J. E. DUNN CONSTRUCTION COMPANY | B= | C | 08/21/2012 | | JOHNP | JOHNP | | B= | C | 4365701 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | C | 08/21/2012 | engineer's letter on file for epoxied anchor installations, bolting and welding and spray fire resistive material from CTL, J. Scott Keim, PE, #38463; RTA Architects letter on file for north exterior wall framing detail | DANF | DANF | | BFR | C | 4365693 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 08/20/2012 | Additional Inspections Required: OLSON PLUMBING & HEATING CO Plumbing Final Inspection is not Completed yet. Need frame, mechanical & plumbing sign offs -- Schedule a new Building Final when above items are complete. | JOHNP | JOHNP | | B= | P | 4365264 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 08/20/2012 | Letters picked up from Architect on North wall framing & Engineer on weld, bolt, anchor observation & fire resistive spray on application | JOHNP | JOHNP | | BSP | P | 4365260 |
COLORADO SHEET METAL CO., INC. | BSP | T | 08/17/2012 | PAID (REC#1071533) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: splice | DALEH | DALEH | | BSP | T | 4364358 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 08/17/2012 | firecaulking in electric room south wall ok | FRANK | FRANK | | BSP | P | 4364276 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | T | 08/16/2012 | PAID (REC#1071191): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: added locker and work rooms | SHELLEY | SHELLEY | | BSP | T | 4363217 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | T | 08/16/2012 | PAID (REC#1071196): ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice page added bath room | TCRIPPEN | TCRIPPEN | | BSP | T | 4363199 |
GREEN ELECTRIC INC | BSP | T | 08/16/2012 | PAID (REC#1071193): PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4363116 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 08/03/2012 | bathroom wall framing and office wall framing rooms #229 and #230; was spliced into approved set | DANF | DANF | | BFR | P | 4354589 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 08/02/2012 | area inspected highlighted in orange and dated on permit set, fire caulking and fire tape, labeling of smoke, 1 hour walls above ceiling grid ok. | ED | ED | | BSP | P | 4353705 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | R | 08/01/2012 | areas above corridors, still need fire caulking and fire tape, | ED | ED | | BSP | R | 4353016 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 07/18/2012 | added north exterior wall framing ; need specific framing detail and added to approved plans | DANF | DANF | | BFR | P | 4343513 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 07/18/2012 | walked framing inspection with Dan | ED | ED | | BSP | P | 4343510 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/28/2012 | horz. 1hr ceiling in rooms 200A and #224 on approved plans sheet 224 | DANF | DANF | | BSP | P | 4333438 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/06/2012 | fire caulk floor penetrations OK | DANF | DANF | | BSP | P | 4321843 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/05/2012 | missing fire caulk in floor penetration where new wall pipes ; recall | DANF | DANF | | BSP | P | 4321165 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 06/04/2012 | hard lid framing in OR rooms #210 and 211; need engineer's from CTL for boom support in both operating rooms; top of shaft fire spray OK | DANF | DANF | | BFR | P | 4320517 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 05/23/2012 | see approved plans for area and exterior wall insulation | FRANK | FRANK | | BFR | P | 4315770 |
J. E. DUNN CONSTRUCTION COMPANY | BIN | P | 05/10/2012 | exterior wall insulation in rooms #220, #221, # 221 sub-sterile and noted on approved plans sheet AC110 | DANF | DANF | | BIN | P | 4308863 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 05/01/2012 | walls as noted on sheet AC110, and core board shaft, ; check for rated walls rooms #222, #223, #224 | DANF | DANF | | BFR | P | 4304273 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 04/19/2012 | meeting with RTA architect, Dave, Dunn super, Tony and myself re rear utility basement hallway ceiling height for pipe at 6'7" as being acceptable. Reviewed with Blake to verify decision | DANF | DANF | | BSP | P | 4298820 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 04/18/2012 | Corridor framing as noted on sheet AC110 of approved plans; contractor and architect had question re basement ceiling height of 6'6' after pipe ran in hallway | DANF | DANF | | BFR | P | 4298336 |
GREEN ELECTRIC INC | E= | C | 08/17/2012 | | MIKEC | MIKEC | | E= | C | 4363930 |
GREEN ELECTRIC INC | E= | C | 08/17/2012 | FIRE ALARM INSPECTION: | MIKEC | MIKEC | | E= | C | 4363925 |
GREEN ELECTRIC INC | ER | P | 08/06/2012 | consultation foreign systems above electrical equipment. | BRET | BRET | | ER | P | 4356345 |
GREEN ELECTRIC INC | ER | P | 08/03/2012 | walls asi #18 and bathroom in same area | MATTHEW | MATTHEW | | ER | P | 4354751 |
GREEN ELECTRIC INC | ER | P | 08/03/2012 | FIRE ALARM INSPECTION: walls asi#18 and bathroom in same area | MATTHEW | MATTHEW | | ER | P | 4354749 |
GREEN ELECTRIC INC | ER | P | 07/30/2012 | corridor pump room and locker room ceiling ok | BRET | BRET | | ER | P | 4351473 |
GREEN ELECTRIC INC | ER | P | 07/03/2012 | hard lid. one room see plan | BRET | BRET | | ER | P | 4335635 |
GREEN ELECTRIC INC | ER | P | 06/19/2012 | rest of walls and feeder conduits | MIKEC | MIKEC | | ER | P | 4328357 |
GREEN ELECTRIC INC | ER | P | 06/11/2012 | FIRE ALARM INSPECTION: f.a stubs corridor | BRET | BRET | | ER | P | 4324152 |
GREEN ELECTRIC INC | ER | P | 06/11/2012 | or 10 and 11 see plans | BRET | BRET | | ER | P | 4324150 |
GREEN ELECTRIC INC | ER | P | 06/01/2012 | or11 ceiling | MIKEC | MIKEC | | ER | P | 4319533 |
GREEN ELECTRIC INC | ER | P | 05/22/2012 | it walls and or11 walls marked on plans. | BRET | BRET | | ER | P | 4314533 |
GREEN ELECTRIC INC | ER | P | 05/09/2012 | walls see plans | MIKEC | MIKEC | | ER | P | 4308198 |
GREEN ELECTRIC INC | ER | P | 04/26/2012 | consultation | BRET | BRET | | ER | P | 4302325 |
GREEN ELECTRIC INC | ER | P | 04/11/2012 | 1st floor bio med 2nd floor IT office wall only | BRET | BRET | | ER | P | 4295110 |
GREEN ELECTRIC INC | ER | P | 03/29/2012 | FIRE ALARM INSPECTION: see card | MIKEC | MIKEC | | ER | P | 4289366 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 08/20/2012 | | JON | JON | | H= | C | 4365256 |
COLORADO SHEET METAL CO., INC. | H= | C | 08/20/2012 | received balance report and plans have been spliced | JON | JON | | H= | C | 4365251 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 08/16/2012 | Recall inspection after plan review has been approved for changes. | JON | JON | | H= | P | 4363715 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 08/15/2012 | RUSS WAS NOT ON SITE FOR INSPECTION NEED TO RECALL WHEN ALL PREVIOUS NOTES ARE COMPLETED AND READY. | JON | JON | | H= | P | 4362120 |
COLORADO SHEET METAL CO., INC. | H= | P | 08/10/2012 | 1- Need plans revised for new storage room and new bath room including plumbing. 2-Need plans revised for new pump room. 3- Needs plans revised for elimination of the two crack units and removal of condensers, these units were replaced chilled water fan coils. 4- All new work to be called for inspection when ready. Roof equipment complete. Need balance report. | JON | JON | | H= | P | 4359374 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/12/2012 | ROUGH DUCT COMPLETE AT HALLWAYS AND SURGERY ROOMS. SEE TELEVAC EXHAUST WHEN READY AT SURGERY ROOMS. STILL NEED ALL EQUIPMENT ON ROOF INSPECTED. NEED SOILS ROOM COMPLETED WITH RADIATION DAMPERS INSTALLED AND SUPPORTED TO INSTRUCTIONS. NEED SMOKE SHUT DOWN INSTALLED AND BALANCE REPORT AT FINAL | JON | JON | | HD | P | 4340464 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/09/2012 | TEST OK AND OK FOR INSULATION ON LOW, MEDIUM, HIGH PRESSURE STEAM RETURNS AND LOW PRESSURE STEAM SUPPLY FROM ROOF EQUIPMENT TO 2ND FLOOR SHAFT. | JON | JON | | HWP | P | 4337962 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 06/07/2012 | 2nd floor hot water, test complete and ok to insulate. | JON | JON | | HWP | P | 4323086 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 05/31/2012 | BASEMENT 4" COPPER TO SHAFT FROM TIE IN MECH ROOM, 100 LB TEST COMPLETE AND OK FOR INSULATION CHILLED WATER ONLY. | JON | JON | | HWP | P | 4319033 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/23/2012 | Consulted on Televac smoke system. ok to wrap rest of systems. still need pent house and all main tie in's below roof line. Call Televac inspection when ready. Call inspection at surgery rooms when ready before tile. | JON | JON | | HD | P | 4315465 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/14/2012 | OK to wrap all rectangular duct. Fire damper at shaft wall ok, call for round duct inspection before wrap. | JON | JON | | HD | P | 4310769 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/08/2012 | OK TO WRAP ALL MEDIUM PRESSURE DUCTS. NEED PROPER SPACING AROUND FIRE/SMOKE DAMPER AT SHAFT WALL. | NANCY | NANCY | | HD | P | 4307685 |
COLORADO SHEET METAL CO., INC. | HD | P | 04/24/2012 | DUCT IN SHAFT OK, OK TO COVER, OK TO BUILD SHAFT WALL. | NANCY | NANCY | | HD | P | 4300968 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 08/21/2012 | PERMIT CORRECTED | JON | JON | | P= | C | 4365697 |
OLSON PLUMBING & HEATING COMPANY | P= | P | 08/20/2012 | STILL NO WATER CLOSET AND LAV ON PERMIT | LYNNIE | LYNNIE | | P= | P | 4365565 |
OLSON PLUMBING & HEATING COMPANY | PRD | C | 08/20/2012 | | LYNNIE | LYNNIE | | PRD | C | 4365557 |
OLSON PLUMBING & HEATING COMPANY | P= | P | 08/15/2012 | SCRUB SINK IN O.R. OK -- ADDING TOILET AND LAV (ASI-18), WALLS OK, STILL NEED UNDER FLOOR DWV --- WILL NEED TO REVISE JOB DISCRIPTION BY FINAL | LEE | LEE | | P= | P | 4362048 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/02/2012 | NORTH END | LYNNIE | LYNNIE | | PRD | P | 4304945 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/30/2012 | SOUTH END-SD/SDO | LYNNIE | LYNNIE | | PRD | P | 4303587 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 04/27/2012 | | LYNNIE | LYNNIE | | PTO | C | 4302807 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 04/20/2012 | CBG TO JOSH 499-2911===ALL DOMESTIC WATER LINES ARE OKAY--GET ROOF DRAINS ON PERMIT TOO===I OKAYD PARTIALS FOR ROOF DRAIN TESTS | LYNNIE | LYNNIE | | PTO | P | 4299669 |