MANS HOMES, LLC | B= | C | 02/22/2017 | | NELIDA | NELIDA | | B= | C | 5421103 |
COPPER MINE PLUMBING AND HEATING INC. | BSP | T | 02/16/2017 | PAID (REC#1402987) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 2-16- 17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5416786 |
MANS HOMES, LLC | B= | P | 02/15/2017 | Temp CO: TO OCCUPY ( Expires: 3/17/2017 12:00:00 AM) | REBECCA | REBECCA | | B= | P | 5416439 |
MANS HOMES, LLC | B= | P | 02/10/2017 | Building final complete pending all other final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), MAUI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5412032 |
MANS HOMES, LLC | BSP | P | 01/05/2017 | grid ceiling ok | ERICR | ERICR | | BSP | P | 5383347 |
MANS HOMES, LLC | BSP | P | 12/16/2016 | Letter for fire caulk around beam on file // Corrections from previous inspection complete | JEREMYA | JEREMYA | | BSP | P | 5370958 |
MANS HOMES, LLC | BSP | P | 12/08/2016 | Need epentration details for all penetrating items at U497 walls (beams, conduits, boxes etc.) // Need to address wall that is stopping continuity of U497 wall at west end of space. Rated assembly was built over to wall, stopped, then restarted on other side of wall rather than passing behind it // Need termination details at exterior walls for the rated assemblies on each side of space // Discussed egress and accessiblity components with contractor and owner | JEREMYA | JEREMYA | | BSP | P | 5363451 |
MANS HOMES, LLC | BSP | T | 12/05/2016 | PAID (REC#1386952) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add new wall design - OK per AJE | MICHAELA | MICHAELA | | BSP | T | 5359797 |
MANS HOMES, LLC | BFR | P | 11/22/2016 | interior walls need backing in bathrooms for grab bars / need other roughs completed | ERICR | ERICR | | BFR | P | 5351383 |
MANS HOMES, LLC | BSP | R | 11/22/2016 | need to run fire barrier to under side of roof sheeting/ need rated electrical boxes in fire barrier wall / need a UL listing for protecting penetrations through fire barrier / Fire barrier stops at unrated horizontal assembly | ERICR | ERICR | | BSP | R | 5351378 |
STARZ PLUMBING AND HEATING INC. | BSP | T | 10/25/2016 | PAID (REC#1375478) PLAN SPLICE FEE: $50 by: DALEH for Plumbing | DALEH | DALEH | | BSP | T | 5326747 |
MANS HOMES, LLC | BSP | P | 10/14/2016 | reviewed fire wall detail | ERICR | ERICR | | BSP | P | 5319297 |
THE PLUG ELECTRIC, LLC | E= | C | 01/30/2017 | | CRAIGS | CRAIGS | | E= | C | 5401799 |
THE PLUG ELECTRIC, LLC | EP | C | 01/27/2017 | | CRAIGS | CRAIGS | | EP | C | 5400848 |
THE PLUG ELECTRIC, LLC | E= | R | 01/27/2017 | add gfci protected receptacle at the warming counter and remove splice in the lighting cord ---- gfci protect the receptacle above the coke cooler ---- label panel correctly --- verify ahu breaker 30 amp max -- verify roof top receptacle that panel schedule calls for is there --- | CRAIGS | CRAIGS | | E= | R | 5400842 |
THE PLUG ELECTRIC, LLC | ER | C | 01/27/2017 | | CRAIGS | CRAIGS | | ER | C | 5400839 |
THE PLUG ELECTRIC, LLC | E= | P | 01/26/2017 | dining room / office / rest rooms ----- OK still need to inspect the kitchen / panels / roof top units | CRAIGS | CRAIGS | | E= | P | 5399474 |
THE PLUG ELECTRIC, LLC | ER | C | 01/26/2017 | above ceiling in the dining room -- kitchen ceiling not in this scope of work | CRAIGS | CRAIGS | | ER | C | 5399467 |
THE PLUG ELECTRIC, LLC | E= | R | 01/25/2017 | remove tiles around the lights so I can inspect above ceiling ---- the final will likely take two inspections --- make sure there are no gfci behind equipment and all receptacles are gfci protected in the kitchen | CRAIGS | CRAIGS | | E= | R | 5398376 |
THE PLUG ELECTRIC, LLC | ER | P | 11/23/2016 | walls only | CRAIGS | CRAIGS | | ER | P | 5352982 |
MAUI MECHANICAL, INC. | H= | C | 02/15/2017 | HEAT FINAL COMPLETE.. | LUKE | LUKE | | H= | C | 5416324 |
MAUI MECHANICAL, INC. | H= | P | 02/15/2017 | TEST AND BALANCE REPORT OK.. | LUKE | LUKE | | H= | P | 5415457 |
MAUI MECHANICAL, INC. | H= | P | 02/10/2017 | TEST AND BALANCE REPORT REQUIRED, ALSO NEED C02 INSTALLED AND INTERLOCKED WITH ROOF TOP UNIT.. REST OK.. | LUKE | LUKE | | H= | P | 5412770 |
MAUI MECHANICAL, INC. | HD | P | 02/08/2017 | TWO LAYERS OF GREASE WRAP AND BANDING COMPLETE.. NOTE: NO ACCESS DOORS REQUIRED.. | LUKE | LUKE | | HD | P | 5410481 |
MAUI MECHANICAL, INC. | HD | P | 02/06/2017 | FIRST LAYER OF GREASE WRAP OK.. WILL NEED TO RE LIGHT TEST AT ROOF GREASE DUCT WAS CUT FREE TO INSTALL WRAP.. | LUKE | LUKE | | HD | P | 5407772 |
MAUI MECHANICAL, INC. | HD | P | 02/01/2017 | GREASE LIGHT TEST GOOD OK FOR FIRST LAYER OF GREASE WRAP... | LUKE | LUKE | | HD | P | 5404720 |
MAUI MECHANICAL, INC. | HC | C | 02/01/2017 | ADDED 800,000 TO LOAD. | LUKE | LUKE | | HC | C | 5404628 |
MAUI MECHANICAL, INC. | HI | C | 02/01/2017 | 10 LB GAS TEST GOOD RAN PER PLANS.. | LUKE | LUKE | | HI | C | 5404621 |
MAUI MECHANICAL, INC. | HD | R | 01/30/2017 | STILL HAVE HOLES IN BOTH GREASE DUCTS RIGHT AND LEFT SIDE OUTLETS.. WAIVED TRIP FEE TODAY.. | LUKE | LUKE | | HD | R | 5402052 |
MAUI MECHANICAL, INC. | HI | P | 01/30/2017 | LOW TEST GAS LINE RAN PER PLANS . NOTE: FOR FINAL NEED MEDIUM GAS STICKERS INSTALLED AND GAS REGULATORS ALL CONNECTED TO APPLIANCES.. | LUKE | LUKE | | HI | P | 5402047 |
MAUI MECHANICAL, INC. | HD | T | 01/27/2017 | PAID (REC#1398336): NOT READY, STILL HAVE HOLES IN GREASE DUCT MECHANICAL CONTRACTOR ON SITE STOPPED THE INSPECTION.. | LUKE | LUKE | | HD | T | 5400350 |
MAUI MECHANICAL, INC. | HD | P | 01/26/2017 | FIX HOLES IN TOP OF GREASE DUCT INSIDE CURB LEFT DUCT, FIX HOLES IN RIGHT HAND SIDE FIRST BUTT JOINT LEFT AND RIGHT CORNER FRONT OF STORE AND BACK SIDE LEFT CORNER 4'' DOWN FROM LAST BUTT JOINT. | LUKE | LUKE | | HD | P | 5399581 |
MAUI MECHANICAL, INC. | HD | P | 01/23/2017 | WILL NEED TO RE LIGHT TEST ALL GREASE DUCT.. NEED SOMEONE TO PULL A PERMIT FOR THE GAS.. NOTE: ALL ROUGH DUCT IN DINING ROOM OK FLEX AND DIFFUSERS ARE INSTALLED.. | LUKE | LUKE | | HD | P | 5396162 |
MAUI MECHANICAL, INC. | HD | P | 01/19/2017 | NO ONE SITE TO PERFORM LIGHT TEST. PLEASE RESCHEDULE. | NANCY | NANCY | | HD | P | 5392781 |
MAUI MECHANICAL, INC. | HD | P | 01/18/2017 | INSPECTOR WAS UNABLE ACCESS TOP OF HOOD - STOPPED INSPECTION | JERRYF | JERRYF | | HD | P | 5392103 |
MAUI MECHANICAL, INC. | HD | R | 01/17/2017 | NEED TO VERIFY GREASE DUCT WITH LIGHT TEST | JERRYF | JERRYF | | HD | R | 5389463 |
MAUI MECHANICAL, INC. | HD | P | 01/13/2017 | ROUGH DUCT IN DINING ROOM SIDE IS MISSING A 8'' SUPPLY AND HOW ARE YOU GOING TO GET RETURN AIR PATH FROM DINING ROOM SEPARATION WALL GOES TO DECK. THIS IS A RETURN AIR PLENUM CEILING. ALL NEW MATERIALS IN PLENUM CEILING RETURN NEEDS TO BE RATED OR ISOLATED. NOTE: BATH FANS ARE INSTALLED AND EXHAUST FROM FANS GO THROUGH ROOF STILL NEED TO SEE ROOF. | LUKE | LUKE | | HD | P | 5389163 |
MAUI MECHANICAL, INC. | HD | L | 01/04/2017 | NOT READY STOPPED INSPECTION - NEED CONTRACTOR TO VERIFY PROPER SIZE OF DUCT AT OFFSETS APPEARS TO BE REDUCED - HAD CONSULT WITH PETER FROM MAUI MECHANICAL - AT NEXT INSPECTION NEED SMALLER INSPECTOR - NEED WASH ABLE SURFACE TO EXTEND 18" ABOVE HOOD - RE INSPECT ALL | JERRYF | JERRYF | | HD | L | 5382386 |
COPPER MINE PLUMBING AND HEATING INC. | P= | C | 02/17/2017 | ok. correction made. | JOHNS | JOHNS | | P= | C | 5418963 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 02/16/2017 | NEED TO REMOVE GAS CONNECTOR AT HOOD WATER , REST OK NOTE : WATER LINE TO MAU VERIFIED , PLANS HAVE BEE SPLICED , VERIFIED ON SITE | GABE | GABE | | P= | P | 5417572 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 02/07/2017 | Changed to partial, Mechanical inspector noticed water lines added to job that are not on the plumbing plan. Need to revise plans and call for inspection. Water lines to rtu and grease hood | JOEL | JOEL | | P= | P | 5408698 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 02/06/2017 | left side toilet lacks side clearance has 15-1/2'', needs 16'' minimum, needs backflow protection for ice maker | JOEL | JOEL | | P= | P | 5407132 |
STARZ PLUMBING AND HEATING INC. | PTO | C | 11/23/2016 | received image | TED | TED | | PTO | C | 5352172 |
STARZ PLUMBING AND HEATING INC. | PB | C | 11/23/2016 | image received | TED | TED | | PB | C | 5352169 |
STARZ PLUMBING AND HEATING INC. | PTO | P | 11/16/2016 | changed from p= to pto, need base inspection completed (was told contractor was going to attach pictures to permit under images of the fix and recall base inspection or recall base for on site inspection), note: pto can be completed after base is completed | TED | TED | | PTO | P | 5345948 |
STARZ PLUMBING AND HEATING INC. | PB | P | 10/26/2016 | 2 traps on one trap arm at front counter floor sink connected to sanitary, reconnect front hand sink drain under floor, note: grease drain and trap ok | TED | TED | | PB | P | 5328618 |
STARZ PLUMBING AND HEATING INC. | PB | R | 10/19/2016 | grease trap is too deep, the outlet connected to building drain is above the trap lid, need permit to cover full scope of work, need plan revised | TED | TED | | PB | R | 5322597 |