ELDER CONSTRUCTION, INC. | B= | C | 04/15/2014 | All other required Final inspections are complete. (This is a computer generated result) | BLAKE | BLAKE | | B= | C | 4720358 |
ELDER CONSTRUCTION, INC. | B= | P | 03/05/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | BLAKE | BLAKE | | B= | P | 4697009 |
ELDER CONSTRUCTION, INC. | B= | P | 05/31/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. still waiting for heating final -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 4533952 |
ELDER CONSTRUCTION, INC. | BE | L | 03/21/2013 | Renewed at 3/21/2013 11:18:33 AM | NELIDA | NELIDA | | BE | L | 4491232 |
ELDER CONSTRUCTION, INC. | B= | P | 07/24/2012 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), LANDMARK PLUMBING & HTG, INC. Mechanical Final Inspection is not Completed yet, RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. complete other finals; 3 exit sign at entrance to vesibules -- Schedule a new Building Final when above items are complete. | DANF | DANF | | B= | P | 4347913 |
ELDER CONSTRUCTION, INC. | B= | P | 07/18/2012 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), LANDMARK PLUMBING & HTG, INC. Mechanical Final Inspection is not Completed yet, RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. need panic hardware at choir, band and study hall rooms/ need grab bars at both restrooms 121 and 122 -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 4343858 |
ELDER CONSTRUCTION, INC. | BFR | P | 06/29/2012 | security office frame ok pending any elec rough needed for wiring going into walls | JOHN | JOHN | | BFR | P | 4334366 |
ELDER CONSTRUCTION, INC. | BSP | P | 06/12/2012 | smoke walls OK | DANF | DANF | | BSP | P | 4325286 |
ELDER CONSTRUCTION, INC. | BFR | P | 05/15/2012 | frame ok for former weight room area | BLAKE | BLAKE | | BFR | P | 4311230 |
ELDER CONSTRUCTION, INC. | BSP | P | 05/01/2012 | fire caulk at shafts ok/ looked at top of smoke walls, recall when all penetrations are fire caulked | BLAKE | BLAKE | | BSP | P | 4304293 |
ELDER CONSTRUCTION, INC. | BFR | P | 04/05/2012 | south half (area A) ok | BLAKE | BLAKE | | BFR | P | 4292879 |
ELDER CONSTRUCTION, INC. | BFR | P | 03/22/2012 | pending other rough inspections sheet A1.4 ok except old weight room and rooms 146 and 147, also sheet A1.3 except rooms 119 and 123 and shaft above corridor above 136 | BLAKE | BLAKE | | BFR | P | 4286549 |
ELDER CONSTRUCTION, INC. | BFR | P | 03/12/2012 | met with jim 491-0156 consultation re:phasing and scheduling/ top of weight room wall ok | BLAKE | BLAKE | | BFR | P | 4281854 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 12/04/2013 | MECHANICAL FINAL OK. REVISED TEST AND BALANCE REPORT RECEIVED, EF17 WITHIN +/- 10% ALLOWANCE. | NANCY | NANCY | | H= | C | 4652740 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 06/05/2013 | TEST AND BALANCE REPORT RECEIVED. EF17 OUTSIDE OF THE =/- 10% ALLOWED. PROVIDE LETTER FROM ENGINEER APPROVING EF17 CFM READINGS. | NANCY | NANCY | | H= | P | 4537590 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 05/31/2013 | RECEIVED PARTIAL TEST AND BALANCE REPORT. EXHAUST READING OUTSIDE OF THE +/- 10% ALLOWED. | NANCY | NANCY | | H= | P | 4533962 |
RIAL HEATING AND AIR CONDITIONING, INC. | HE | L | 03/21/2013 | Renewed at 3/21/2013 11:21:23 AM | NELIDA | NELIDA | | HE | L | 4491236 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 09/21/2012 | GAS FINAL COMPLETED BY STATE INSPECTOR. GAS INSPECTIONS FOR SCHOOLS ARE DONE BY STATE. GAS ACCIDENTALLY ADDED TO THE REGIONAL BUILDING DEPARTMENT PERMIT. | NANCY | NANCY | | H= | C | 4386285 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 07/10/2012 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4338895 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 07/06/2012 | FRAMING OK FOR FIRE/SMOKE DAMPER IN WALL TO SECURITY/VESTIBULE AREA. | NANCY | NANCY | | HD | P | 4337329 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 07/05/2012 | PROPERLY FRAME WALL FOR FIRE/SMOKE DAMPER GOING INTO SECURITY/VESTIBULE AREA. | NANCY | NANCY | | HD | P | 4336558 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 06/22/2012 | NOTE ADDED 7/5/1: STILL NEED TO SEE FIRE/SMOKE DAMPER FOR SECURITY AREA. STILL NEED TO SEE SUPPLY AIR INTO SECURITY/VESTIBULE AREA. ALSO COMPLETE THREE OFFICES OFF OF LOBBY AREA. MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | P | 4330647 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 05/30/2012 | FINAL ABOVE CEILING OK FOR: AREA A, EXCEPT DRAMA CLASSROOM. AREA B, ALL OK. WOMEN'S BATHROOM EXHAUST OK. STILL NEED TO SEE EXHAUST IN PHYSICS, ANATOMY AND EARTH SCIENCE. | NANCY | NANCY | | H= | P | 4318378 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/15/2012 | VAV 8-102: OK TO WRAP MEDIUM PRESSURE AND LOW PRESSURE DUCTS. OLD WEIGHT ROOM: OK TO WRAP FOR ALL VAV'S. ROOM 103: RETURN AIR INSTALLED THROUGH WALL ABOVE CEILING, PROVIDE LETTER FROM ENGINEER APPROVING LOCATION. SMOKE DAMPER INSTALLED BETWEEN EMSEMBLE AND STORAGE. | NANCY | NANCY | | HD | P | 4311415 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/08/2012 | VAV'S 127, 139, 141, 142 AND 143: SUPPLY AIR ALL OK INCLUDING WRAP. OK TO COVER. ENSEMBLE AND OFFICE 103: SUPPLY AIR ALL OK INCLUDING WRAP, OK TO COVER. COLLEGE CONNECT AND COLLEGE CONNECT STORAGE: SUPPLY AIR ALL OK, INCLUDING WRAP, OK TO COVER. BOYS AND GIRLS BATHROOMS: SUPPLY AIR OK INCLUDING WRAP, OK TO COVER. CUSTODIAN, BREAK ROOM AND MEN'S BATHROOM: EXHAUST OK. STILL NEED TO SEE WOMEN'S BATHROOM EXHAUST. QUESTION REGARDING RETURN AIR PATH FROM OFFICE 103? COMPLETE SMOKE DAMPER IN WALL BETWEEN ENSEMBLE AND STORAGE. | NANCY | NANCY | | HD | P | 4307972 |
LANDMARK PLUMBING AND HEATING, INC. | HWP | C | 04/30/2012 | HWP TIE IN AT ALL VAV'S OK. OK TO INSULATE ALL. | NANCY | NANCY | | HWP | C | 4303742 |
LANDMARK PLUMBING AND HEATING, INC. | HWP | P | 04/27/2012 | RESCHEDULED FOR MONDAY PER JIM/ELDER CONSTRUCTION. | NANCY | NANCY | | HWP | P | 4303335 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 04/26/2012 | NEW WEIGHT ROOM: ABOVE CEILING ALL OK EXCEPT NEED TO INSTALL SOUND BOOTS. OK FOR TILES PER MECHANICAL ONLY. BAND ROOM: ROUGH DUCT OK, OK TO WRAP. CHOIR ROOM: ROUGH DUCT OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4302578 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 04/17/2012 | 60 LB TEST OK. INSTALLED AS PER PRINTS. COUNTER STRIKE AND SLEEVE OK. STILL NEED TO SEE EMERGENCY SHUT OFFS IN CEILINGS. | NANCY | NANCY | | HI | C | 4298059 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 04/13/2012 | QUESTION REGARDING RETURN AIR/RETURN AIR PATH FROM PHYSICS. ANATOMY AND EARTH SCIENCE CLASSROOMS. AREA A CLASSROOMS: OK TO WRAP ALL LOW PRESSURE DUCTS EXCEPT STILL NEED TO SEE DUCTS FOR VAV'S 7/153 AND 8/152. EXHAUST DUCT FOR PHYSICS AND ANATOMY CLASSROOMS OK. RTU3 SUPPLY: OK TO WRAP. | NANCY | NANCY | | HD | P | 4296518 |
LANDMARK PLUMBING AND HEATING, INC. | HWP | P | 04/12/2012 | ADD SCOPE OF HWP TO YOUR PERMIT DETAILS. AREA A: HWS/HWR ALL OK, OK TO INSULATE. STILL NEED TO SEE TIE IN AT VAV'S. AREA B: HWS/HWR ALL OK EXCEPT STILL NEED TO SEE LINES TO EQUIPMENT NORTH OF ELEVATOR AND MACHINE ROOM. OK TO INSULATE. STILL NEED TO SEE TIE IN AT VAV'S. AREA C: HWS/HWR ALL OK EXCEPT STILL NEED TO SEE LINES IN EXISTING WEIGHT ROOM AREA. OK TO INSULATE. STILL NEED TO SEE TIE IN AT VAV'S. | NANCY | NANCY | | HWP | P | 4296022 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 04/05/2012 | AREA C: OK TO WRAP MEDIUM AND LOW PRESSURE DUCTS EXCEPT STILL NEED TO SEE DUCTS FOR VAV 9/146, VAV 9/147 AND VAV 8/148. STILL NEED TO SEE FIRE/SMOKE DAMPER FOR SECURITY AREA FRAMED AND INSTALLED. AREA B: OK TO WRAP MEDIUM AND LOW PRESSURE DUCTS EXCEPT STILL NEED TO SEE DUCTS FOR VAV 8/128, VAV 8/105 AND MEDIUM PRESSURE ONLY FOR VAV 8/102. OK TO INSTALL ANGLES ON SHAFT BOTTOMS. | NANCY | NANCY | | HD | P | 4292723 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | C | 03/20/2012 | ARMAFLEX REPAIRED IN SHAFT. | NANCY | NANCY | | HRP | C | 4285344 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 03/20/2012 | DID NOT SEE PERMIT CARD ON SITE. ANGLES INSTALLED ON ALL FIRE.SMOKE DAMPERS IN SHAFTS PER ENGINEERS DRAWING. LETTER RECEIVED FROM ENGINEER APPROVING INSTALLATION OF ANGLES IN SHAFTS. | NANCY | NANCY | | HD | P | 4285332 |
RIAL HEATING AND AIR CONDITIONING, INC. | H16 | P | 03/19/2012 | PICTURES AND PAPERS RECEIVED REGARDING FIRE/SMOKE DAMPERS IN SHAFTS. | NANCY | NANCY | | H16 | P | 4284518 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | P | 03/12/2012 | 400 LB TEST OK ON LINESET TO FCU123. REPAIR BREAKS IN ARMAFLEX IN SHAFT. STILL NEED TO SEE ROOF AND EQUIPMENT HOOK UP. | NANCY | NANCY | | HRP | P | 4281911 |
RIAL HEATING AND AIR CONDITIONING, INC. | H16 | P | 02/24/2012 | MECHANICAL CONTRACTOR MUST FIND OUT MANUFACTURER OF FIRE DAMPERS ALREADY INSTALLED ON SITE BEFORE FRAMING REQUIREMENTS FOR DAMPERS CAN BE DETERMINED. WILL NEED BUILDING TO BE INVOLVED REGARDING PROPER SHAFT CONSTRUCTION. | NANCY | NANCY | | H16 | P | 4275543 |