct plan if door shown at stairs is the crawl space access door, and if so size door to verify it meets size to equipment in crawl space, IECC indicates R-11 on crawl space walls, where's the S.A. & R. A. ducts in the crawl space? coordinate duct loss in heat loss calculations for what, unconditioned crawl space?, verify loss at floor for an unconditioned crawl space? | | Mechanical | 666369 |
Mechanical | Original | / | 10/23/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 666345 |
Mechanical | Original | / | 10/21/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 665904 |
Plan Coordinator | Original | / | 10/21/2013 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 665897 |
Construction | Original | D | 10/21/2013 | DANM | DANM | Provide location of crawl space access Clarify if crawl space is conditioned or unconditioned - indicate location of insulation on section (floor or wall?) See plans Walk OK | | Construction | 665896 |
Construction | Original | / | 10/21/2013 | DANM | DANM | In Current Review by DANM | | Construction | 665838 |
Construction | Original | / | 10/21/2013 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 665823 |
Plan Coordinator | Original | / | 10/21/2013 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 665788 |
Enumeration | Original | A | 10/21/2013 | AMY | AMY | This home was destroyed in the Blackforest Fire. | | Enumeration | 665786 |
Floodplain | Original | N | 10/18/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 665348 |