MAHLER GC GENERAL CONTRACTING COMPANY | B= | C | 03/14/2017 | All other required Final inspections are complete. (This is a computer generated result) | DALE | DALE | | B= | C | 5440191 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | P | 03/10/2017 | complete all other inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection HD= by HEALTHDEPT is not Completed yet, CASCADE PLUMBING & HEATING Plumbing Final Inspection is not Completed yet. | DALE | DALE | | B= | P | 5437430 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | R | 03/09/2017 | complete all other inspections / need signage for restrooms, doors and occupant load. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection HD= by HEALTHDEPT is not Completed yet, AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, CASCADE PLUMBING & HEATING Plumbing Final Inspection is not Completed yet, MEYER ELECTRIC Electrical Final Inspection is not Completed yet, PREMIER MECHANICAL Mechanical Final Inspection is not Completed yet. | DALE | DALE | | B= | R | 5436208 |
MEYER ELECTRIC | BSP | T | 02/16/2017 | PAID (REC#1403053) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: revise one line | SHELBY | SHELBY | | BSP | T | 5416971 |
MAHLER GC GENERAL CONTRACTING COMPANY | BFR | P | 01/30/2017 | walls ok pending all other inspections / ceiling joists have not been cut for equipment / went over accessible elements with contractor | DALE | DALE | | BFR | P | 5401404 |
INTERMOUNTAIN POWER SERVICES INC | E= | C | 03/08/2017 | Disconnect moved to other side of RTU and has proper working clearance. | DEAN | DEAN | | E= | C | 5434487 |
INTERMOUNTAIN POWER SERVICES INC | E= | R | 03/07/2017 | electrician not on site | TOMC | TOMC | | E= | R | 5433039 |
INTERMOUNTAIN POWER SERVICES INC | E= | P | 03/02/2017 | pending working clearance for rtu disconnect for gas line | TIMA | TIMA | | E= | P | 5429809 |
INTERMOUNTAIN POWER SERVICES INC | E= | P | 02/28/2017 | need 20 amp breaker for walk-in compressor,need gfci breaker for diswasher,need arc flash sticker and where panel fed from labeling,breaker lock out for hand dryers,label roof top disconnects,need wires inside rtu in raceway,--rest ok-- | TIMA | TIMA | | E= | P | 5427563 |
INTERMOUNTAIN POWER SERVICES INC | EP | C | 02/28/2017 | 200 amp sub panel ok | TIMA | TIMA | | EP | C | 5427557 |
INTERMOUNTAIN POWER SERVICES INC | EP | R | 02/24/2017 | equipment ground wire at exterior disconnect needs to be terminated to disconnect enclosure not neutral bar | TIMA | TIMA | | EP | R | 5424592 |
INTERMOUNTAIN POWER SERVICES INC | ER | C | 02/24/2017 | | TIMA | TIMA | | ER | C | 5424590 |
BJ COMPANY, LLC | E= | C | 02/15/2017 | FIRE ALARM INSPECTION: fplp cable | TIMA | TIMA | | E= | C | 5416091 |
INTERMOUNTAIN POWER SERVICES INC | ES | C | 01/26/2017 | Commercial Service: already completed | TIMA | TIMA | | ES | C | 5399698 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 01/26/2017 | walls ok | TIMA | TIMA | | ER | P | 5399689 |
MEYER ELECTRIC | EP | R | 12/06/2016 | need to check sub panel and feeder at service disconnect------need plans revised to show 250 al service and feeder instead of 3/0 cu--- | TIMA | TIMA | | EP | R | 5361713 |
MEYER ELECTRIC | ES | C | 12/06/2016 | Commercial Service: 200 amp 3/w ok to set meter | TIMA | TIMA | | ES | C | 5361710 |
MEYER ELECTRIC | ES | R | 12/05/2016 | need service conductors installed to line side of disconnect | TIMA | TIMA | | ES | R | 5360295 |
AIRTECH MECHANICAL, INC. | H= | C | 03/10/2017 | ALL CORRECTIONS MADE | JERRYF | JERRYF | | H= | C | 5437062 |
AIRTECH MECHANICAL, INC. | H= | P | 03/09/2017 | NEED WH FLUE CLAIMED ON PERMIT - NEED FILTER DOOR AND FILTER AT FURNACE - REST OK - INTERLOCKS OK | JERRYF | JERRYF | | H= | P | 5436329 |
PREMIER MECHANICAL | H= | C | 03/09/2017 | ALL OK | JERRYF | JERRYF | | H= | C | 5436323 |
PREMIER MECHANICAL | HC | C | 03/02/2017 | RELEASE METER FOR 23 SYSTEM | JERRYF | JERRYF | | HC | C | 5429749 |
PREMIER MECHANICAL | HI | C | 03/02/2017 | PRESSURE TEST OK - PIPING PER PLAN - AT FINAL VERIFY ALL REGS / LIMITERS AND FINAL CONNECTIONS AT INTERIOR - ADD 2 STUBS TO PERMIT - ROOF IS COMPLETE ALL LABELS / REGS AND VENTS ARE INSTALLED - BY FINAL NEED 2# LETTER FROM GAS SUPPLIER | JERRYF | JERRYF | | HI | C | 5429703 |
AIRTECH MECHANICAL, INC. | H= | P | 03/02/2017 | TAB REPORT RECEIVED - STILL NEED ALL OTHER ITEMS ADDRESSED | JERRYF | JERRYF | | H= | P | 5429034 |
ALNOR INC. | H= | C | 03/01/2017 | OK NOTE TO CONTRACTOR WILL NEED PRESSURE TEST ON ALL FUTURE COOLER INSPECTIONS | JERRYF | JERRYF | | H= | C | 5428276 |
PREMIER MECHANICAL | H16 | C | 03/01/2017 | NEED WATER HEATER VENT CLAIMED ON PERMIT AND INSPECTION CALLED WHEN READY - HAD CONSULT WITH PLUMBING CONTRACTOR ON SERVICE ACCESS FOR WATER HEATER MAY BE A HEIGHT CLEARANCE PROBLEM WILL NEED INSTALL MANUAL TO VERIFY | JERRYF | JERRYF | | H16 | C | 5428272 |
AIRTECH MECHANICAL, INC. | H= | P | 02/27/2017 | NEED THE FOLLOWING INSPECTIONS - ROOF / INTERLOCKS / TAB / GREASE WRAP / CO2 SENSOR PER PLAN / CONDENSATE DRAINS AT FURNACE AND COIL - REST OF ABOVE CEILING SA/RA GRILLES OK | JERRYF | JERRYF | | H= | P | 5425532 |
ALNOR INC. | H16 | C | 02/27/2017 | NEED HRP INSPECTION | JERRYF | JERRYF | | H16 | C | 5425527 |
PREMIER MECHANICAL | HI | P | 02/13/2017 | Keep on test and recall when all piping on roof, piping to water heater and cook line is installed. regulators are to be located at appliances per plans. 10 lb test ok.. | JON | JON | | HI | P | 5413806 |
AIRTECH MECHANICAL, INC. | HD | P | 02/03/2017 | 2 GREASE DUCT OK FOR WRAP - ABOVE CEILING SA/RA OK - STILL NEED DISH HOOD DUCT - RESTROOM EXHAUST DUCT - BY FINAL NEED THE FOLLOWING - TAB REPORT - VERIFY GREASE DUCT ACCESS DOOR AND WRAP NEED INSTALL MANUAL FOR WRAP AT NEXT INSPECTION - ROOF INSPECTION - FINAL TIE IN AT RETURN DUCT AT GRILLES NOTES: HOOD WALL OK | JERRYF | JERRYF | | HD | P | 5406693 |
PREMIER MECHANICAL | HI | P | 02/02/2017 | PIPING IN HOOD WALL OK ONLY - WILL NEED PRESSURE TEST AT FUTURE INSPECTION | JERRYF | JERRYF | | HI | P | 5405074 |
AIRTECH MECHANICAL, INC. | HD | P | 02/02/2017 | NOTES ADDED AT 10:37 - NEED SHEET ROCK REMOVED AT HOOD WALL TO VERIFY NON COMBUSTIBLE CONSTRUCTION - WHY WAS WALL SHEET ROCKED BEFORE WALL INSPECTION ???? | JERRYF | JERRYF | | HD | P | 5405052 |
CASCADE PLUMBING & HEATING | P= | C | 03/10/2017 | ok. corrections made. | JOHNS | JOHNS | | P= | C | 5438135 |
CASCADE PLUMBING & HEATING | P= | P | 03/09/2017 | need trap guards @ both bathroom floor drains, need flush handle @ mens bathroom on right side of toilet, need to caulk both hand wash @ kitchen sinks, need crates installed @ floor sinks, need 3" vent next to swamp cooler 3' above cooling unit. note: NEED TO VERIFY TEMPERING, NEED TO VERIFY BACKFLOW PREVENTER, NEED TO CHECK COMPLETED WATER HEATER, NEED TO CHECK FRONT DRINK AREA. | JOHNS | JOHNS | | P= | P | 5435911 |
CASCADE PLUMBING & HEATING | PTO | C | 02/13/2017 | ok. corrections made. | JOHNS | JOHNS | | PTO | C | 5413800 |
CASCADE PLUMBING & HEATING | PTO | P | 01/30/2017 | h2o needs support thru out | JOEL | JOEL | | PTO | P | 5401564 |
CASCADE PLUMBING & HEATING | PB | C | 01/17/2017 | ok. NOTE: per plan | JOHNS | JOHNS | | PB | C | 5389953 |