COLORADO STRUCTURES INC | B= | C | 05/17/2016 | splice complete | DANE | DANE | | B= | C | 5200617 |
COLORADO STRUCTURES INC | BSP | T | 05/13/2016 | PAID (REC#1329535) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add partition wall | MICHAELA | MICHAELA | | BSP | T | 5199449 |
COLORADO STRUCTURES INC | B= | P | 05/12/2016 | bathroom in rear of unit OK / storage room wall at rear of unit is shown as a future wall on plans and needs to be splice into plans / once spliced into plans it is OK for final -- Schedule a new Building Final when above items are complete. | DANE | DANE | | B= | P | 5198408 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 05/06/2016 | | BRET | BRET | | E= | C | 5193632 |
E LIGHT ELECTRIC SERVICES, INC | ESL | C | 04/15/2016 | 4 floor boxes. | BRET | BRET | | ESL | C | 5178134 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 04/12/2016 | walls | BRET | BRET | | ER | P | 5176824 |
JLC ELECTRIC LLC | E= | C | 03/23/2016 | | BRET | BRET | | E= | C | 5161014 |
JLC ELECTRIC LLC | E= | P | 03/22/2016 | gfci protect receptacle within 6' of mop sink, 40 amp max on rtu no power exhaust. 45 amp fuses and 50 amp breaker installed. | BRET | BRET | | E= | P | 5160236 |
JLC ELECTRIC LLC | E= | R | 02/23/2016 | -------------------Before final, plans must be revised and resubmitted to show the RTU and electric water heater on panel schedule, also remove temp lighting and any other incorrect information from panel schedule-------------- | DEAN | DEAN | | E= | R | 5140575 |
JLC ELECTRIC LLC | ER | P | 02/04/2016 | walls ok attach to 110 permit to cover demising wall rough | BRET | BRET | | ER | P | 5128347 |
JLC ELECTRIC LLC | ESL | C | 12/22/2015 | | BRET | BRET | | ESL | C | 5104016 |
RL CHECKETTS HVAC | H= | C | 04/07/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5172671 |
BOCHNAK MECHANICAL, INC. | H= | C | 04/06/2016 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 5171128 |
BOCHNAK MECHANICAL, INC. | H= | P | 04/05/2016 | NO LADDER TO ACCESS ROOF, STILL NEED TO SEE REGULATOR AND LABELS. | NANCY | NANCY | | H= | P | 5170662 |
RL CHECKETTS HVAC | H= | P | 04/01/2016 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5167424 |
RL CHECKETTS HVAC | H= | P | 03/29/2016 | PLUMBING VENT TO BE 10 FEET AWAY OR 3 FEET ABOVE RTU ECONOMIZER. PERMANENTLY LABEL RTU WITH NUMBER 120. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5165067 |
BOCHNAK MECHANICAL, INC. | H= | P | 03/07/2016 | FOR FINAL NEED LETTER FROM CSPU APPROVING MEDIUM PRESSURE GAS FOR THIS ADDRESS. INSTALL ADDRESS TAG, MEDIUM PRESSURE LABELS, REGULATOR AND PROTECTION FOR GAS LINE UNDER LADDER. | NANCY | NANCY | | H= | P | 5149177 |
BOCHNAK MECHANICAL, INC. | HC | C | 03/07/2016 | OK TO SET 2 POUND METER. | NANCY | NANCY | | HC | C | 5149176 |
BOCHNAK MECHANICAL, INC. | HI | C | 03/07/2016 | 10 POUND TEST OK. INSTALLED AS PER PRINTS. | NANCY | NANCY | | HI | C | 5149172 |
BOCHNAK MECHANICAL, INC. | H= | P | 03/03/2016 | NOT READY FOR FINAL. | NANCY | NANCY | | H= | P | 5147559 |
BOCHNAK MECHANICAL, INC. | HI | P | 03/03/2016 | NO ROOF ACCESS TO SEE WHICH GAS LINE IS GOING TO EACH SUITE AND TO VERIFY INSTALLATION TO PRINTS. INSTALL ADDRESS TAG. STILL NEED PRESSURE TEST FOR NEXT HI INSPECTION. 10 LB TEST OK TODAY | NANCY | NANCY | | HI | P | 5147558 |
RL CHECKETTS HVAC | HD | P | 02/23/2016 | NEED GAS CONTRACTOR ATTACHED TO PERMIT. ROUGH TRUNK LINES AND LATERALS OK.. BATH EXHAUST ABOVE CEILING OK. NO DIFFUSERS OR ROOF YET. | NANCY | NANCY | | HD | P | 5140568 |
BOCHNAK MECHANICAL, INC. | P= | C | 03/16/2016 | WATER HEATER INSTALLED , TEMPERING AT LAV . ALL TO PLAN | GABE | GABE | | P= | C | 5156444 |
BOCHNAK MECHANICAL, INC. | P= | R | 03/15/2016 | SHOULD BE TRIP FEE , NO HOT WATER , NO POWER TO DRINKING FOUNTAINS , WAIVED THIS TIME ONLY | GABE | GABE | | P= | R | 5155202 |
BOCHNAK MECHANICAL, INC. | P= | L | 03/14/2016 | CONTRACTOR CANCELED | GABE | GABE | | P= | L | 5154370 |
BOCHNAK MECHANICAL, INC. | PTO | C | 02/25/2016 | per plan, check water heater at final. | TAYLOR | TAYLOR | | PTO | C | 5142473 |
BOCHNAK MECHANICAL, INC. | PTO | R | 02/24/2016 | not ready, nothing on test. | TAYLOR | TAYLOR | | PTO | R | 5141209 |