GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 09/14/2016 | phase 3 complete / staff dressing rooms OK | DANE | DANE | | B= | C | 5293061 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/28/2016 | staff changing rooms and bathroom framing OK pending other roughs except roll in shower / discussed accessible elements for roll in shower and placement of valves and hand held / need to inspect penetrations in smoke barrier after fixed | DANE | DANE | | BFR | P | 5256773 |
RK MECHANICAL, LLC | BSP | T | 03/02/2016 | PAID (REC#1339990) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: revised duct to larger size | DALEH | DALEH | | BSP | T | 5146360 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/02/2016 | PLAN SPLICE: (No Fee) by: DANM for Construction: Swapping changing/lockerrooms and staff toilet | DANM | DANM | | BSP | P | 5146337 |
RK MECHANICAL, LLC | BSP | T | 03/02/2016 | PAID (REC#1339990) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 3-3-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5146286 |
E LIGHT ELECTRIC SERVICES, INC | BSP | T | 03/02/2016 | PAID (REC#1339991) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise cath lab locker room | SHELBY | SHELBY | | BSP | T | 5146273 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 08/06/2015 | Partial for phase 2 pending mechanical and electric. Staff restroom work is being moved to phase 3 due to floor thickness. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), E LIGHT ELECTRIC SERVICES, INC Electrical Final Inspection is not Completed yet, RK MECHANICAL, INC Mechanical Final Inspection is not Completed yet, RK MECHANICAL, INC Plumbing Final Inspection is not Completed yet. | TOMG | TOMG | | B= | P | 5009119 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/22/2015 | Partial frame phase two walls only pending electric and plumbing. No ceiling areas were inspected. | TOMG | TOMG | | BFR | P | 4998976 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 07/08/2015 | phase (1) ok, pending other inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), E LIGHT ELECTRIC SERVICES, INC Electrical Final Inspection is not Completed yet, RK MECHANICAL, INC Mechanical Final Inspection is not Completed yet, RK MECHANICAL, INC Plumbing Final Inspection is not Completed yet. | ED | ED | | B= | P | 4988472 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/23/2015 | at Nurses holing room add smoke barrier labeling above ceiling - will need to inspect back of wall ( corridor side) at next inspection, at Reading room, fire tape between beam and wall,-- Ultra Sound room above ceiling ok, pending other inspections | ED | ED | | BFR | P | 4978718 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/19/2015 | Contractor had to leave jobsite. No inspection performed. | TOMG | TOMG | | BFR | P | 4976910 |
E LIGHT ELECTRIC SERVICES, INC | BSP | P | 05/21/2015 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | P | 4958918 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | T | 05/21/2015 | PAID (REC#1264450) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: REVISED MECHANICAL PLANS | RUSSELL | RUSSELL | | BSP | T | 4958863 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/15/2015 | wall framing ok - high light on sheet A101- pending other inspections, will need above grid inspection for smoke, fire partition walls | ED | ED | | BFR | P | 4955328 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | T | 05/08/2015 | PAID (REC#1262109) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: Revisions to mechanical | RUSSELL | RUSSELL | | BSP | T | 4951355 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | T | 05/07/2015 | PAID (REC#1262109) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise scope of work | MICHAELA | MICHAELA | | BSP | T | 4950555 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 08/29/2016 | | RANDY | RANDY | | E= | C | 5280364 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 08/29/2016 | FIRE ALARM INSPECTION: fire alarm rough and final ok | RANDY | RANDY | | E= | C | 5280362 |
E LIGHT ELECTRIC SERVICES, INC | ER | C | 08/29/2016 | FIRE ALARM INSPECTION: fire alarm rough and final ok | RANDY | RANDY | | ER | C | 5280361 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 08/19/2016 | above ceilings ok | RANDY | RANDY | | ER | P | 5273370 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 08/03/2016 | hard lid ok | RANDY | RANDY | | ER | P | 5260654 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 07/27/2016 | walls ok | RANDY | RANDY | | ER | P | 5255005 |
E LIGHT ELECTRIC SERVICES, INC | EE | L | 06/16/2016 | Renewed at 6/16/2016 11:26:51 AM | KENYATTA | KENYATTA | | EE | L | 5224026 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 08/18/2015 | public bathrooms, corridor, reception desk, waiting for splice sheets on locker room bathroom | GARYL | GARYL | | E= | P | 5017347 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 08/07/2015 | ceilings in public bathroom | GARYL | GARYL | | ER | P | 5010424 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 08/06/2015 | Final except: public bathroom, reception desk, locker room bathroom | GARYL | GARYL | | E= | P | 5009521 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 08/04/2015 | ceiling locker room ok partial pending staff bathroom rough. | BRET | BRET | | ER | P | 5007632 |
E LIGHT ELECTRIC SERVICES, INC | ER | R | 08/03/2015 | ceiling in locker room failed--low voltage on tiles, walls for reception desk and bath room walls ok, | GARYL | GARYL | | ER | R | 5006767 |
E LIGHT ELECTRIC SERVICES, INC | EP | P | 08/03/2015 | disconnect for cath/machine, cath equipment, and ceiling | GARYL | GARYL | | EP | P | 5006758 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 07/22/2015 | locker room walls | GARYL | GARYL | | ER | P | 4998857 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 07/10/2015 | Phase One is complete | GARYL | GARYL | | E= | P | 4991179 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 07/09/2015 | following OK: staff lounge, reading room 1 and 2, partial on ultra sound, nurse holding, | GARYL | GARYL | | E= | P | 4990061 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 06/29/2015 | "Cath-room" walls only | GARYL | GARYL | | ER | P | 4982726 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 06/25/2015 | FIRE ALARM INSPECTION: ok to cover ceilings, have red card on sight for next inspection (final?) | GARYL | GARYL | | ER | P | 4981220 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 06/22/2015 | marked /dated on approved set, ceilings | GARYL | GARYL | | ER | P | 4977925 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 05/22/2015 | walls only, marked, datd on prints | GARYL | GARYL | | ER | P | 4959950 |
RK MECHANICAL, LLC | H= | C | 09/09/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5288829 |
RK MECHANICAL, LLC | H= | P | 09/07/2016 | CORRECTIONS MADE ON TWO FIRE SMOKE DAMPERS, LAST TIE IN COMPLETE ON MEDIUM PRESSURE SYSTEM.. NOTE: PENDING TEST AND BALANCE REVIEW. | LUKE | LUKE | | H= | P | 5287159 |
RK MECHANICAL, LLC | HD | P | 08/29/2016 | REMOVE FIRE CAULK FROM AROUND DAMPER PROPERLY INSTALL BREAK AWAY CONNECTIONS AT BOTH DAMPERS. | NANCY | NANCY | | HD | P | 5280828 |
RK MECHANICAL, LLC | HD | P | 08/25/2016 | QUESTION REGARDING DAMPER FRAMING. RESCHEDULED INSPECTION FOR TOMORROW. | NANCY | NANCY | | HD | P | 5278090 |
RK MECHANICAL, LLC | HD | P | 08/19/2016 | FIRE DAMPER FRAMING OK IN CORRIDOR A-1-5 10X10 AND 50X18 TWO DAMPERS TOTAL. OK TO FINISH SHEET ROCK UP TO THE DAMPERS. | LUKE | LUKE | | HD | P | 5273625 |
RK MECHANICAL, LLC | H16 | C | 08/17/2016 | THIS IS A NOTE TO THE INSPECTOR GOING TO THIS JOB SITE ON FRIDAY 8/19/16. PLEASE CONTACT JOHN AT 491-4527 TO FIND OUT WHERE TO MEET HIM AT MEMORIAL NORTH HOSPITAL. THIS INSPECTION IS TO LOOK AT A COUPLE OF FIRE DAMPER FRAMES THAT GOT COVERED UP PRIOR TO SEEING THE CORRECTIONS THAT NEEDED TO BE MADE. JOHN IS GOING TO REMOVE THE SHEET ROCK FROM AROUND THE FRAMED OPENINGS WIDE ENOUGH SO YOU CAN SEE THE HORIZONTAL ATTACHMENTS AT THE KING STUDS. THE KING STUDS WERE FINE AT THE ORIGINAL INSPECTION, HE DOES NOT HAVE TO REMOVE THE ROCK FROM FLOOR TO CEILING. HE IS SUPPOSED TO HAVE THE DAMPER INSTALLATION INSTRUCTIONS ON SITE. DO NOT FINAL OUT THE PERMIT, THERE IS SOME NEW WORK GOING ON SHOWN ON THE LATEST SPLICE PLUS ALL THE ORIGINAL WORK STILL NEEDS A TEST AND BALANCE REPORT. THANKS. | NANCY | NANCY | | H16 | C | 5271952 |
RK MECHANICAL, LLC | HD | P | 08/17/2016 | M201 ASI700: RELOCATED DIFFUSERS ABOVE CEILING IN STAFF TOILET AND SHOWER OK. THIS AREA OK EXCEPT NEED TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | P | 5271635 |
RK MECHANICAL, LLC | HD | P | 08/05/2016 | M201, ASI008: TB286 MEDIUM AND LOW PRESSURE SUPPLY AIR OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 5263315 |
RK MECHANICAL, LLC | H= | P | 06/28/2016 | Partialed to reopen permit. | JACK | JACK | | H= | P | 5233232 |
RK MECHANICAL, LLC | HE | L | 06/16/2016 | Renewed at 6/16/2016 11:26:56 AM | KENYATTA | KENYATTA | | HE | L | 5224027 |
RK MECHANICAL, LLC | HD | P | 08/10/2015 | PROPERLY FRAME FIRE/SMOKE DAMPERS IN WALL. LABEL ACCESS DOORS AND GRID. | NANCY | NANCY | | HD | P | 5011691 |
RK MECHANICAL, LLC | H= | P | 08/05/2015 | M201. LOCKER ROOM PROPER ALL COMPLETE EXCEPT FOR TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5008807 |
RK MECHANICAL, LLC | HD | P | 08/05/2015 | M201. FRAME FIRE/SMOKE DAMPERS PER MANUFACTURERS INSTRUCTIONS. FAN COIL ROOM AND SHOWER ROOM ABOVE CEILING OK. OK TO WRAP FAN COIL SUPPLY DUCT. NO CEILING IN SHOWER YET. | NANCY | NANCY | | HD | P | 5008806 |
RK MECHANICAL, LLC | H= | P | 07/24/2015 | PHASE 1 NURSES HOLDING: ALL COMPLETE EXCEPT STILL NEED TEST AND BALANCE REPORT AND REVISED/APPROVED PRINTS. PHASE 2 CATH LAB: ALL COMPLETE EXCEPT STILL NEED TEST AND BALANCE REPORT AND REVISED/APPROVED PRINTS. | NANCY | NANCY | | H= | P | 5000593 |
RK MECHANICAL, LLC | HD | P | 07/24/2015 | PHASE 2.CATH LAB: ABOVE CEILING ALL OK, LOCKER ROOM AREA: VAV 285 LOW PRESSURE SUPPLY AIR OK, OK TO WRAP. STILL NEED REST OF LOCKER ROOM AREA AND DAMPERS INSTALLED IN PUBLIC BATHROOMS. | NANCY | NANCY | | HD | P | 5000590 |
RK MECHANICAL, LLC | HD | P | 06/23/2015 | M201. PHASE 1 ABOVE CEILING OK. NEED REVISED/APPROVED PRINTS BY FINAL. SEE NOTES DATED 6/23/15 REGARDING DAMPERS ETC. | NANCY | NANCY | | HD | P | 4979356 |
RK MECHANICAL, LLC | HD | P | 06/05/2015 | M201. SUPPLY/RETURN AND EXHAUST ABOVE CEILINGS OK. OK TO WRAP SUPPLIES. SEE HAND WRITTEN NOTES ON THIS M201 REGARDING POSSIBLE CHANGES IN LOCATION OF DUCTS AND DAMPERS. | NANCY | NANCY | | HD | P | 4968123 |
RK MECHANICAL, LLC | HRR | P | 05/29/2015 | SHEET M201 DATED 3/26/15. SUPPLY/RETURN IN HOLDING AREAS EXCEPT HOLDING A1302 OK. OK TO WRAP SUPPLIES. NO EXHAUST YET. NEED REVISED/APPROVED PRINTS. | NANCY | NANCY | | HRR | P | 4963607 |
RK MECHANICAL, LLC | P= | C | 08/19/2016 | NOTE : ALL TO PLAN , TEMPERING AT SINK | GABE | GABE | | P= | C | 5274091 |
RK MECHANICAL, LLC | PTO | P | 07/28/2016 | CATH LAB LOCKER , DWV AND WATER ON TEST , NEED TO FIND LOCATION OF SHOWER TO FINAL PTO | GABE | GABE | | PTO | P | 5256756 |
RK MECHANICAL, LLC | P= | P | 08/06/2015 | SCRUB SINK AT CATH LAB OK | GABE | GABE | | P= | P | 5009682 |
RK MECHANICAL, LLC | PTO | P | 08/05/2015 | SCRUB SINK IN LOCKER ROOM , DWV AND WATER | GABE | GABE | | PTO | P | 5008775 |
RK MECHANICAL, LLC | PTO+ | P | 08/03/2015 | NORTH SIDE CATH LAB SINK DWV AND WATER OK | GABE | GABE | | PTO+ | P | 5006120 |
RK MECHANICAL, LLC | P= | P | 07/10/2015 | ULTRA SOUND COMPLETE , STAFF LOUNGE OK , DUAL CHECKS AT ALL WATER CONNECTED APPLIANCES , PHASE ONE COMPLETE | GABE | GABE | | P= | P | 4990417 |
RK MECHANICAL, LLC | P= | P | 06/26/2015 | PATIENT HOLDING OK , ULTRA SOUND SINKS TEMPERED , ULTRA SOUND BATH ROOM NOT READY . | GABE | GABE | | P= | P | 4982078 |
RK MECHANICAL, LLC | PB | P | 06/15/2015 | CORRECTIONS MADE IN CATH LAB WATER PIPING , ULTRA SOUND BATH AND HAND WASH SINK DWV AND WATER OK , ALL DWV IN CLEAN AND STERILE CEILING OK | GABE | GABE | | PB | P | 4973662 |
RK MECHANICAL, LLC | PB | T | 06/12/2015 | PAID (REC#1267626) AFTER-HOURS INSPECTION: $200 From: TERRI 6/15/15 mon 5 p.m, | TERRI | TERRI | | PB | T | 4972058 |
RK MECHANICAL, LLC | PTO | P | 06/10/2015 | CATH LAB DOMESTIC ONLY . WATER UNDERSIZED AT BATH ROOM HOT , REST OK | GABE | GABE | | PTO | P | 4970436 |
RK MECHANICAL, LLC | PTO | R | 06/09/2015 | NO CONTACT # , WHERE IS PROJECT | GABE | GABE | | PTO | R | 4969978 |