J. E. DUNN CONSTRUCTION COMPANY | B= | C | 08/25/2014 | All other required Final inspections are complete. (This is a computer generated result) | ED | ED | | B= | C | 4802809 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 02/14/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: dtortorice@springsgov.com or 385-5099), BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet, COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. Inspected on 2/13. building side ok, pending other inspections | ED | ED | | B= | P | 4687084 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 01/27/2014 | above ceiling penitrations / wall labeling ok | ED | ED | | BFR | P | 4677920 |
COLORADO SHEET METAL CO., INC. | BSP | T | 12/31/2013 | PAID (REC#1175084) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4664978 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 12/30/2013 | interior walls, and soffits ok, pending other inspections, will need above ceiling inspection, before final | ED | ED | | BFR | P | 4664208 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 12/17/2013 | walls west of corridor ok, ( marked on plans) | ED | ED | | BFR | P | 4658249 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 10/31/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet, COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet. conference rooms final ok, fire signed off., (phase 1) complete. -- Schedule a new Building Final when above items are complete. | ED | ED | | B= | P | 4633194 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 10/28/2013 | above ceilings at conference rooms ok | ED | ED | | BFR | P | 4630990 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 10/15/2013 | wall framing on sheet A110 ok, need to see penitrations sealed and wall labeling above ceilings | ED | ED | | BFR | P | 4622563 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/25/2014 | | MATTHEW | MATTHEW | | E= | C | 4802808 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 02/27/2014 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | E= | C | 4694168 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 02/11/2014 | gfci's installed ----- still need to look at procedure lights | CRAIGS | CRAIGS | | E= | P | 4685436 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 02/10/2014 | still need gfci protection at sink-----need to see the surgery lights installed----printed panel sch. -------rest ok -----------------see approved drawings for outlet and light locations ------ | BRIAN | BRIAN | | E= | P | 4684715 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 02/04/2014 | FIRE ALARM INSPECTION: FIRE ALARM-- complete | BRIAN | BRIAN | | E= | C | 4682675 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 02/04/2014 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | ER | C | 4682669 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 02/04/2014 | ceilings ok-----need to see surgery light at time of final | BRIAN | BRIAN | | ER | C | 4682649 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 01/30/2014 | ceiling marked on plans-------------- fire alarm was inspected same area | MATTHEW | MATTHEW | | ER | P | 4680838 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/30/2013 | FIRE ALARM INSPECTION: all walls | MATTHEW | MATTHEW | | ER | P | 4664409 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/30/2013 | all walls complete | MATTHEW | MATTHEW | | ER | P | 4664400 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/19/2013 | prep rooms and recovery walls | TOMC | TOMC | | ER | P | 4660664 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/17/2013 | FIRE ALARM INSPECTION: walls in GI prep area | MATTHEW | MATTHEW | | ER | P | 4658487 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/17/2013 | wall in GI prep area that do not have emergency system wiring installed | MATTHEW | MATTHEW | | ER | P | 4658484 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ESL | C | 11/21/2013 | under slab ok EMT is taped | BRIAN | BRIAN | | ESL | C | 4645989 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 10/30/2013 | 3 GI offices ok | MATTHEW | MATTHEW | | E= | P | 4632445 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/28/2013 | first floor 3 office ceilings for GI lab | MATTHEW | MATTHEW | | ER | P | 4630830 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/14/2013 | ----walls ok---- | BRIAN | BRIAN | | ER | P | 4622189 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 06/16/2014 | PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4758919 |
COLORADO SHEET METAL CO., INC. | H= | C | 03/06/2014 | REVISED TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4698502 |
COLORADO SHEET METAL CO., INC. | H= | P | 02/12/2014 | TEST AND BALANCE REPORT RECEIVED. SOME READINGS MISSING DUE TO LACK OF DIGITAL CONTROLS. PROVIDE REVISED REPORT OR LETTER FROM ENGINEER APPROVING THIS REPORT. | NANCY | NANCY | | H= | P | 4686339 |
COLORADO SHEET METAL CO., INC. | H= | P | 02/04/2014 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4682300 |
COLORADO SHEET METAL CO., INC. | H= | P | 02/03/2014 | ABOVE CEILING ALL OK EXCEPT STILL NEED TO SEE LAST SUPPLY INTO GI LAB 1337 INSTALLED. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4682093 |
COLORADO SHEET METAL CO., INC. | H= | P | 01/16/2014 | ABOVE CEILING WEST OF CORRIDOR ALL OK. | NANCY | NANCY | | H= | P | 4673207 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 01/15/2014 | 20 LB TEST OK ON LOW PRESSURE STEAM FOR HUMIDIFIERS. OK TO INSULATE AND LABEL. 20 LB TEST OK ON CONDENSATE FOR HUMIDIFIERS. OK TO INSULATE AND LABEL. NO HUMIDIFIERS INSTALLED YET. | NANCY | NANCY | | HWP | P | 4672084 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 12/31/2013 | ALL VAV FAN COIL PIPING OK FOR INSULATION AND LABELING | ROBERTV | ROBERTV | | HWP | P | 4665055 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/12/2013 | SHEET M401.31. ABOVE CEILING ALL OK, OK TO WRAP SUPPLY. NO EXHAUST THROUGH OUTSIDE WALL, HUMIDIFIERS OR CORRIDOR YET. | NANCY | NANCY | | HD | P | 4656019 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/28/2013 | THREE CONFERENCE ROOMS AND HALLWAY BETWEEN CONFERENCE ROOMS: ABOVE CEILING ALL OK INCLUDING FLEX AND DIFFUSERS. | NANCY | NANCY | | HD | P | 4630918 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/16/2013 | SEE SHEET M401.3A FOR DATE AND SIGNATURE. SUPPLY/RETURN/EXHAUST DUCTS AND LATERALS OK. OK TO WRAP SUPPLY. NO EXHAUST FANS, VAV'S YET. | NANCY | NANCY | | HD | P | 4623798 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 02/11/2014 | | JOEL | JOEL | | P= | C | 4685211 |
OLSON PLUMBING & HEATING COMPANY | P= | P | 02/10/2014 | lavs need mixing valves | JOEL | JOEL | | P= | P | 4684858 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 01/03/2014 | check 1-1/4'' hot tie in at final | JOEL | JOEL | | PTO | C | 4666244 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 12/17/2013 | h2o walls o.k dwv complete, revise h2o plan | JOEL | JOEL | | PTO | P | 4658534 |
OLSON PLUMBING & HEATING COMPANY | PB | C | 11/18/2013 | | JOEL | JOEL | | PB | C | 4643614 |