GORDON CONSTRUCTION COMPANY, INC | B= | C | 09/10/2009 | | DANF | DANF | | B= | C | 3883340 |
GORDON CONSTRUCTION COMPANY, INC | BE | C | 07/16/2009 | | JAN | JAN | | BE | C | 3858800 |
GORDON CONSTRUCTION COMPANY, INC | BSP | T | 01/26/2009 | PAID (REC#843701) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY splice for electrical comments | SHELBY | SHELBY | | BSP | T | 3794805 |
GORDON CONSTRUCTION COMPANY, INC | B= | P | 01/23/2009 | 1) ELECTRIC AND HEATING FINALS 2)MISSING SHOW SEAT 3) WALL PROTECTION FOR WATERCLOSET IN SHOWER ROOM 4) REMOVE DBL KEYED LOCK EXTERIOR ENTRY DOOR; NEED OPEN/CLOSED LOCK ON INTER DOOR 5)LAV KNEE PROTECTION, 6"BASE SHOWER AREA AND FLOOR COVERING | DANF | DANF | | B= | P | 3794588 |
RIDGEVIEW PLUMBING | BSP | T | 01/23/2009 | PAID (REC#843530) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new 3/4 water line | TCRIPPEN | TCRIPPEN | | BSP | T | 3794267 |
GORDON CONSTRUCTION COMPANY, INC | BFN | C | 12/18/2008 | OPEN HOLE OBSERVATION ON FILE | DANF | DANF | | BFN | C | 3783560 |
GORDON CONSTRUCTION COMPANY, INC | BFN | P | 12/09/2008 | WEST WALL OF RAMP OK; STILL NEED EAST WALL | DANF | DANF | | BFN | P | 3779662 |
GORDON CONSTRUCTION COMPANY, INC | BFR | P | 11/20/2008 | interior walls ok pending other rough sign offs | JOND | JOND | | BFR | P | 3772784 |
GDS ELECTRIC | E= | C | 02/02/2009 | | MATTHEW | MATTHEW | | E= | C | 3797515 |
GDS ELECTRIC | E= | L | 01/29/2009 | locked 12:53pm | ARNOLD | ARNOLD | | E= | L | 3796397 |
GDS ELECTRIC | E= | P | 01/22/2009 | ENGINEERS LETTER DOES DOES NOT MATCH BREAKER RATING IN THESE 2 PANELS. THEY ARE ONLY 10K. ALSO NEED HANDLE TIES ON ALL MULTIWIRE CIRCUITS FOR FURNITURE. | DEAN | DEAN | | E= | P | 3793828 |
GDS ELECTRIC | ER | C | 01/14/2009 | BREAK ROOM CEILING OK. | DEAN | DEAN | | ER | C | 3791047 |
GDS ELECTRIC | ER | P | 01/09/2009 | ALL CEILINGS EXCEPT BREAK ROOM OK. | DEAN | DEAN | | ER | P | 3789848 |
GDS ELECTRIC | ES | P | 01/09/2009 | 200-AMP 4 WIRE NEW XFMR AND PANEL FOR SUITE 150. THIS IS FED FROM AN EXISTING MDP.-------NEED PLANS CHANGED AND RESUBMIT THRU PLAN REVIEW TO SHOW WHAT HAS ACTUALLY BEEN INSTALLED,-------------------ALSO ON FINAL NEED TO CHECK XFMR FOR 1 COMMON GROUNDING LUG POINT---------------AFTER PLANS APPROVED, CHECK FAULT CURRENTS--------------- | DEAN | DEAN | | ES | P | 3789847 |
GDS ELECTRIC | ER | P | 11/24/2008 | bath, storage, and shower hardlids ok | MATTHEW | MATTHEW | | ER | P | 3774020 |
GDS ELECTRIC | ER | P | 11/19/2008 | walls ok --- need access to j-boxes above hard lids | MATTHEW | MATTHEW | | ER | P | 3772193 |
GDS ELECTRIC | ESL | C | 11/18/2008 | floor boxes and stubs ok | MATTHEW | MATTHEW | | ESL | C | 3771491 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 06/18/2009 | RECEIVED BALANE REPORT. | LYNNS | LYNNS | | H= | C | 3847888 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 01/20/2009 | NEED BALNCE REPORT. | LYNNS | LYNNS | | H= | P | 3792215 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 01/16/2009 | REMOVE FLEX THROUGH FIRE WALL ABOVE WEST OFFICES, REMOVEPLASTIC COVERING FIRE DAMPERS ON WEST WALL, NEED BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3791759 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 01/08/2009 | ROUGH DUCT. QUESTION RETURN AIR SPACE WITH COMBUSTABLES IN IT. NOTE:FULLY SPRINKLED ABOVE AND BELOW CEILING. CHECK FLEX ABOVE 121. | LYNNS | LYNNS | | HD | P | 3788886 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 11/21/2008 | ROUGH DUCT ABOVE CEILINGS IN BATH ROOMS, OK TO COVER. | LYNNS | LYNNS | | HD | P | 3773351 |
RIDGEVIEW PLUMBING | P= | C | 01/23/2009 | | MARTY | MARTY | | P= | C | 3794339 |
RIDGEVIEW PLUMBING | PTO | C | 01/23/2009 | | MARTY | MARTY | | PTO | C | 3794338 |
RIDGEVIEW PLUMBING | PTO | P | 11/26/2008 | WATER PIPE NOT SIZED PER PLANS (COLD WATER 3/4" MAINS), TYPE L COPPER REQUIRED (USED TYPE M), DWV TEST OK --- NOTES FOR RBD --- URNAL C/O FACES OPPOSITE BATHROOM UP HIGH, NEED AAV AT BREAK SINK | LEE | LEE | | PTO | P | 3775908 |
RIDGEVIEW PLUMBING | PB | C | 11/10/2008 | | MARTY | MARTY | | PB | C | 3767629 |