Health Dept. | Original | A | 1/8/2015 | HEALTHDEPT | HEALTHDEPT | OWTS Permit ON0033859 issued 1/8/15. Mike McCarthy | mmccarthy | Health Dept. | 755388 |
Mechanical | Original | A | 12/17/2014 | TCRIPPEN | TCRIPPEN | | | Mechanical | 752265 |
Mechanical | Original | D | 12/15/2014 | TCRIPPEN | TCRIPPEN | missing equipment certificate | | Mechanical | 751263 |
Electronic Plan | Original | / | 12/15/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 751261 |
Resubmittal 2 | Original | / | 12/11/2014 | MINDY | MINDY | Resubmittal #2 | | Resubmittal 2 | 750985 |
Health Dept. | Original | D | 12/11/2014 | HEALTHDEPT | HEALTHDEPT | The existing OWTS (ON0033859) was installed and approved in 1986 for a 3 bedroom house. The new plans are for a 4 bedroom house. Per the regulations the existing soil treatment area is undersized, and requires an additional 300 sq.ft. of soil treatment area. The existing 1,500 gallon septic tank is adequate for use for the 4 bedroom house. A Major Repair OWTS permit is required for the required soil treatment area addition, and must be issued prior to approval of the plans. Mike McCarthy | mmccarthy | Health Dept. | 750843 |
Mechanical | Original | D | 12/10/2014 | TCRIPPEN | TCRIPPEN | okay one more try in the mechanical duct design plan box you should have only M-1 M-2 and M-3, the rest will go into the heat loss cals- equipment box. do not resubmit the IECC with your cals it is already approved and in the correct box thank you | | Mechanical | 750515 |
Construction | Original | A | 12/10/2014 | DANM | DANM | | | Construction | 750498 |
Resubmittal 1 | Original | / | 12/10/2014 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 750441 |
Health Dept. | Original | D | 11/24/2014 | HEALTHDEPT | HEALTHDEPT | Contact Health Department for onsite wastewater treatment system requirements. MYM 578-3199 | Michelle Martinez | Health Dept. | 747490 |
Mechanical | Original | D | 11/21/2014 | TCRIPPEN | TCRIPPEN | You have up loaded incorrectly the mechanical duct design plan is for the duct lay only . Heat loss cals and equipment certificate is for the rest of heating cals and furnace data.The IECC belongs in the IECC form and building cals not heating cals. No review until up loaded correctly. Thank you | | Mechanical | 747325 |
Construction | Original | D | 11/21/2014 | DANM | DANM | Label use of all spaces on lower level Clarify type and support of circular stair Provide at least one building section noting required information Specify window types on main level Provide attic access sizes and locations Provide missing headers, beam and ledger sizes on main floor framing Provide no. of plies and material of bottom chords for trusses GT6A-GT6C Locate trusses GTJ1, J08-J10, J12, J13, J16 on roof framing Clarify various girder trusses Clarify missing header Do not include heat load calculations with IECC Certificate See plans | | Construction | 747309 |
County Zoning | Original | A | 11/20/2014 | DSDARCHULETA | DSDARCHULETA | | | County Zoning | 746916 |
Zoning/Planning | Original | / | 11/19/2014 | DSDARCHULETA | DSDARCHULETA | In Current Review by DSDARCHULETA | | Zoning/Planning | 746580 |
Electronic Plan | Original | / | 11/18/2014 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 746560 |
Enumeration | Original | A | 11/18/2014 | AMY | AMY | | | Enumeration | 746289 |
Electronic Plan | Original | / | 11/18/2014 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 746288 |
Floodplain | Original | N | 11/17/2014 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 746160 |