GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 07/01/2013 | All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | C | 4554354 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/13/2013 | Additional Inspections Required: COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, GREEN ELECTRIC INC Electrical Final Inspection is not Completed yet. Need other sign offs | JOHNP | JOHNP | | B= | P | 4486133 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 03/05/2013 | OK after electrical sign off | JOHNP | JOHNP | | BFR | P | 4481549 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/20/2013 | OK after other sign offs | JOHNP | JOHNP | | BFR | P | 4474615 |
GREEN ELECTRIC INC | E= | C | 03/20/2013 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 4490880 |
GREEN ELECTRIC INC | ER | C | 03/20/2013 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | ER | C | 4490876 |
GREEN ELECTRIC INC | E= | C | 03/20/2013 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 4490873 |
GREEN ELECTRIC INC | E= | C | 03/20/2013 | | CRAIGS | CRAIGS | | E= | C | 4490864 |
GREEN ELECTRIC INC | ER | R | 03/05/2013 | Not ready | JOSEPH | JOSEPH | | ER | R | 4481803 |
GREEN ELECTRIC INC | E= | R | 03/05/2013 | FIRE ALARM INSPECTION: Not ready | JOSEPH | JOSEPH | | E= | R | 4481801 |
GREEN ELECTRIC INC | ER | R | 03/05/2013 | FIRE ALARM INSPECTION: Not ready | JOSEPH | JOSEPH | | ER | R | 4481790 |
GREEN ELECTRIC INC | ER | P | 02/22/2013 | wall outlets in room 3046 | JOSEPH | JOSEPH | | ER | P | 4475637 |
COLORADO SHEET METAL CO., INC. | H= | C | 07/01/2013 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4554353 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/15/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. FIRE DAMPER, ANGLES, MINI-SPLIT AND CONDENSATE ALL OK. | NANCY | NANCY | | H= | P | 4488136 |
COLORADO SHEET METAL CO., INC. | HRP | C | 03/08/2013 | 350 LB TEST OK ON LINESET FOR MINI-SPLIT. | NANCY | NANCY | | HRP | C | 4483763 |
COLORADO SHEET METAL CO., INC. | HD | P | 03/08/2013 | FRAMING FOR TRANSFER AIR FIRE DAMPER OK. OK TO INSTALL DAMPER AND ANGLES. | NANCY | NANCY | | HD | P | 4483760 |
COLORADO SHEET METAL CO., INC. | HD | P | 03/05/2013 | EP LAB: ABOVE CEILING OK. OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 4481503 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/19/2013 | ok to wrap medium and low pressure at EP lab. | JON | JON | | HD | P | 4473687 |