GREAT WEST CONSTRUCTION, LLC | B= | C | 12/09/2016 | All other finals completed | NELIDA | NELIDA | | B= | C | 5364716 |
PROCOM ELECTRICAL SERVICES, INC. | BSP | T | 12/06/2016 | PAID (REC#1387314) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added 100A/3P disconnect. | BERTHA | BERTHA | | BSP | T | 5361212 |
GREAT WEST CONSTRUCTION, LLC | B= | P | 11/28/2016 | Temp CO: all partials ( Expires: 12/28/2016 12:00:00 AM) | JANE | JANE | | B= | P | 5353410 |
GREAT WEST CONSTRUCTION, LLC | B= | P | 11/23/2016 | pending other final inspections / west wall sealing completed. Additional Inspections Required (computer generated): HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet. | ERICR | ERICR | | B= | P | 5352920 |
HVAC SOLUTIONS, INC. | BSP | T | 11/16/2016 | PAID (REC#1382668) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised to show radiation dampers in bathroom 305 | JUSTINC | JUSTINC | | BSP | T | 5345910 |
GREAT WEST CONSTRUCTION, LLC | BSP | P | 11/10/2016 | Above ceiling penetrations at all rated assemblies OK in all areas except west end of suite. Contractor to leave ceiling tiles out in areas for inspection at final // Wall designations marked above ceiling on all rated assemblies | JEREMYA | JEREMYA | | BSP | P | 5341556 |
GREAT WEST CONSTRUCTION, LLC | BSP | T | 11/09/2016 | PAID (REC#1380570) PLAN SPLICE FEE: $50 by: DANM for Construction: Revise note regarding gyp in corridors | DANM | DANM | | BSP | T | 5340029 |
GREAT WEST CONSTRUCTION, LLC | BIN | C | 10/06/2016 | Insulation all installed at exterior walls and all sound insulation throughout interior space complete / Detail for wall termination at windo on file | JEREMYA | JEREMYA | | BIN | C | 5312435 |
GREAT WEST CONSTRUCTION, LLC | BFR | P | 09/21/2016 | Need peentration details for bar joists running through rated assemblies / Need detail for wall termination detail at exterior window / Complete other roughs / Need to have mechanical inspector inspect all damper framing prior to covering. | JEREMYA | JEREMYA | | BFR | P | 5298893 |
GREAT WEST CONSTRUCTION, LLC | BFR | R | 09/16/2016 | Call ahead was done, talked to contractor and informed him I would be along within 30 min. All was OK. Upon arrival, all workers, including general contractor, had left and suite was locked. Next wasted trip WILL result in a trip fee. Complete all other rough inspections prior to recalling the frame inspection. | JEREMYA | JEREMYA | | BFR | R | 5295885 |
PROCOM ELECTRICAL SERVICES, INC. | BSP | P | 08/31/2016 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Additional outlets in clouded areas on plans | SHELBY | SHELBY | | BSP | P | 5282582 |
HVAC SOLUTIONS, INC. | BSP | P | 08/31/2016 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised to add EF to closet | JUSTINC | JUSTINC | | BSP | P | 5282542 |
GREAT WEST CONSTRUCTION, LLC | BSP | T | 08/29/2016 | PAID (REC#1355806) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise floor plan | MICHAELA | MICHAELA | | BSP | T | 5280043 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 12/09/2016 | corrections made | RANDY | RANDY | | E= | C | 5364590 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 12/07/2016 | label new disconnect and bond water in area served by xfmr | MATTHEW | MATTHEW | | E= | P | 5362768 |
PROCOM ELECTRICAL SERVICES, INC. | E= | R | 11/28/2016 | need disconnect for xfmr secondaries within 10' or meet the requirements of 240.21(C)(6), bond water to building steel in area being served by xfmr, need #6cu supply side bonding jumper between xfmr and panel, #12 on 40 amp breaker inside type 3 em panel, label em panel where fed from and circuits | MATTHEW | MATTHEW | | E= | R | 5354293 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 11/23/2016 | Rms 300 - 309 OK Rm 310 - needs gfi protection Rms 315 & 316- EM receptacles not working or have reverse polarity Rms 317 - 320 OK | TOMC | TOMC | | E= | P | 5352968 |
PROCOM ELECTRICAL SERVICES, INC. | EP | P | 11/23/2016 | panel L3D 100 amp 120/208 MB ----all panels need index , panel labels , flash stickers | TOMC | TOMC | | EP | P | 5352965 |
PROCOM ELECTRICAL SERVICES, INC. | ER | C | 11/23/2016 | rough in complete | TOMC | TOMC | | ER | C | 5352953 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 11/16/2016 | FIRE ALARM INSPECTION: fire alarm rough ok | MATTHEW | MATTHEW | | E= | C | 5346399 |
PROCOM ELECTRICAL SERVICES, INC. | ER | C | 11/16/2016 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | ER | C | 5346381 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 11/15/2016 | ceilings NOT ready are marked and dated on prints, alarm not ready | GARYL | GARYL | | ER | P | 5344875 |
PROCOM ELECTRICAL SERVICES, INC. | ER | R | 11/10/2016 | ceiling---- too many loose ends | MATTHEW | MATTHEW | | ER | R | 5341799 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 09/22/2016 | walls ok---leave rock above panels off for panel inspection. | RANDY | RANDY | | ER | P | 5300028 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 09/22/2016 | FIRE ALARM INSPECTION: fire alarm wall rough ok-----no red card on site | RANDY | RANDY | | ER | P | 5300023 |
HVAC SOLUTIONS, INC. | H= | C | 12/08/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5363157 |
HVAC SOLUTIONS, INC. | H= | P | 12/07/2016 | CONDENSER HAS BEEN LABELED - STILL NEED TAB REPORT | JERRYF | JERRYF | | H= | P | 5362272 |
HVAC SOLUTIONS, INC. | H= | P | 11/23/2016 | PERMANENTLY LABEL CONDENSER WITH SUITE NUMBER. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5352710 |
HVAC SOLUTIONS, INC. | HD | P | 11/16/2016 | PROVIDE INSTALLATION INSTRUCTIONS FOR HEPA SUPPLY DIFFUSERS IN OR. COMPLETE FC-1. INSTALL BACK DRAFT DAMPER IN OUTSIDE AIR DUCT OF FC-1. COMPLETE HUMIDIFIER. INSTALL ALL DAMPER ACCESS DOORS. INSTALL RETAINING ANGLES ON DAMPER ABOVE TOILET 305 DOOR. PROVIDE INSTALLATION INSTRUCTIONS FOR CEILING RADIATION DAMPERS INSTALLED IN TOILET 305. REST ABOVE CEILING OK. BY FINAL LABEL GRID TO SHOW DAMPER LOCATIONS. | NANCY | NANCY | | HD | P | 5346357 |
HVAC SOLUTIONS, INC. | HD | P | 11/08/2016 | NEED REVISED/APPROVED PRINTS SHOWING HOW THE CEILING IN TOILET 305 IS BEING PROTECTED, LOOKS LIKE A RATED CEILING HAS BEEN BUILT. ABOVE CEILING IN NURSING, PRE-OP, CORRIDOR, POST-OP, AND RECEPTION OK. FRAMING FOR DAMPER ABOVE TOILET 305 DOOR OK. | NANCY | NANCY | | HD | P | 5339615 |
HVAC SOLUTIONS, INC. | HD | P | 10/17/2016 | FC-1: SUPPLY AND RETURN DUCTS AND LATERALS ABOVE "OR" CEILING OK, OK TO WRAP. CONDENSATE DRAIN IN WALL OF JANITOR ROOM OK, OK TO COVER. RECEPTION 309: MEDIUM/LOW PRESSURE SUPPLIES ABOVE SOFFIT AREA OK, OK TO WRAP. REST OF LOW PRESSURE SUPPLY TRUNK LINES AND LATERALS OK, OK TO WRAP. FIVE NEW DAMPERS: DAMPERS AND RETAINING ANGLES OK. WAITING 307, DAMPER OVER DOOR: FRAMING, DAMPER AND ANGLES OK. EXHAUST: SEAL ALL MISSED JOINTS ON EXHAUST DUCTS. NO EQUIPMENT, FLEX, OR DIFFUSERS YET. BY FINAL INSTALL DAMPER ACCESS DOORS. | NANCY | NANCY | | HD | P | 5320073 |
HVAC SOLUTIONS, INC. | HD | P | 10/05/2016 | FRAMING FOR FIVE NEW DAMPERS OK, OK TO COVER. OK TO INSTALL DAMPERS. WAITING 307: DAMPER OVER DOOR AND 48 X 18 DAMPERS: KING STUDS OK, OK TO INSTALL ROCK UP TO 10 FEET ABOVE FLOOR ONLY. | NANCY | NANCY | | HD | P | 5310853 |
HVAC SOLUTIONS, INC. | HD | P | 09/23/2016 | ADD SUITE NUMBER ONTO PERMIT. FRAME ALL DAMPER OPENINGS PER DAMPER MANUFACTURERS INSTRUCTIONS. | NANCY | NANCY | | HD | P | 5301621 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 12/08/2016 | CORRECTIONS MADE , ALL TO PLAN | GABE | GABE | | P= | C | 5363096 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 11/23/2016 | NEED HAMMER ARRESTER AT HUMIDIFIER AS PER MFR , REST OK AND TO PLAN | GABE | GABE | | P= | P | 5353173 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 10/28/2016 | NOTE : UNDER BELLY , DWV ONLY ALL ON TEST TO PLAN | GABE | GABE | | PTO | C | 5330176 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | T | 10/27/2016 | PAID (REC#1376443) AFTER-HOURS INSPECTION: $200 From: JESSIE Friday 10-28-16 6:30 am | JESSIE | JESSIE | | PTO | T | 5329398 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 10/05/2016 | IN WALL DWV AND COPPER ON TEST TO PLAN , NEED TO SPLICE PLANS FOR NEW SINK AND WATER HEATER LOCATION , | GABE | GABE | | PTO | P | 5311397 |