HAIGH CONSTRUCTION, INC. | B= | C | 04/12/2017 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 5472611 |
HAIGH CONSTRUCTION, INC. | B= | P | 03/30/2017 | Building final is complete pending fire final. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | JEREMYA | JEREMYA | | B= | P | 5460816 |
HAIGH CONSTRUCTION, INC. | BFR | P | 03/14/2017 | Above ceiling in corridors and south stairwell complete / complete pending other Finals | RICHB | RICHB | | BFR | P | 5440639 |
HAIGH CONSTRUCTION, INC. | BIN | C | 03/08/2017 | Attic insulation and attic draft stop observed from roof top access doors OK // Training with Rich B. | JEREMYA | JEREMYA | | BIN | C | 5435422 |
HAIGH CONSTRUCTION, INC. | BFR | P | 01/24/2017 | Partition framing and lower level OK // Need to seal all penetrations above dropped ceiling in corridor | JEREMYA | JEREMYA | | BFR | P | 5397014 |
MATRIX ELECTRIC, INC. | BSP | T | 08/22/2016 | PAID (REC#1352069): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Changed service later to 500CU rather than AL. Revised upper level restroom and corridor. | BERTHA | BERTHA | | BSP | T | 5274491 |
MATRIX ELECTRIC, INC. | BSP | P | 07/18/2016 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: reduce scope of second floor installation ( E4, E5). | SHELBY | SHELBY | | BSP | P | 5247892 |
HAIGH CONSTRUCTION, INC. | BFR | P | 03/07/2016 | New wall framing at main level OK at new door / Still need mech inspection for damper framing | JEREMYA | JEREMYA | | BFR | P | 5149505 |
HAIGH CONSTRUCTION, INC. | BFR | P | 01/22/2016 | Framing at under stair storage on both north and south stairs OK / Elevator equipment room framing OK | JEREMYA | JEREMYA | | BFR | P | 5121676 |
HAIGH CONSTRUCTION, INC. | BIN | P | 01/11/2016 | Exterior thermal insulation OK / Interior fir barrier insulation OK | JEREMYA | JEREMYA | | BIN | P | 5113608 |
HAIGH CONSTRUCTION, INC. | BFR | P | 12/29/2015 | Exterior wall framing at second floor OK / Exterior wall of north stairs OK / Will need listings for corridor walls at first and second levels. Walls are metal stud on one side and wood stud on the other / Shaft liner installed at corridor lid on first level per ES Legacy report ER 3579 per approved plans / Will need to address red iron framing under stairs that isn't wrapped for fire protection / Will need to address PVC pipe penetrations at second floor rated assembly / Will need listed assembly for Glue-lam beam penetrating fire rated assembly at second floor. | JEREMYA | JEREMYA | | BFR | P | 5107058 |
HAIGH CONSTRUCTION, INC. | BIN | P | 12/14/2015 | Main level, exterior walls OK / Anchor bolts from frame inspection complete | JEREMYA | JEREMYA | | BIN | P | 5098460 |
HAIGH CONSTRUCTION, INC. | BFR | P | 12/10/2015 | Main level exterior walls ONLY / Need anchor bolts within 12" of plate breaks / OK to continue insulation | JEREMYA | JEREMYA | | BFR | P | 5096654 |
FRONTIER MECHANICAL SYSTEMS INC | BSP | T | 09/21/2015 | PAID (REC#1289107) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: New splice pages moving bath rooms has changed engineers. | TCRIPPEN | TCRIPPEN | | BSP | T | 5040417 |
MATRIX ELECTRIC, INC. | BSP | P | 09/21/2015 | PLAN SPLICE: (No Fee) by: DOUG for Electrical: New engineering firm Redraw. | DOUG | DOUG | | BSP | P | 5040356 |
HAIGH CONSTRUCTION, INC. | BLA | C | 07/08/2015 | | JEREMYA | JEREMYA | | BLA | C | 4988797 |
HAIGH CONSTRUCTION, INC. | BTR | P | 06/25/2015 | All but entry roof OK | JEREMYA | JEREMYA | | BTR | P | 4980928 |
HAIGH CONSTRUCTION, INC. | BLA | P | 05/19/2015 | Lath at south side of building up to entry OK | JEREMYA | JEREMYA | | BLA | P | 4957372 |
HAIGH CONSTRUCTION, INC. | BLA | P | 05/14/2015 | LAth at east side of bldg OK | JEREMYA | JEREMYA | | BLA | P | 4954954 |
HAIGH CONSTRUCTION, INC. | BLA | P | 05/04/2015 | North wall OK | JEREMYA | JEREMYA | | BLA | P | 4948661 |
HAIGH CONSTRUCTION, INC. | BSP | P | 04/08/2015 | Training with JA on B occ. VB construction core shell structures. | DANE | DANE | | BSP | P | 4932153 |
HAIGH CONSTRUCTION, INC. | BFR | P | 04/08/2015 | Met superintendent on-site. He gave me a structural letter for all field changes. Was only looking for a blessing to pour the second floor slab. No rough inspections have been completed yet. Will need to complete rough framing inspection once all other rough inspections have been completed / Training with Inspector Swennes on V-B, core/shell construction | JEREMYA | JEREMYA | | BFR | P | 4932115 |
HAIGH CONSTRUCTION, INC. | BSP | T | 02/05/2015 | PAID (REC#1246326) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Trusses | MICHAELA | MICHAELA | | BSP | T | 4897216 |
HAIGH CONSTRUCTION, INC. | BBB | C | 01/16/2015 | Bond beam at top of shaft OK | JEREMYA | JEREMYA | | BBB | C | 4886640 |
HAIGH CONSTRUCTION, INC. | BBB | P | 01/09/2015 | Bond beam at elevation 14' OK | JEREMYA | JEREMYA | | BBB | P | 4883206 |
HAIGH CONSTRUCTION, INC. | BFI | P | 11/24/2014 | R 10 along perimeter, still need engineer inspection letter for foundation, (note) trusses are still pending | ED | ED | | BFI | P | 4859147 |
HAIGH CONSTRUCTION, INC. | BFN | P | 11/05/2014 | Authorized third party inspection, CTL Thompson | JEREMYA | JEREMYA | | BFN | P | 4849145 |
HAIGH CONSTRUCTION, INC. | BFT | C | 11/05/2014 | Footing OK / Eufer in place / Also inspected by third party, contractor will provide letter | JEREMYA | JEREMYA | | BFT | C | 4849138 |
MATRIX ELECTRIC, INC. | E= | C | 08/30/2016 | | MATTHEW | MATTHEW | | E= | C | 5281061 |
MATRIX ELECTRIC, INC. | E= | P | 08/26/2016 | need gfci protection in pit except single outlet for sump-------------- no sprinklers installed at time of inspections; if sprinkler is installed at a later date all electrical will need to be 3r | MATTHEW | MATTHEW | | E= | P | 5279145 |
MATRIX ELECTRIC, INC. | E= | L | 08/25/2016 | called at 10:50 nobody on site 11:35 service disconnect turned off; no power to building I don't know why it's turned off so I'm not turning it on without talking to someone------------------ still need to verify all dedicated circuits to elevator pit are installed | MATTHEW | MATTHEW | | E= | L | 5277960 |
MATRIX ELECTRIC, INC. | E= | P | 08/23/2016 | need dedicated sump outlet in elevator pit | MATTHEW | MATTHEW | | E= | P | 5275896 |
MATRIX ELECTRIC, INC. | E= | R | 07/19/2016 | not ready: partial list: need plans revised showing correct service lat and adjusted AIC, finish panel schedules, need gear opened, install all lights and exit signs on plans, jumper PRV at water GEC, ground box and blank in electric room, OCPD for elevator over sized (110 amp max?), ground both disconnects in elevator room, gfci outlet in elevator room, need pit access, neutral fused in cab light disco------- inspected interior only; need access to roof and check exterior at time of re-inspect | MATTHEW | MATTHEW | | E= | R | 5248567 |
MATRIX ELECTRIC, INC. | EUG | P | 03/04/2016 | under slab electric heat for concrete | GARYL | GARYL | | EUG | P | 5148079 |
MATRIX ELECTRIC, INC. | ER | P | 03/01/2016 | hallways and stairwell drop ceilings ok | MATTHEW | MATTHEW | | ER | P | 5145270 |
MATRIX ELECTRIC, INC. | ES | C | 02/03/2016 | Commercial Service: 1200 amp 3 phase service for new core and shell: ok to set meter-------------------- INSPECTORS NOTE: BY FINAL NEED PLANS REVISED TO SHOW (4) SETS OF 500 CU SERVICE LATERALS AND NEW AIC; WATER GEC HAS NOT BEEN INSTALLED; CHECK AT FINAL | MATTHEW | MATTHEW | | ES | C | 5127725 |
MATRIX ELECTRIC, INC. | ES | R | 01/29/2016 | install service lateral, bond risers and meter, need neutral bonded in ct can | MATTHEW | MATTHEW | | ES | R | 5126210 |
MATRIX ELECTRIC, INC. | ER | P | 01/19/2016 | bath hardlids | MATTHEW | MATTHEW | | ER | P | 5117984 |
MATRIX ELECTRIC, INC. | ES | P | 01/05/2016 | Commercial Service: 400 amp 3 phase 208v service for house panel only; ok to set ct meter ---------------- contractor has an additional service that has not been built at this time which will require an additional shut down | MATTHEW | MATTHEW | | ES | P | 5109957 |
MATRIX ELECTRIC, INC. | ES | R | 12/31/2015 | install main bonding jumper, install brass tag, need plans revised showing 300 amp OCPD, grounding electrode conductor to water not installed-------inspected house panel service only;second service not ready | MATTHEW | MATTHEW | | ES | R | 5108404 |
MATRIX ELECTRIC, INC. | ER | P | 12/29/2015 | stairwell only | GARYL | GARYL | | ER | P | 5106577 |
MATRIX ELECTRIC, INC. | ER | P | 12/18/2015 | Second floor perimeter walls.----------!st floor bathroom and corridor walls. -----------Irreversible UFER inspected. | JOSEPH | JOSEPH | | ER | P | 5101451 |
MATRIX ELECTRIC, INC. | ER | P | 12/09/2015 | exterior walls main level | MATTHEW | MATTHEW | | ER | P | 5095275 |
MATRIX ELECTRIC, INC. | EUG | P | 11/05/2015 | underground to 1 pole light directly north of building and underground to pole light at southeast corner of bldg---------- verify concrete walkway on entire north side on bldg from back of curb to bldg (pcv 6" deep) | MATTHEW | MATTHEW | | EUG | P | 5073709 |
MATRIX ELECTRIC, INC. | EUG | P | 10/13/2015 | did not see any underground to inspect, I did a slab inspection------ (4) 3" pvc from exterior wall to interior wall (panel location? no plans on site), 1" from exterior wall to water stub inside bldg | MATTHEW | MATTHEW | | EUG | P | 5056183 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | C | 03/27/2017 | ELEVATOR COMPLETE | ERIC | ERIC | | HE= | C | 5456102 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 03/23/2017 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 5454321 |
FRONTIER MECHANICAL SYSTEMS INC | H= | P | 03/17/2017 | SCREEN ALL REGULATOR VENT TERMINATION ELBOWS. CALL IN FINAL INSPECTION. | NANCY | NANCY | | H= | P | 5444329 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 03/17/2017 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5444318 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 02/27/2017 | FIRE/SMOKE DAMPER FOR TRANSFER GRILL 2 ALL OK. | NANCY | NANCY | | HD | P | 5425506 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 01/25/2017 | FRAMING FOR TUNNEL CORRIDOR DAMPER OK. SPACING FOR DAMPER ABOVE DOUBLE DOOR OK, OK TO INSTALL ANGLES. | NANCY | NANCY | | HD | P | 5398562 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 01/23/2017 | UPPER LEVEL TUNNEL CORRIDOR: DAMPER FRAMING OK. LOWER LEVEL TUNNEL CORRIDOR: PROPERLY FRAME DAMPER OPENING. | NANCY | NANCY | | HD | P | 5396074 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 01/19/2017 | NEED F/SD INSTALLATION MANUAL WHEN READY TO VERIFY FRAMING | JERRYF | JERRYF | | HD | P | 5393198 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 01/18/2017 | NEED F/SD DAMPER FRAMING INSTALLATION MANUAL - NOT READY | JERRYF | JERRYF | | HD | P | 5392204 |
FRONTIER MECHANICAL SYSTEMS INC | HE | C | 01/05/2017 | | TERRI | TERRI | | HE | C | 5382766 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 03/16/2016 | ON SITE INSPECTION OF DAMPERS ABOVE DOUBLE DOOR. DAMPERS FRAMED AS PER ENGINEERS LETTER. ALTHOUGH THE DAMPER OPENINGS ARE NOT FRAMED AS PER MANUFACTURERS INSTRUCTIONS THE ENGINEER HAS APPROVED THIS FRAMING. OK TO INSTALL DAMPERS. NEED TO SEE ANNULAR SPACING BEFORE ANGLES ARE INSTALLED. PROVIDE FRAMING AND INSTALLATION INSTRUCTIONS FOR FIRE/SMOKE DAMPER IN TUNNEL CORRIDOR. PROVIDE LADDER TO SEE FRAMING AND DAMPER INSTALLATION. | NANCY | NANCY | | HD | P | 5156285 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 03/14/2016 | LETTER FROM MECHANICAL ENGINEER APPROVING DAMPER INSTALLATION ABOVE DOUBLE DOORS RECEIVED AND SCANNED. | NANCY | NANCY | | HD | P | 5153925 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 01/20/2016 | ENGINEER TO PROVIDE DETAILED DRAWING OF REQUIRED FRAMING FOR INSTALLING DAMPERS ABOVE 42 INCH WIDE DOOR. FRAME TUNNEL CORRIDOR DAMPER OPENING PER DAMPER MANUFACTURERS INSTRUCTIONS. | NANCY | NANCY | | HD | P | 5119605 |
FRONTIER MECHANICAL SYSTEMS INC | HI | C | 01/07/2016 | 10# OK ON ALL PIPING - AT FINAL CONFIRM SCREENS IN ALL REG VENTS - PIPING PER PLAN - 2# LETTER HAS BEEN RECIEVED | JERRYF | JERRYF | | HI | C | 5112040 |
FRONTIER MECHANICAL SYSTEMS INC | HC | C | 01/05/2016 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5110323 |
FRONTIER MECHANICAL SYSTEMS INC | HI | P | 01/05/2016 | 10 LB TEST OK ON MEDIUM PRESSURE GAS LINE FROM METER UP TO ROOF. OK TO COVER. NO GAS TO RTU'S YET. BY FINAL NEED LETTER FROM CSPU APPROVING MEDIUM PRESSURE FOR THIS ADDRESS. | NANCY | NANCY | | HI | P | 5110321 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 12/28/2015 | 1ST FLOOR: BATH EXHAUST ABOVE BATHROOM HARD LIDS AND CORRIDOR OK, NOT THROUGH FLOOR YET. 2ND FLOOR: RTU-1 AND RTU-2 SUPPLY AND RETURN MEDIUM PRESSURE TRUNK LINES AROUND ELEVATOR OK, OK TO WRAP. DUCTS NOT THROUGH FLOOR YET. RTU-3 18 X 16 SUPPLY DUCT OK, OK TO WRAP, NOT TURNED DOWN YET. ALL PVC MUST BE ISOLATED FROM RETURN PLENUMS. WILL NEED ACCESS TO EQUIPMENT ABOVE TUNNEL CORRIDORS. PROVIDE INSTALLATION INSTRUCTIONS FOR DAMPERS BEING INSTALLED IN TUNNEL CORRIDORS. VERIFY RTU SMOKE DETECTORS ARE BEING MONITORED AT FIRE PANEL, IF NOT WILL NEED REMOTE INDICATORS INSTALLED. | NANCY | NANCY | | HD | P | 5106278 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | L | 12/23/2015 | LOCKED AT 3:30 PM. | NANCY | NANCY | | HD | L | 5105203 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 12/14/2015 | RTU-3: SUPPLY TRUNK LINES ON 1ST AND 2ND FLOORS OK , OK TO WRAP. RTU-1: 16 X 14 AND 14 X 8 SUPPLY DUCTS ABOVE 1ST FLOOR TUNNEL OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 5098526 |
FRONTIER MECHANICAL SYSTEMS INC | P= | C | 03/24/2017 | CORRECTIONS MADE , HAMMER ARRESTER ABOVE BREAK ROOM | GABE | GABE | | P= | C | 5455191 |
FRONTIER MECHANICAL SYSTEMS INC | P= | P | 03/23/2017 | NEED HAMMER ARRESTER AT URINAL , REST OK , ELEVATOR SHAFT DISCHARGE OK , SINKS TEMPERED , WATER HEATER OK | GABE | GABE | | P= | P | 5454217 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | C | 01/20/2016 | | TED | TED | | PRD | C | 5119053 |
FRONTIER MECHANICAL SYSTEMS INC | PTO+ | C | 01/19/2016 | elevator pump discharge piping | TED | TED | | PTO+ | C | 5118657 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 12/23/2015 | 1st floor hallway, bathrooms, mech. room and drinking fountain dwv and water ok | TED | TED | | PTO | C | 5104788 |
FRONTIER MECHANICAL SYSTEMS INC | PB | C | 10/07/2015 | complete base permit per Lee Devlin, no more base work to be done | TED | TED | | PB | C | 5052030 |
FRONTIER MECHANICAL SYSTEMS INC | PB | P | 10/05/2015 | 1st floor ok | TED | TED | | PB | P | 5050557 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 05/07/2015 | no under deck clamps | JOEL | JOEL | | PRD | P | 4950860 |
FRONTIER MECHANICAL SYSTEMS INC | PB | P | 05/07/2015 | h20 service under slab o.k | JOEL | JOEL | | PB | P | 4950858 |