TURNER CONSTRUCTION COMPANY | B= | C | 05/14/2015 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4954715 |
TURNER CONSTRUCTION COMPANY | B= | P | 06/24/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), RK MECHANICAL, INC Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 4764025 |
TURNER CONSTRUCTION COMPANY | BFR | C | 06/24/2014 | | BERTW | BERTW | | BFR | C | 4764024 |
RK MECHANICAL, LLC | BSP | T | 06/09/2014 | PAID (REC#1202350) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: Relocating duct to eliminate fire dampers. | DALEH | DALEH | | BSP | T | 4753733 |
TURNER CONSTRUCTION COMPANY | BSP | T | 06/03/2014 | PAID (REC#1198394) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Add controls at assorted doors | MICHAELA | MICHAELA | | BSP | T | 4749828 |
TURNER CONSTRUCTION COMPANY | BSP | R | 05/01/2014 | after further review with mech inspector Mrs Nancy all penetration in all rated walls need to be firecaulked and inspected | BERTW | BERTW | | BSP | R | 4731296 |
TURNER CONSTRUCTION COMPANY | BFR | P | 04/03/2014 | ok pending other roughs completed | BERTW | BERTW | | BFR | P | 4714256 |
TURNER CONSTRUCTION COMPANY | B= | P | 04/03/2014 | guard shack and 2nd floor office space only ok pending other finals completed -- Schedule a new Building Final when above items are complete./need all door hardware installed | BERTW | BERTW | | B= | P | 4714236 |
TURNER CONSTRUCTION COMPANY | BFR | P | 02/26/2014 | guard shack ok | BERTW | BERTW | | BFR | P | 4693330 |
TURNER CONSTRUCTION COMPANY | BSP | P | 02/26/2014 | ffirecaulking above grid ok | BERTW | BERTW | | BSP | P | 4693329 |
TURNER CONSTRUCTION COMPANY | BFR | P | 02/19/2014 | 2nd floor walls ok/above grid firecaulking inspection required | BERTW | BERTW | | BFR | P | 4689578 |
TURNER CONSTRUCTION COMPANY | BSP | P | 01/13/2014 | inspections assigned to bert | BLAKE | BLAKE | | BSP | P | 4671025 |
LUDVIK ELECTRIC CO. | E= | C | 05/15/2014 | | MIKEC | MIKEC | | E= | C | 4739683 |
LUDVIK ELECTRIC CO. | ER | P | 04/11/2014 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 4719531 |
LUDVIK ELECTRIC CO. | ER | P | 02/27/2014 | CEILING ROOM 230---SECURITY DESK WALLS--- | BRIAN | BRIAN | | ER | P | 4694351 |
LUDVIK ELECTRIC CO. | ER | P | 02/19/2014 | SEE ORANGE CARD | MIKEC | MIKEC | | ER | P | 4689552 |
LUDVIK ELECTRIC CO. | ER | P | 01/31/2014 | WALLS | MIKEC | MIKEC | | ER | P | 4681720 |
RK MECHANICAL, LLC | H= | C | 09/03/2014 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4809244 |
RK MECHANICAL, LLC | H= | P | 06/23/2014 | MECHANICAL FINAL OK PENDING REVIEW OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4763352 |
RK MECHANICAL, LLC | H= | P | 05/30/2014 | TEST AND BALANCE REPORT RECEIVED. WAITING TO COMPARE BALANCE REPORT TO NEW REVISED/APPROVED PRINTS. LABEL ALL ACCESS DOORS, GRID AND EQUIPMENT. | NANCY | NANCY | | H= | P | 4748890 |
RK MECHANICAL, LLC | H= | P | 04/30/2014 | NEED REVISED/APPROVED PRINTS. LABEL ALL ACCESS DOORS, GRID AND EQUIPMENT. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4730238 |
RK MECHANICAL, LLC | HRP | C | 04/30/2014 | CONTINUOUS LINESETS, NO PRESSURE TEST REQUIRED. | NANCY | NANCY | | HRP | C | 4730235 |
RK MECHANICAL, LLC | HWP | C | 04/30/2014 | EQUIPMENT ALREADY UNDER WORKING PRESSURE. PIPING ALREADY INSULATED. NO VISIBLE LEAKS THROUGH INSULATION. CONTRACTOR HAS COVERED ALL PIPING AT THEIR OWN RISK. | NANCY | NANCY | | HWP | C | 4730234 |
RK MECHANICAL, LLC | HD | C | 04/16/2014 | BEFORE FINAL NEED INSPECTION ON CHILLED WATER AND REFRIGERATION PIPING. FOR FINAL NEED REVISED/APPROVED PRINTS, COMPLETE CONDENSATE DRAINS, LABEL ALL EQUIPMENT INCLUDING ROOF, LABEL ALL DAMPERS, PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | C | 4721273 |
RK MECHANICAL, LLC | HD | P | 03/20/2014 | CHANGED FROM HRR TO HD INSPECTION . INSPECTED RM 230 FOR 2 FIRE DAMPER FRAMING DETAILS. OK . ALSO 1ST FLOOR VAV-50 RELOCATED AND DUCT OK . FCU 16 RELOCATED UNIT AND DUCT OK | DAVIDH | DAVIDH | | HD | P | 4705951 |
RK MECHANICAL, LLC | HD | P | 03/18/2014 | CONFERENCE 201: ABOVE CEILING ALL OK, OK TO WRAP. COMPUTER/MIS: ABOVE CEILING ALL OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4704243 |
RK MECHANICAL, LLC | HD | P | 03/13/2014 | SECOND FLOOR. SHEET M121. FRAMING FOR TWO FIRE DAMPERS FOR FCU15 OK, OK TO INSTALL DAMPERS. NEED TO SEE DAMPER CLEARANCES BEFORE ANGLES ARE INSTALLED. SHEET M122. FAN COIL IN CORRIDOR OUTSIDE OF BATHROOMS OK. | NANCY | NANCY | | HD | P | 4702115 |
RK MECHANICAL, LLC | HD | P | 02/18/2014 | SHEET M122. SEE RFI 11. NEED REVISED/APPROVED PRINTS REMOVING VAV SHOWN AT END OF 14X12 SUPPLY TRUNK AND NEW VAV INSTALLED TO SUPPLY THE BATHROOMS AND ROOM 230. WILL ALSO NEED FIRE DAMPER REMOVED FROM PRINTS. ABOVE CEILING OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4688336 |