J. J. O'DONNELL CONSTRUCTION LTD | B= | P | 09/26/2007 | NEED BALANCE REPORT TO COMPLETE HVAC INSPECTION / FIRE INSPECTION COMPLETED ; 9 - 25 - 07 BY DAC. | BOBB | BOBB | | B= | P | 3560734 |
J. J. O'DONNELL CONSTRUCTION LTD | B= | C | 09/26/2007 | SEE H= FOR BALANCE REPORT AND F= COMPLETE | KIM | KIM | | B= | C | 3560727 |
J. J. O'DONNELL CONSTRUCTION LTD | BFR | P | 08/20/2007 | FRAME INSPECTION OK WITH OTHER ROUGH INSPECTIONS. | BOBB | BOBB | | BFR | P | 3560720 |
D & J QUALITY ELECTRIC INC | E= | C | 09/24/2007 | | MIKEC | MIKEC | | E= | C | 3560712 |
D & J QUALITY ELECTRIC INC | E= | P | 09/21/2007 | RTU BREAKER TOO LARGE [50 AMP]---NEED 40 AMP MAXIMUM | THOMAS | THOMAS | | E= | P | 3560704 |
D & J QUALITY ELECTRIC INC | ER | P | 09/20/2007 | GRID CIELINGS GOOD | THOMAS | THOMAS | | ER | P | 3560696 |
D & J QUALITY ELECTRIC INC | ES | C | 08/24/2007 | COMMERCIAL SERVICE: 200A, 4W, TAGGED 4037, D AND J ELECT | GARYL | GARYL | | ES | C | 3560688 |
D & J QUALITY ELECTRIC INC | ES | R | 08/21/2007 | SEE OTHER SERVICE INSPECTION THIS DATE. | DAVID | DAVID | | ES | R | 3560680 |
D & J QUALITY ELECTRIC INC | ER | R | 08/21/2007 | NO ROUGH INSPECTION ON THIS TRIP, ALREADY BEING SHEETROCKED. | DAVID | DAVID | | ER | R | 3560672 |
D & J QUALITY ELECTRIC INC | ES | R | 08/21/2007 | SECURE SERVICE CONDUIT PER NEC (EVERY 10' AND EVERY 3' FROM A TERMINATION POINT PANELS, LB'S, ETC...) | DAVID | DAVID | | ES | R | 3560664 |
D & J QUALITY ELECTRIC INC | ER | P | 08/16/2007 | WALLS AND HARD LIDS OK.-----------NEED TO STRAP CONDUITS ABOVE MAIN PANEL-------------------- | DEAN | DEAN | | ER | P | 3560657 |
D & J QUALITY ELECTRIC INC | ER | P | 08/15/2007 | EAST WALL BOXES NEED SUPPORT(NO SHEETROCK ON BACK SIDE OF WALL),OTHER WALLS OK | SHELBY | SHELBY | | ER | P | 3560649 |
D & J QUALITY ELECTRIC INC | ESL | C | 08/01/2007 | | DAVID | DAVID | | ESL | C | 3560642 |
HVAC SOLUTIONS, INC. | H= | C | 09/26/2007 | RECEIVED BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 3560875 |
HVAC SOLUTIONS, INC. | H= | P | 09/25/2007 | NEED BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3560868 |
HVAC SOLUTIONS, INC. | HV | C | 09/24/2007 | WATER | LYNNS | LYNNS | | HV | C | 3560859 |
HVAC SOLUTIONS, INC. | HV | C | 09/24/2007 | WATER | LYNNS | LYNNS | | HV | C | 3560852 |
HVAC SOLUTIONS, INC. | HD | C | 09/24/2007 | ROUGH DUCT AND INSULATION. FOR FINAL NEED TO SEE INTERLOCK AND BALANCE REPORT | LYNNS | LYNNS | | HD | C | 3560844 |
O' DONNELL PLUMBING | H= | C | 09/21/2007 | GAS FINAL ONLY... DOUBLE CHECK GAS CONNECTIONS ON ROOF AT HVAC FINAL. NOTE TO BUILDING CONTRACTOR ONLY ONE INSPECTION CALLED TO DATE ON HVAC. NO PERMIT FOR WATER HEATER AND VENT, WITH INSPECTIONS CALLED. ALSO ALL IS CONCEALED AT THIS TIME IN KITCHEN FOR TYPE 1 HOOD. | JON | JON | | H= | C | 3560799 |
O' DONNELL PLUMBING | HC | C | 09/17/2007 | OK FOR METER. | JON | JON | | HC | C | 3560791 |
O' DONNELL PLUMBING | HI | C | 09/17/2007 | GAS TO PLANS 5- STUBS... 10 LB TEST. COOKLINE APPLAINCE CONNECTIONS FOR FINAL. | JON | JON | | HI | C | 3560783 |
HVAC SOLUTIONS, INC. | HD | P | 08/29/2007 | GREASE DUCT OK TO WRAP. | LYNNS | LYNNS | | HD | P | 3560835 |
O' DONNELL PLUMBING | P= | C | 09/21/2007 | | JEFF | JEFF | | P= | C | 3560828 |
O' DONNELL PLUMBING | P= | R | 09/17/2007 | MARK O'DONNEL FIELD CANCELLED | JEFF | JEFF | | P= | R | 3560819 |
O' DONNELL PLUMBING | PTO | C | 08/17/2007 | | JEFF | JEFF | | PTO | C | 3560812 |
O' DONNELL PLUMBING | PB | C | 07/27/2007 | | JEFF | JEFF | | PB | C | 3560806 |