BUILDINGS BY DESIGN, LLC | B= | C | 11/19/2009 | | DANF | DANF | | B= | C | 3913827 |
BUILDINGS BY DESIGN, LLC | B= | R | 09/21/2009 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: ngadson@springsgov.com or 385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet. 1) OPTICAL CENTER NEED SIGN ABOVE DOOR AT ENTRY EXTERIOR "WHEN BUILDING OCCUPYED" 2) AT ENTRY SLIDING DOORS NEED KEYED LOCK INDICATORS OPEN OR CLOSED AND SIGNS ABOVE | DANF | DANF | | B= | R | 3887589 |
BUILDINGS BY DESIGN, LLC | BFR | C | 09/21/2009 | | DANF | DANF | | BFR | C | 3887584 |
BUILDINGS BY DESIGN, LLC | BFR | P | 08/21/2009 | New wall in Room #154 ok at 8' height | MIKE | MIKE | | BFR | P | 3874753 |
BUILDINGS BY DESIGN, LLC | BFR | R | 08/20/2009 | New Training Room #154 - Rated wall not extended to deck per design | MIKE | MIKE | | BFR | R | 3874274 |
BUILDINGS BY DESIGN, LLC | BFR | P | 08/12/2009 | ROOM #105 BREAK ROOM FRAMING EXTERIOR WALLS AND NEW ADDED EXIT DOOR OK | DANF | DANF | | BFR | P | 3870496 |
BUILDINGS BY DESIGN, LLC | BFR | P | 07/29/2009 | CEILING FRAMING IN ROOM #153 | DANF | DANF | | BFR | P | 3864735 |
BUILDINGS BY DESIGN, LLC | BFR | P | 07/24/2009 | Partition wall framing for New Cash #153 & New Computer #151 ok, Need electric & heat inspections | MIKE | MIKE | | BFR | P | 3862815 |
BUILDINGS BY DESIGN, LLC | BFR | P | 07/01/2009 | room 161, audit area | DANF | DANF | | BFR | P | 3853203 |
BUILDINGS BY DESIGN, LLC | BSP | T | 06/24/2009 | PAID (REC#864145) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY splice 13 pages | SHELBY | SHELBY | | BSP | T | 3850136 |
CLIMATE SYSTEMS, INC | BSP | T | 06/24/2009 | PAID (REC#864146) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: splice for change to multiple mechanical sheets | DALEH | DALEH | | BSP | T | 3850025 |
BUILDINGS BY DESIGN, LLC | BSP | T | 06/24/2009 | PAID (REC#864147) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Splice for snack bar & office changes | SHELLEY | SHELLEY | | BSP | T | 3849971 |
BUILDINGS BY DESIGN, LLC | BSP | T | 06/24/2009 | PAID (REC#864148) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice pages moving offices a round | TCRIPPEN | TCRIPPEN | | BSP | T | 3849945 |
BUILDINGS BY DESIGN, LLC | BFR | P | 06/22/2009 | partial- room 104- new managers office at east side of building- frame ok pending revision sheet being approved by rbd plancheck and all other rough trades being inspected | BLAKE | BLAKE | | BFR | P | 3849107 |
BUILDINGS BY DESIGN, LLC | BFR | P | 06/01/2009 | KNEE WALL AT PHOTO SHOP OK | DANF | DANF | | BFR | P | 3840629 |
BUILDINGS BY DESIGN, LLC | BFR | P | 05/29/2009 | PHOTO SHOP FURRED WALL AND JANITOR CLOSET AT REAR OF STORE OK | DANF | DANF | | BFR | P | 3840223 |
BUILDINGS BY DESIGN, LLC | BFR | P | 05/20/2009 | vison center framing ok | DANF | DANF | | BFR | P | 3836608 |
BUILDINGS BY DESIGN, LLC | BFR | R | 05/19/2009 | 1) MISSING BRIDGING AT 1/3 POINTS 2) STRIP BRIDGING OF CEILING JOIST REQUIRE 2 EACH SCREWS AT EACH JOICE. 3) SECURE ENDS OF BRACING AT 45 DEGREE STUD BRACING, SEVERAL AREAS WHERE LATERAL BRACING WAS CUT OUT | DANF | DANF | | BFR | R | 3836196 |
BIBLE ELECTRIC, INC. | E= | C | 08/26/2009 | COULD NOT FIND PERMIT CARD | JOSEPH | JOSEPH | | E= | C | 3877003 |
BIBLE ELECTRIC, INC. | E= | P | 08/25/2009 | ALL EXCEPT RTU'S | MIKEC | MIKEC | | E= | P | 3876163 |
BIBLE ELECTRIC, INC. | ER | C | 08/20/2009 | WALLS TRAINING ROOMS 154,155 | MIKEC | MIKEC | | ER | C | 3874061 |
BIBLE ELECTRIC, INC. | ER | P | 08/19/2009 | CEILING IN BREAKROOM
| JOSEPH | JOSEPH | | ER | P | 3873592 |
BIBLE ELECTRIC, INC. | ER | P | 08/13/2009 | BREAK ROOM WALLS | JOSEPH | JOSEPH | | ER | P | 3871182 |
BIBLE ELECTRIC, INC. | ER | P | 07/29/2009 | COMPUTER ROOM HARDLID | MIKEC | MIKEC | | ER | P | 3864471 |
BIBLE ELECTRIC, INC. | ER | P | 07/24/2009 | CASH AND COMP.WALLS | MIKEC | MIKEC | | ER | P | 3862771 |
BIBLE ELECTRIC, INC. | E= | P | 07/17/2009 | managers office | MIKEC | MIKEC | | E= | P | 3859544 |
BIBLE ELECTRIC, INC. | ER | P | 07/02/2009 | audit room.tighten ground screw in outlet box | MIKEC | MIKEC | | ER | P | 3853797 |
BIBLE ELECTRIC, INC. | ER | R | 06/26/2009 | =====POC IS LESS @ 970-214-7537=====BAKERY CEILINGS ONLY=== | GARYL | GARYL | | ER | R | 3851395 |
BIBLE ELECTRIC, INC. | E= | P | 06/22/2009 | vision and optical | MIKEC | MIKEC | | E= | P | 3848910 |
BIBLE ELECTRIC, INC. | ER | P | 06/22/2009 | walls fax and pole area | MIKEC | MIKEC | | ER | P | 3848909 |
BIBLE ELECTRIC, INC. | ER | P | 06/01/2009 | knee wall ok permit locked up | MIKEC | MIKEC | | ER | P | 3840324 |
BIBLE ELECTRIC, INC. | ER | P | 05/28/2009 | optical sales west wall | MIKEC | MIKEC | | ER | P | 3839155 |
BIBLE ELECTRIC, INC. | ER | P | 05/27/2009 | janitors walls | MIKEC | MIKEC | | ER | P | 3838844 |
BIBLE ELECTRIC, INC. | ER | P | 05/18/2009 | walls and hardlids | MIKEC | MIKEC | | ER | P | 3835483 |
CLIMATE SYSTEMS, INC | H= | C | 09/08/2009 | RECEIVED BALANCE REPORT, SENT TO SCANNING. | LYNNS | LYNNS | | H= | C | 3881675 |
K & A MECHANICAL | H= | C | 08/24/2009 | GAS FINAL. | LYNNS | LYNNS | | H= | C | 3875463 |
CLIMATE SYSTEMS, INC | HD | C | 08/24/2009 | ROUGH DUCT IN TRAINING AREA. UNIT HEATER VENTS CORRECTED. | LYNNS | LYNNS | | HD | C | 3875460 |
CLIMATE SYSTEMS, INC | H= | P | 08/24/2009 | HVAC FINAL PENDING BALANCE REPORTS. | LYNNS | LYNNS | | H= | P | 3875458 |
K & A MECHANICAL | HO | C | 08/20/2009 | 60# TEST ON DOCK LINE OK. LABELS ON. | LYNNS | LYNNS | | HO | C | 3874408 |
K & A MECHANICAL | HI | C | 08/19/2009 | 3- 10# TESTS ON LINES TO THREE UNIT HEATERS ON LOADING DOCK. | LYNNS | LYNNS | | HI | C | 3873645 |
K & A MECHANICAL | HO | P | 08/19/2009 | LOADING DOCK LINE ON ROOF, NO TEST, CANNOT HAVE UNION ON NORTH/EAST SIDE UNLESS AFTER A SHUTOFF OR WITH-IN 3' OF AN APPLIANCE. RTU-22, 60# TEST. NEED TO LABEL ALL ELEVATED PRESSURE GAS LINES. | LYNNS | LYNNS | | HO | P | 3873640 |
CLIMATE SYSTEMS, INC | H= | P | 08/17/2009 | NEED BALANCE REPORT, | LYNNS | LYNNS | | H= | P | 3872310 |
CLIMATE SYSTEMS, INC | HD | P | 08/17/2009 | BREAD OVEN B-VENTS (4), EDC ROOM EXHAUST, MEN'S/WOMEN'S BATH FAN EXHAUST,EF-2&3, NEED TO SEAL DUCT IN BREAK ROOM, VISION CENTER R/D,OK. | LYNNS | LYNNS | | HD | P | 3872308 |
CLIMATE SYSTEMS, INC | HD | P | 07/29/2009 | ROUGH DUCT ABOVE CEILING IN "NEW CASH" ROOM, OK TO COVER. | LYNNS | LYNNS | | HD | P | 3864402 |
CLIMATE SYSTEMS, INC | H= | P | 07/15/2009 | GREASE WRAP AND MUA TO HOOD OK. NEED A BALANCE REPORT ON HOOD. NEED TO SEE COMPLETION OF SCOPE OF WORK. | LYNNS | LYNNS | | H= | P | 3858487 |
CLIMATE SYSTEMS, INC | HD | P | 07/13/2009 | GRE3ASE DUCT OK TO FIREWRAP. | LYNNS | LYNNS | | HD | P | 3857158 |
CLIMATE SYSTEMS, INC | HD | P | 07/10/2009 | GREASE DUCT STILL HAS HOLES IN THE WELD JOINTS. REPAIR AND MARK FOR RE-INSPECTION. | LYNNS | LYNNS | | HD | P | 3856658 |
CLIMATE SYSTEMS, INC | HD | R | 07/09/2009 | NEED TO HAVE A LIGHT TEST IN DUCT THAT INSPECTOR CAN OBSERVE. APPEARS TAT THERE ARE MULTIPLE HOLES IN THW WELDS THAT WILL LEAK. K&A MECHANICAL DOES NOT HAVR THIS HOOD PERMITTEDE. SPOKE WITH GENERAL CONTRACTOR AND INFORMED HIM OF THIS. | LYNNS | LYNNS | | HD | R | 3855927 |
K & A MECHANICAL | HI | P | 06/26/2009 | 3- 60# TESTS ON GAS TO ROTISSERIE AND BREAD OVENS OK. | LYNNS | LYNNS | | HI | P | 3851353 |
K & A MECHANICAL | H= | P | 06/11/2009 | PARTIAL GAS FINAL FOR LINE TO RTU-20. | LYNNS | LYNNS | | H= | P | 3844795 |
K & A MECHANICAL | HI | P | 06/05/2009 | 60# TEST ON GAS LINE TO RTU-20 OK. | LYNNS | LYNNS | | HI | P | 3842859 |
K & A MECHANICAL | P= | C | 09/02/2009 | | LEE | LEE | | P= | C | 3880247 |
K & A MECHANICAL | PTO | P | 08/20/2009 | DELI COOLERS OK PENDING TWO FLOOR SINKS BURIED UNDER COOLER | LEE | LEE | | PTO | P | 3874473 |
K & A MECHANICAL | P= | P | 08/20/2009 | BREAK SINK AND VISION OK | LEE | LEE | | P= | P | 3874471 |
K & A MECHANICAL | PTO | P | 08/19/2009 | LACKS WRAPS ON 5- VENT STACKS AT COOLERS (TESTS OK) TWO FLOOR SINKS NOT IN VIEW | LEE | LEE | | PTO | P | 3873868 |
K & A MECHANICAL | PTO | P | 08/18/2009 | BREAKROOM SINK OK | LEE | LEE | | PTO | P | 3873213 |
K & A MECHANICAL | PB | C | 08/14/2009 | BREAK SINK OK | LEE | LEE | | PB | C | 3871522 |
K & A MECHANICAL | PB | P | 07/30/2009 | MEAT AND FLORAL OK | LEE | LEE | | PB | P | 3864989 |
K & A MECHANICAL | PB | P | 07/29/2009 | MEAT -- LOW TEST, LACKS VENT ON SYSTEM | LEE | LEE | | PB | P | 3864327 |
K & A MECHANICAL | PB | P | 07/28/2009 | EXTENSION OF 4" G/W IN MEAT (SEE PLANS) | LEE | LEE | | PB | P | 3864207 |
K & A MECHANICAL | PB | P | 07/27/2009 | CONTACT # LES- 970-214-7537 -- MEAT -- CASES 1&2 OK, FOUR FLOOR SINKS TOTAL (SEE PLANS) | LEE | LEE | | PB | P | 3863650 |
K & A MECHANICAL | PWO | R | 07/24/2009 | NO CONTACT NUMBER GIVEN--CALLED IN AS A PWO?--WALKED THROUGH STORE COULDNT SEE ANY WORK TENTS ETC THAT WOULD NEED A PWO | LYNNIE | LYNNIE | | PWO | R | 3862591 |
K & A MECHANICAL | PB | P | 06/17/2009 | ADDED A 3'' FLOOR SINK TO THE BAKERY AREA. | SCOTT | SCOTT | | PB | P | 3847070 |
K & A MECHANICAL | PB | P | 06/11/2009 | BAKERY RACK WASHER, NEED ENGINEERS APPROVAL FOR EJECTOR IN PLACE OF GRAVITY DRAIN, NO DETAILS AT THIS TIME ON CHANGES TO APPROVED PLANS, 4" DRAIN, 2" VENT AND 2" PIT DISCHARGE TEST OK | LEE | LEE | | PB | P | 3844794 |
K & A MECHANICAL | P= | L | 06/05/2009 | CALLED IN WRONG, WANTED MECHANICAL INSPECTION | LEE | LEE | | P= | L | 3842560 |
K & A MECHANICAL | PB | P | 06/04/2009 | DELI -- THREE 4" DRAINS ON GREASE WASTE OK (SEE PLANS) | LEE | LEE | | PB | P | 3841979 |
K & A MECHANICAL | P= | P | 06/04/2009 | VISION CENTER OK | LEE | LEE | | P= | P | 3841973 |
K & A MECHANICAL | PB | P | 05/28/2009 | SANITARY FROM VISION THRU PHOTO OK PENDING LISTING FOR HUSKY BANDS, PL TO PL IN QUESTION | LEE | LEE | | PB | P | 3839498 |
K & A MECHANICAL | PTO | P | 05/18/2009 | VISION CENTER DWV COMPLETE, WATER PIPE IN WALLS COMPLETE, STILL NEED OVERHEAD H20 TO POINT OF CONNECTION | LEE | LEE | | PTO | P | 3835961 |
K & A MECHANICAL | PTO | R | 05/15/2009 | SCREW PROTECTION INCOMPLETE AT TOP AND BOTTOM PLATES PER 2003 IPC, LOST TEST ON DWV, WATER PIPE NOT SIZED PER PLANS, VENTS ABOVE WALLS NOT GRADED, ETC: | LEE | LEE | | PTO | R | 3835008 |
K & A MECHANICAL | PB | P | 05/11/2009 | VISION CENTER OK, STILL NEED TIE IN SAME AREA (SEE PLANS) | LEE | LEE | | PB | P | 3833312 |
K & A MECHANICAL | PB | P | 05/08/2009 | CALL MARTIN 970-566-3368 (DAY SUPER) UPON ARRIVAL, VISION CENTER -- LOST TEST | LEE | LEE | | PB | P | 3832699 |