J. E. DUNN CONSTRUCTION COMPANY | B= | C | 06/30/2014 | All other required Final inspections are complete. (This is a computer generated result) | CHRISM | CHRISM | | B= | C | 4767791 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 06/27/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | CHRISM | CHRISM | | B= | P | 4767507 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 06/26/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet. missing vertical grab bars in restrooms -- Schedule a new Building Final when above items are complete. | CHRISM | CHRISM | | B= | P | 4766534 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 06/04/2014 | 6th floor framing above door 6400 "B" OK, will need fire caulk completed | DAN | DAN | | BFR | P | 4751121 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/02/2014 | above grid ok north wing up to but not including two hour wall section | CHRISM | CHRISM | | BSP | P | 4749096 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 05/16/2014 | above grid east wing | CHRISM | CHRISM | | BSP | P | 4740511 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 05/01/2014 | walls and soffits at nurses station and offices | CHRISM | CHRISM | | BFR | P | 4730770 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 04/17/2014 | walls in rooms 6316 to 6302 and 6317 to 6303, soffits in 6334 to 6318 | CHRISM | CHRISM | | BFR | P | 4721929 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 04/01/2014 | walls ok 6326 TO 6334, soffits ok, 6422 to 6436 | CHRISM | CHRISM | | BFR | P | 4712383 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 03/24/2014 | walls in corridors 6490, 6491, 6492 ok pending other roughs | CHRISM | CHRISM | | BFR | P | 4706952 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 03/17/2014 | walls ok 6418 to 6436, soffits ok 6404 to 6418 | CHRISM | CHRISM | | BFR | P | 4703311 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 03/03/2014 | walls ok room 6404 thru 6418 | CHRISM | CHRISM | | BFR | P | 4695712 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 01/31/2014 | inspections assigned to chris | BLAKE | BLAKE | | BSP | P | 4681115 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 06/27/2014 | | MATTHEW | MATTHEW | | E= | C | 4766727 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 06/27/2014 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | E= | C | 4766725 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 06/26/2014 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | E= | C | 4766656 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | T | 06/26/2014 | PAID (REC#1203811) ok to final once trip fee has been paid | MATTHEW | MATTHEW | | E= | T | 4766649 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 06/25/2014 | NORTH EAST WING--SEE PLANS ---DID NOT LOOK AT PANELS--- | BRIAN | BRIAN | | E= | P | 4765343 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 06/19/2014 | remainder of rough to include nurses station | MATTHEW | MATTHEW | | ER | C | 4761387 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/17/2014 | ceiling marked on plans | MATTHEW | MATTHEW | | ER | P | 4759490 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/17/2014 | FIRE ALARM INSPECTION: ceiling marked on plans | MATTHEW | MATTHEW | | ER | P | 4759489 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 06/16/2014 | FIRE ALARM INSPECTION: not ready | MATTHEW | MATTHEW | | ER | R | 4758407 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/16/2014 | elevator lobby ceiling ok | MATTHEW | MATTHEW | | ER | P | 4758405 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/12/2014 | Ceilings marked on plans and storage ceiling outside gym | MATTHEW | MATTHEW | | ER | P | 4756639 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/11/2014 | FIRE ALARM INSPECTION: walls in board room | MATTHEW | MATTHEW | | ER | P | 4755966 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/11/2014 | walls in board room and ceilings marked on plans | MATTHEW | MATTHEW | | ER | P | 4755965 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 06/05/2014 | inspected all panels and 45 kva xfmr in electrical room----- need plans revised showing feeder to panels NL6B sec 1 and 2 is now 150 amp----- feeder to panel EL6B not landed on 100 amp breaker at this time | MATTHEW | MATTHEW | | EP | P | 4751982 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/05/2014 | ceiling marked on approved plans | MATTHEW | MATTHEW | | ER | P | 4751962 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | L | 06/04/2014 | called 3 times to voice mail--- need to recall | MATTHEW | MATTHEW | | EP | L | 4751026 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/02/2014 | FIRE ALARM INSPECTION: marked and dated on prints---- ceilings only | GARYL | GARYL | | ER | P | 4749350 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 06/02/2014 | nurses station walls--marked and dated on prints | GARYL | GARYL | | ER | P | 4749344 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 05/30/2014 | FIRE ALARM INSPECTION: inspected patient rooms only------- cable not strapped | MATTHEW | MATTHEW | | ER | R | 4748483 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/29/2014 | ceilings only--marked and dated on prints | GARYL | GARYL | | ER | P | 4747576 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/27/2014 | see plans with the general contractor | CRAIGS | CRAIGS | | ER | P | 4746192 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/27/2014 | FIRE ALARM INSPECTION: see plans with the general | CRAIGS | CRAIGS | | ER | P | 4746191 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/20/2014 | FIRE ALARM INSPECTION: FIRE ALARM---BOX AND PIPE---SEE DRAWINGS | BRIAN | BRIAN | | ER | P | 4741962 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/20/2014 | WALLS SEE DRAWINGS---- | BRIAN | BRIAN | | ER | P | 4741961 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/19/2014 | WALLS IN ROOM 2229 ON 2ND FLOOR | BRIAN | BRIAN | | ER | P | 4741132 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/19/2014 | FIRE ALARM INSPECTION: -----FIRE ALARM BOXES AND CABLE----PART OF EAST WING CEILINGS | BRIAN | BRIAN | | ER | P | 4741120 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/13/2014 | FIRE ALARM INSPECTION: walls, hardlid and soffit marked on plans | MATTHEW | MATTHEW | | ER | P | 4737648 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/13/2014 | walls and soffit marked on plans--------- critical lights in cloud need to be hard piped (check plans) | MATTHEW | MATTHEW | | ER | P | 4737637 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/07/2014 | FIRE ALARM INSPECTION: FIRE ALARM PIPE AND BOXES----SEE PLANS---- | BRIAN | BRIAN | | ER | P | 4734614 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/07/2014 | WALLS AND SOFIT---SEE PLANS--- | BRIAN | BRIAN | | ER | P | 4734613 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/06/2014 | FIRE ALARM INSPECTION: area marked on plans ok | MATTHEW | MATTHEW | | ER | P | 4733304 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/06/2014 | walls and soffits marked on plans | MATTHEW | MATTHEW | | ER | P | 4733288 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/28/2014 | FIRE ALARM INSPECTION: FIRE ALARM STUBS / BOXES---NO WIRE 6302---6302T---6007---6009---6011 | BRIAN | BRIAN | | ER | P | 4728452 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/28/2014 | WALLS IN ROOMS-----6302--6302T---6007--6009--6011-------SOFIT NORTH WING WEST SIDE ROOMS----- | BRIAN | BRIAN | | ER | P | 4728428 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/22/2014 | walls and soffits marked on plans | MATTHEW | MATTHEW | | ER | P | 4724481 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/17/2014 | FIRE ALARM INSPECTION: walls marked on plans | MATTHEW | MATTHEW | | ER | P | 4722093 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/17/2014 | walls marked on plans | MATTHEW | MATTHEW | | ER | P | 4722087 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/16/2014 | walls and soffits marked on approved plans | MATTHEW | MATTHEW | | ER | P | 4721477 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/16/2014 | FIRE ALARM INSPECTION: area marked on approved plans | MATTHEW | MATTHEW | | ER | P | 4721472 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/08/2014 | walls marked on approved plans ok | MATTHEW | MATTHEW | | ER | P | 4716052 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/31/2014 | walls and soffits marked on plans | MATTHEW | MATTHEW | | ER | P | 4711817 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/26/2014 | soffits in 4 patient rooms; marked on plans | MATTHEW | MATTHEW | | ER | P | 4709002 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/24/2014 | walls---corridor and rooms marked on plans | MATTHEW | MATTHEW | | ER | P | 4707131 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/24/2014 | FIRE ALARM INSPECTION: corridor and rooms marked on plans | MATTHEW | MATTHEW | | ER | P | 4707122 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/13/2014 | walls marked on approved plans | MATTHEW | MATTHEW | | ER | P | 4701619 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/06/2014 | WALLS--rooms 6414--6416--6418--6422 | BRIAN | BRIAN | | ER | P | 4697942 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 02/27/2014 | patient rooms marked on approved set | MATTHEW | MATTHEW | | ER | C | 4694172 |
COLORADO SHEET METAL CO., INC. | H= | C | 06/26/2014 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4765713 |
COLORADO SHEET METAL CO., INC. | H= | P | 06/19/2014 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4761767 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 06/16/2014 | PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4758929 |
COLORADO SHEET METAL CO., INC. | H= | P | 06/13/2014 | INSTALL SMOKE DETECTION AT DAMPERS #1, 2 AND 8. ABOVE CEILING OK EXCEPT FOR CONFERENCE ROOM FOR THIS CONTRACTOR ONLY. | NANCY | NANCY | | H= | P | 4757754 |
COLORADO SHEET METAL CO., INC. | H16 | C | 06/11/2014 | LETTER FROM ARCHITECT APPROVING FIRE DAMPER FRAMING RECEIVED AND SCANNED. | NANCY | NANCY | | H16 | C | 4755364 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/05/2014 | DAMPER INSPECTION. DAMPER 3: PROVIDE LETTER FROM ENGINEER APPROVING INSTALLATION. DAMPERS 1 AND 6: OK. | NANCY | NANCY | | HD | P | 4752088 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/02/2014 | DAMPER INSPECTION. DAMPER 1: FRAMED TOO TIGHT. DAMPER 3: QUESTION REGARDING FRAMING, NOT OVER A DOOR LIKE APPROVED DIAGRAM SHOWS, PROVIDE ENGINEER LETTER SHOWING HOW THIS IS TO BE FRAMED. DAMPER 6: BOTTOM TRACK HAS BEEN NOTCHED FOR CONDUIT. DAMPERS 2, 5, 7, 8, 9, 10, 11 AND 12: OK. | NANCY | NANCY | | HD | P | 4749719 |
COLORADO SHEET METAL CO., INC. | H16 | C | 05/27/2014 | FRAMING FOR DAMPERS AND ARCHITECT LETTER APPROVING FRAMING RECEIVED AND SCANNED. | NANCY | NANCY | | H16 | C | 4745390 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 05/15/2014 | East Wing: Branches to VAV's ok in east wing only. | NANCY | NANCY | | HWP | P | 4739804 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/15/2014 | East Wing: Above ceiling all ok except still need to complete two bathrooms and corner suite. | NANCY | NANCY | | HD | P | 4739801 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 03/26/2014 | MAIN HW SUPPLY AND RETURN OK TO INSULATE, CHECK BRANCHES WHEN READY | ROBERTV | ROBERTV | | HWP | P | 4709406 |
COLORADO SHEET METAL CO., INC. | HD | P | 03/26/2014 | ALL DUCT ON PLAN PAGE M406 OK TO INSULATE. FIRE DAMPERS #3,8,9,10 NEED STRUCTURAL ENGINEER DETAIL TO PROVIDE INSTALLATION METHOD NOT LISTED BY MANUFACTURER SPANNING 7' BETWEEN FULL HEIGHT STUDS. FIRE DAMPER #1 NEEDS REFRAMED. FIRE DAMPER #2 AND #6 NEED HEADERS TO ATTACH TO FULL STUDS OR FRAME BOX HEADER ATTACHED TO FULL HEIGHT STUDS TO PROVIDE SUPPORT FOR PARTIAL FIRE DAMPER STUDS. FIRE DAMPERS #5,8,11,12 NOT READY. FIRE DAMPER #7 FRAMING IS OK. FIRE DAMPER #4 IS EXISTING | ROBERTV | ROBERTV | | HD | P | 4709401 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/28/2014 | SHEET M406. CIRCLED AREA IN GREEN: SUPPLY/RETURN AND EXHAUST ALL OK, OK TO WRAP. EXHAUST FIRE/SMOKE DAMPER FRAMING OK, OK TO COVER. SUPPLY AIR FIRE/SMOKE DAMPER FRAMING NOT OK, VERTICAL SUPPORTS NOT SCREWED TO HORIZONTAL FRAMING. | NANCY | NANCY | | HD | P | 4694831 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/11/2014 | SHEET M406. SUPPLY/RETURN/EXHAUST OK. OK TO WRAP SUPPLY AND RETURN. NO DAMPERS YET. | NANCY | NANCY | | HD | P | 4685413 |
COLORADO SHEET METAL CO., INC. | HD | R | 02/10/2014 | NO CALL AHEAD # GIVEN FOR RUSS IN REQUEST, NO PERSONNEL AT CONSTRUCTION ENTRANCE DESK OFF OF 6TH FLOOR, DOOR LOCKED TO CONSTRUCTION AREA. LEFT INSPECTION NOTICE (waived trip fee) | ROBERTV | ROBERTV | | HD | R | 4684970 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 06/24/2014 | | TIM | TIM | | P= | C | 4764572 |
OLSON PLUMBING & HEATING COMPANY | P= | R | 06/23/2014 | field cancelled | JOEL | JOEL | | P= | R | 4763329 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 05/28/2014 | DWV AND H2O IN ROOMS . 6336 , 6245 , 6008 , 6002 . TO COMPLETE | GABE | GABE | | PTO | C | 4746905 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 04/29/2014 | rooms 6302, 6007, 6009, 6011 | TIM | TIM | | PTO | P | 4729586 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 04/15/2014 | 6304-6316, 6309-6317 ok | TIM | TIM | | PTO | P | 4720756 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/31/2014 | rooms 6318 through 6334 as marked on plan. | DICK | DICK | | PTO | P | 4712123 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/19/2014 | 6417, 19, 21, 25...east side pto complete | TIM | TIM | | PTO | P | 4704797 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/14/2014 | rooms 6422 - 6436 dwv and h2o see plan | TIM | TIM | | PTO | P | 4702515 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/28/2014 | rooms 6404 thru 6420 even numbers as marked on plan. | DICK | DICK | | PTO | P | 4694834 |
OLSON PLUMBING & HEATING COMPANY | PTO | L | 02/27/2014 | LEFT CALL AHEAD MESSAGE WHEN ON WAY AND LEFT SECOND MESSAGE WHILE ON 6TH FLOOR AT CONSTRUCTION OFFICE, NEED TO RESCHEDULE. | DICK | DICK | | PTO | L | 4694469 |