GREAT WEST CONSTRUCTION, LLC | B= | C | 05/28/2009 | | DANF | DANF | | B= | C | 3839369 |
GREAT WEST CONSTRUCTION, LLC | BSP | P | 04/21/2009 | LETTER FROM ARTHITECT RE QUESTION ON HANDRAIL AT STAGE AND ACCESSIBLE BATHROOM AT WOMEN BATHROOM; CALL SUPER AND OKED ONE HANDRAIL AT STEPS AND 5' CLEAR SPACE NOT REQUIRED BECAUSE ALREADY EXISTING ACCESSIBLE WATERCLOSET AREA | DANF | DANF | | BSP | P | 3825884 |
GREAT WEST CONSTRUCTION, LLC | B= | P | 04/10/2009 | 1) fire final 2) plumbing final 3) Guardrail at south mezzanine stairs less then 42" 4) handrail less then 34" same location 5) lower and upper mezzanine south side, latching hardware does not meet hardware exiting requirements 6) missing tempered glass in all prayer room doors 7) panic bar short hardware 8) exit path has roller door in pathway 9) missing vertical grab bar in bathrooms 10)bathroom need 6" base complete area of bath 11) missing handrail at stage stairs both sides 12)missing light above stairs to control room 13) women accessible requirements added stalls no 5' clear space | DANF | DANF | | B= | P | 3822690 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 03/19/2009 | eng. on file for stacking beam and south stairs | DALE | DALE | | BFR | P | 3814992 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 03/04/2009 | walls between prayer rooms upstairs ok / need all other roughs signed off | JOND | JOND | | BFR | P | 3808837 |
GREAT WEST CONSTRUCTION, LLC | BFT | C | 02/18/2009 | OPEN HOLE OBSERVATION LETTER ON FILE FROM MGA STRUCTURAL ENGINEERING, KEVIN J. ROTH #31463 | DANF | DANF | | BFT | C | 3803600 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 02/18/2009 | LETTER ON FILE FOR STRUCTURAL ELEMENTS OF WEST MEXXANINE AREA; MGA KEVIN J. ROTH, P.E. #31463 | DANF | DANF | | BFR | P | 3803597 |
GREAT WEST CONSTRUCTION, LLC | BSP | T | 02/12/2009 | PAID (REC#846818) ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH splice for change to wall and duct configuration | DALEH | DALEH | | BSP | T | 3801877 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 02/04/2009 | ENGINEER'S LETTER ON FILE FOR AV MEZZANINE AREA; NEED LETTER FOR WEST MEZZANINE FRAMING WELDING, BOLTING COLUMNS AND BEAMS | DANF | DANF | | BFR | P | 3798632 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 01/30/2009 | NEED ENGINEER'S LETTER WITH STAMP FOR DECK STEEL FRAMING OBSERVATION INACCORDANCE TO APPROVED PLANS; NEED OPENHOLE FOR PADS | DANF | DANF | | BFR | P | 3797317 |
GREAT WEST CONSTRUCTION, LLC | BSP | P | 01/30/2009 | walked with Dan | DALE | DALE | | BSP | P | 3797313 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 12/30/2008 | OK engineer to do steel decking frame and weld before pouring | JIMP | JIMP | | BFR | P | 3785985 |
GREAT WEST CONSTRUCTION, LLC | BFT | P | 12/01/2008 | all footins ok, need open hole | DALE | DALE | | BFT | P | 3776429 |
GREAT WEST CONSTRUCTION, LLC | BFT | P | 11/24/2008 | west half mesh and re-bar ok | DALE | DALE | | BFT | P | 3774509 |
GREAT WEST CONSTRUCTION, LLC | BFT | P | 11/18/2008 | ok except betweem grid line 5&6 | DALE | DALE | | BFT | P | 3771815 |
GREAT WEST CONSTRUCTION, LLC | BFT | R | 11/17/2008 | steel not per plan | DALE | DALE | | BFT | R | 3771108 |
WEST ELECTRIC GROUP, INC. | E= | C | 04/09/2009 | | MIKEC | MIKEC | | E= | C | 3821884 |
WEST ELECTRIC GROUP, INC. | EP | C | 04/03/2009 | PANELS AND TRANSFORMERS IN THE BASEMENT ELECTRIC ROOM,THE EXTERIOR ELECTRIC ROOM AND THE DIMMER ROOM | JERRY | JERRY | | EP | C | 3819889 |
WEST ELECTRIC GROUP, INC. | ER | C | 04/03/2009 | | JERRY | JERRY | | ER | C | 3819883 |
WEST ELECTRIC GROUP, INC. | ER | P | 03/30/2009 | SEE ORANGE CARD AND MOVED FIRE ALARM BY WEST SIDE ENTRANCE | JERRY | JERRY | | ER | P | 3817720 |
WEST ELECTRIC GROUP, INC. | ER | P | 03/20/2009 | CEILINGS IN ROOMS 143 AND 107: SECOND FLOOR CHASE | MATTHEW | MATTHEW | | ER | P | 3815415 |
WEST ELECTRIC GROUP, INC. | ER | P | 03/16/2009 | MEZZANINE HARD LID ROOM #'S MARKED ON ORANGE CARD ------ 2- FCU DISCONNECTS NOT INSTALLED; ACCESS DOORS AT BOTH LOCATIONS; CHECK AT FUTURE INSPECTIONS -------- | MATTHEW | MATTHEW | | ER | P | 3813038 |
WEST ELECTRIC GROUP, INC. | ER | P | 03/10/2009 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 3810935 |
WEST ELECTRIC GROUP, INC. | ER | P | 02/26/2009 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 3806675 |
WEST ELECTRIC GROUP, INC. | ER | P | 02/23/2009 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 3804887 |
WEST ELECTRIC GROUP, INC. | ER | P | 02/18/2009 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 3803519 |
WEST ELECTRIC GROUP, INC. | ER | P | 02/10/2009 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 3800953 |
WEST ELECTRIC GROUP, INC. | ER | P | 02/03/2009 | WALLS 146,149,152, STAGE HARDLID | MIKEC | MIKEC | | ER | P | 3798279 |
WEST ELECTRIC GROUP, INC. | ER | P | 01/26/2009 | WALLS ROOMS 114A,133,134,105,147,135,132,137,148,M101,M102,M103-------FIRE ALARM BOX ROUGH OK IN THESE AREAS INFORMED CONTRACTOR NEED SPERATE PERMIT FOR THIS------ | TIMA | TIMA | | ER | P | 3795045 |
WEST ELECTRIC GROUP, INC. | EUG | P | 12/10/2008 | SLAB FOR STAGE AREA OK. | DEAN | DEAN | | EUG | P | 3780342 |
WEST ELECTRIC GROUP, INC. | EUG | P | 11/26/2008 | REMAINING SLAB OK. | DEAN | DEAN | | EUG | P | 3775448 |
WEST ELECTRIC GROUP, INC. | ESL | P | 11/21/2008 | SEE PLANS,WEST END AND STAGE AREA | MIKEC | MIKEC | | ESL | P | 3773831 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 04/08/2009 | RECEIVED BALANCE REPORT. SENT TO SCANNING. | LYNNS | LYNNS | | H= | C | 3821278 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 04/06/2009 | HVAC FINAL PENDING BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3820428 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 03/12/2009 | ROUGH DUCT FOR EVR-1 THROUGH 1ST, 2ND AND ROOF OK. | LYNNS | LYNNS | | HD | P | 3812126 |
HEATING & PLUMBING ENGINEERS, INC | HRP | P | 03/06/2009 | 9- 350# TESTS OK. NEED TO SEE FINAL CONNECTIONS TO EQUIPMENT AND INSULATION AT FINAL. | LYNNS | LYNNS | | HRP | P | 3809425 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 02/27/2009 | SUPPLY AND RETURN ON AHU-4 OK. | LYNNS | LYNNS | | HD | P | 3807078 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 02/11/2009 | ROUGH DUCT, SEE SHEETS M2.11 AND M2.11A FOR DUCT AND DATE. | LYNNS | LYNNS | | HD | P | 3801337 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 01/22/2009 | ROUGH DUCT ABOVE CEILINGS OK TO COVER. SEE SHEETS M2.11 AND M2.11A FOR DUCT AND DATE. | LYNNS | LYNNS | | HD | P | 3793887 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 04/29/2009 | | LEE | LEE | | P= | C | 3828725 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 04/17/2009 | WAITING FOR AAV APPROVAL (FAX LETTER TO RBD), REST OK | LEE | LEE | | P= | P | 3825325 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 04/09/2009 | WATER TEMP EXCEEDS 110 DEGREES AT LAVS, WAITING FOR ENGINEERS LETTER TO ALLOW A.A.V. AT BREAK SINK | LEE | LEE | | P= | P | 3822049 |
HEATING & PLUMBING ENGINEERS, INC | PTO | L | 04/06/2009 | CAN SEE AAV APPROVAL ON FINAL | LEE | LEE | | PTO | L | 3820373 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 02/04/2009 | STILL WAITING FOR AAV APPROVAL AT BREAK SINK --- NOTES FOR RBD --- ACCESS TO HAMMER ARRESTORS IN BOTH RESTROOMS, TRAP PRIMER ACCESS IN MENS RESTROOM ON SIDE WALL NEXT TO FLOOR DRAIN, AAV ACCESS AT BREAK SINK IF APPROVED | LEE | LEE | | PTO | P | 3798814 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 02/02/2009 | LACKS SCREW PROTECTION THRUOUT, ALSO NEED LETTER FROM ENGINEER TO ALLOW AAV AT BAR SINK | LEE | LEE | | PTO | P | 3797614 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 01/30/2009 | SUITE NUMBERS?---BAR SINK DWV HAS NO TEST--REST OK--GET THIS SINK ON PERMIT TOO BY NEXT INSPECTION--SHOULD READ 3-WC 2-LAVS 2-URNIALS 2-FLOOR DRAINS 1-SINK | LYNNIE | LYNNIE | | PTO | P | 3797010 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 11/18/2008 | TRANSFER THIS PERMIT TO G.C PERMIT | LEE | LEE | | PB | C | 3774798 |