EPIC CONSTRUCTION, INC. | B= | C | 10/14/2021 | All other required Final inspections are complete. (This is a computer generated result) | DAKOTAB | DAKOTAB | | B= | C | 7141751 |
EPIC CONSTRUCTION, INC. | B= | P | 10/06/2021 | Items from previous inspection corrected -- Building final OK pending other finals. Additional Inspections Required (computer generated): ELECTRIC TECH INC. Electrical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 7132463 |
EPIC CONSTRUCTION, INC. | B= | P | 09/28/2021 | Need to install all partitions in restroom -- Sink height in both restrooms currently at 34 1/2" -- Pending other finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ELECTRIC TECH INC. Electrical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 7123284 |
EPIC CONSTRUCTION, INC. | BSP | P | 09/28/2021 | Training with Dakota / Discussed accessibility requirement and building final requirements | CHAD | CHAD | | BSP | P | 7123282 |
EPIC CONSTRUCTION, INC. | BFR | P | 08/05/2021 | Interior light gauge frame OK pending other roughs -- Reviewed need for Core/Shell permit to be completed prior to interior finish permit completed -- Reviewed Accessible Elements -- Training with Erik | DAKOTAB | DAKOTAB | | BFR | P | 7062686 |
EPIC CONSTRUCTION, INC. | BSP | P | 08/05/2021 | Training with Dakota on steel stud framing, kitchen hood types, A occupancy, and fire treated backing / | ERIKK | ERIKK | | BSP | P | 7062685 |
EPIC CONSTRUCTION, INC. | BFR | P | 07/26/2021 | HOOD WALL FRAME -- Light gauge frame at kitchen hood wall OK pending mechanical -- Reviewed frame inspection requirements and accessible elements with site rep. | DAKOTAB | DAKOTAB | | BFR | P | 7049568 |
ELECTRIC TECH INC. | E= | C | 10/14/2021 | | BRET | BRET | | E= | C | 7141750 |
ELECTRIC TECH INC. | E= | P | 09/29/2021 | pending series rating paperwork of panels, and aic calculations and labels for rooftop equipment | BRET | BRET | | E= | P | 7123825 |
ELECTRIC TECH INC. | E= | P | 09/27/2021 | reverse polarity exterior patio receptacle, open boxes at phone board location, Install 15 amp breaker for hood control circuit, need aic calculations for panel and roof top equipment, need series rating paper work and labels for panels, cord grips for patio festoon lighting gfci protect cooler receptacle within 6' of bar sink | BRET | BRET | | E= | P | 7120846 |
ELECTRIC TECH INC. | E= | P | 09/23/2021 | roof only, need to resubmit plans with series rating and aic calculations of all root top equipment, breaker oversized for one exhaust fan | BRET | BRET | | E= | P | 7117687 |
ELECTRIC TECH INC. | ER | P | 09/20/2021 | ceilings except 2 lighting control j-boxes and fixture by back door | BRET | BRET | | ER | P | 7112678 |
ELECTRIC TECH INC. | ER | P | 08/11/2021 | hard lid complete | BRET | BRET | | ER | P | 7068596 |
ELECTRIC TECH INC. | ER | P | 08/10/2021 | walls complete | BRET | BRET | | ER | P | 7066485 |
ELECTRIC TECH INC. | ER | P | 08/09/2021 | office switch wall | BRET | BRET | | ER | P | 7065009 |
ELECTRIC TECH INC. | ER | P | 08/05/2021 | walls ok except panel and switch bank walls | BRET | BRET | | ER | P | 7061813 |
ELECTRIC TECH INC. | ER | P | 08/04/2021 | walls marked with x's on plans still need looked at | RANDY | RANDY | | ER | P | 7059855 |
ELECTRIC TECH INC. | ER | P | 07/26/2021 | 2 - Hoods, common wall only - Ok | BRETC | BRETC | | ER | P | 7048945 |
ELECTRIC TECH INC. | ESL | C | 07/12/2021 | | BRET | BRET | | ESL | C | 7032056 |
AIRTECH MECHANICAL, INC. | H= | C | 09/24/2021 | CORRECTIONS MADE, SEE IMAGES / MECHANICAL FINAL OK | WHITNEYH | WHITNEYH | | H= | C | 7120013 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | C | 09/24/2021 | GAS AND WATER HEATER VENT FINAL OK / | WHITNEYH | WHITNEYH | | H= | C | 7119217 |
YOUNGERS COMMERCIAL SERVICES, LLC | H= | C | 09/24/2021 | REFRIGERATION FINAL OK | WHITNEYH | WHITNEYH | | H= | C | 7119214 |
AIRTECH MECHANICAL, INC. | H= | P | 09/24/2021 | RECEIVED REVISED TAB REPORT, WILL UPLOAD TO IMAGES BY END OF DAY / INTERLOCK VERIFIED / ALL FLEX AND DIFFUSERS OK / THERMOSTATS INSTALLED / SMOKE DETECTORS, CONDENSATE DRAINS AND REMOTE INDICATORS OK FOR RTU 1-3 / ROOF OK EXCEPT TEF 2 EXHAUST TERMINATION CLEARANCE TO RTU-2 ECONOMIZER AND SEAL BETWEEN GREASE DUCT AND TERMINATION PLATE FOR HOODS KEF-1 AND KEF- 2 / OK FOR CONTRACTOR TO ATTACH IMAGES OF CORRECTIONS TO AN INSPECTION REQUEST / | WHITNEYH | WHITNEYH | | H= | P | 7119196 |
AIRTECH MECHANICAL, INC. | HSP | P | 09/24/2021 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES / QUESTIONING EXHAUST READING FOR KEF-1 AS TEST REPORT REFLECTS 990 CFMS AND LISTING IS 2925 CFMS / NO TEST READING FOR KEF-3 / CONTRACTOR TO SUBMIT REVISED TEST AND BALANCE REPORT / | WHITNEYH | WHITNEYH | | HSP | P | 7118703 |
PRESTIGE MECHANICAL CONTRACTORS,INC | H= | P | 09/20/2021 | GAS FINAL PENDING: NEED TO COMPLETE HV INSPECTION. NEED ALL QUICK DISCONNECTS AND RESTRAINTS INSTALLED ON COOKING EQUIPMENT. CONNECT GAS TO PATIO HEATER. / ALL MEDIUM PRESSURE STICKERS AND REGULATORS INSTALLED. | DUSTINS | DUSTINS | | H= | P | 7112611 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HV | P | 09/20/2021 | WATER HEATER VENT TERMINATION NEEDS TO MEET REQUIREMENTS OF PAGE 25 IN THE INSTALLATION INSTRUCTIONS. | DUSTINS | DUSTINS | | HV | P | 7112591 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | C | 09/20/2021 | 10 LB TEST OK FOR GAS PIPING TO PATIO HEATER. PIPING PER PLAN. ALL GAS PIPING COMPLETE. | DUSTINS | DUSTINS | | HI | C | 7112588 |
AIRTECH MECHANICAL, INC. | HD | P | 09/03/2021 | MAKE UP AIR MAIN TRUNK OK, OK TO WRAP. CONNECTIONS TO HOOD 1 OK. NEED TO COMPLETE CONNECTIONS TO HOOD 2 AND HOOD 3. KEEP WRAP FOR MAKE UP AIR DUCTS 18" MINIMUM FROM TOP OF HOOD. | DUSTINS | DUSTINS | | HD | P | 7097431 |
AIRTECH MECHANICAL, INC. | HD | P | 09/02/2021 | HOOD WALL CLEAR OF COMBUSTIBLE MATERIAL. | DUSTINS | DUSTINS | | HD | P | 7095402 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HV | P | 09/02/2021 | WATER HEATER VENT LACKS SUPPORT. MISSING COMBUSTION AIR CONDENSATE DRAIN LINE PER PAGE 25 FIGURE 20. TERMINATION INCOMPLETE, WILL NEED TO MEET REQUIREMENTS OF INSTALLATION INSTRUCTIONS ON PAGE 25 AND 3' ABOVE OR 10' AWAY FROM ECONOMIZER WITHIN 10'. | DUSTINS | DUSTINS | | HV | P | 7095391 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | P | 09/02/2021 | 10 LB TEST OK FOR COOK LINE GAS PIPING, PIPING PER PLAN. 10 LB TEST OK FOR WATER HEATER GAS PIPING. PIPING PER PLAN. STILL NEED TO SEE GAS PIPING COMPLETE FOR PATIO HEATERS. CHECK MEDIUM PRESSURE STICKERS, REGULATORS AND CONNECTIONS TO EQUIPMENT AT FINAL. OUTDOOR REGULATORS NEED TO HAVE APPROVED VENT CAPS BY FINAL. | DUSTINS | DUSTINS | | HI | P | 7095378 |
AIRTECH MECHANICAL, INC. | HD | P | 08/24/2021 | NON-COMBUSTIBLE MATERIAL MUST BE REMOVED FROM HOOD WALL / ECONOMIZER LACKS 10' CLEARANCE TO PLUMBING EXHAUST VENT AND BATHROOM EXHAUST VENT AT ROOF-TOP / --INSPECTION COMPLETE ON REPAIRED HOLES IN ALL GREASE DUCTS FROM DROP CONNECTION TO HOOD CONNECTION / OK TO WRAP 1ST AND 2ND LAYERS, CONTRACTOR TO TAKE IMAGES OF FIRST LAYER FOR REVIEW AT INSPECTION OF SECOND LAYER / | WHITNEYH | WHITNEYH | | HD | P | 7082779 |
AIRTECH MECHANICAL, INC. | HD | P | 08/23/2021 | ALL COMBUSTIBLES TO BE REMOVED FROM HOOD-WALL FROM FLOOR TO 18 INCHES ABOVE TOP OF HOOD / REPAIR ALL HOLES IN GREASE DUCTS SERVING HOODS 1-3 / ECONOMIZER LACKS 10' HORIZONTAL CLEARANCE TO PLUMBING EXHAUST VENT AND BATHROOM EXHAUST AT ROOF-TOP / | WHITNEYH | WHITNEYH | | HD | P | 7081350 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HC | C | 08/17/2021 | OK TO SET 2 LB METER AT THIS ADDRESS. | DUSTINS | DUSTINS | | HC | C | 7075205 |
PRESTIGE MECHANICAL CONTRACTORS,INC | HI | P | 08/17/2021 | NEED REFRIGERATION CONTRACTOR TO ATTACH TO PERMIT. 10 LB TEST OK. PIPING PER PLAN TO ALL EQUIPMENT ON ROOF. NEED TO SEE GAS PIPING COMPLETED TO WATER HEATER, COOK LINE AND PATIO HEATERS. (ALL THREE CAPPED IN CEILING LOCATION OF EQUIPMENT) CHECK MEDIUM PRESSURE STICKERS, REGULATORS AND CONNECTIONS TO EQUIPMENT AT FINAL. OUTDOOR REGULATORS NEED TO HAVE APPROVED VENT CAPS BY FINAL. | DUSTINS | DUSTINS | | HI | P | 7075197 |
AIRTECH MECHANICAL, INC. | HD | P | 08/17/2021 | GREASE DUCT LIGHT TEST AT CONTRACTORS SHOP. NO HOLES FOUND IN THREE DUCT DROPS SIGNED AND DATED. OK TO WRAP WITH TWO LAYERS AND INSTALL THROUGH CURB. CONTRACTOR TO PROVIDE PICTURES OF FIRST LAYER. | DUSTINS | DUSTINS | | HD | P | 7074569 |
AIRTECH MECHANICAL, INC. | HD | P | 07/23/2021 | NEED GAS CONTRACTOR AND REFRIGERATION CONTRACTOR TO ATTACH TO PERMIT. HOOD WALL CLEAR OF COMBUSTIBLE MATERIALS. BATH EXHAUST NOT COMPLETE. RTU-1, RTU-2 AND RTU-3 SUPPLY AIR MAIN TRUNKS AND LATERALS OK, OK TO WRAP EXCEPT 12" SUPPLY AIR ABOVE BATHROOMS FOR RTU-3 NOT COMPLETE.. RTU-1, RTU-2 AND RTU-3 RETURN AIR DUCTS OK EXCEPT RTU-1 RETURN AIR TAPS NOT INSTALLED. MAKE UP AIR MAIN TRUNK OK EXCEPT NOT COMPLETE THROUGH ROOF, NO LATERALS INSTALLED YET. NO KITCHEN EXHAUST DUCTS INSTALLED YET. NO ROOF TODAY. | DUSTINS | DUSTINS | | HD | P | 7047314 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 10/11/2021 | engineer letter for cart iron and copper water received, chemical dispenser at 3 comp sink has asse 1055 rating, drain down tee installed at mop sink for chemical dispenser see image, plan splice done | JOSEPHD | JOSEPHD | | P= | C | 7136378 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 10/07/2021 | contractor to provide installation instructions for chemical dispenser at 3 comp sink needs to have asse 1055 rating or air gap per 608.13.9, chemical dispenser at mop sink needs to have a approved pressure bleed down device to protect vacuum breaker , need engineer letter for items from previous inspections, can not get plan splice to download will update notes once that is done, rest ok | JOSEPHD | JOSEPHD | | P= | P | 7133858 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 09/24/2021 | install partitions at restrooms and equipment at bar area, height at lavs exceed 34 inches, still need revised plans and engineers letter, missing stainer at floor sink for soda machine, need revised plans for approved connections at chemical dispenser above mop sink, need backflow protection at oven and proper air gaps through out, re- inspect all. | TAYLOR | TAYLOR | | P= | P | 7119203 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 08/04/2021 | WHERE IS DRAIN FOR ROOF HYDRANT? STILL NEED PLANS REVISION NOTED ON PB INSPECTION, NOTE/ Rest ok/ Check AAVs at final | CODYP | CODYP | | PTO | P | 7060812 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 08/02/2021 | Need all VTR penetrations, toilet flanges, roof hydrant installed with drain / need plans revision noted on PB inspection / rest ok. Note: Need engineers letter for L copper on overhead mains and hood wall, cast DWV hood wall, and CPVC on soda feed line / 1 AAV beverage and 1 AAV at bar / check water heater, backflows, and mechanical room piping at final. | DANR | DANR | | PTO | P | 7056972 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 07/26/2021 | hood wall ok, need engineers approval for cast iron and copper piping. | TAYLOR | TAYLOR | | PTO | P | 7048649 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PB | P | 07/07/2021 | revise plans for new sizing and layout, note: test ok. | TAYLOR | TAYLOR | | PB | P | 7026857 |
PRESTIGE MECHANICAL CONTRACTORS,INC | XPS | T | 09/28/2021 | PAID (REC#1811155): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 4 revisions: adjusted sheet P3.0 and P4.0. | SHANEN | SHANEN | | XPS | T | 7121760 |