WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 09/27/2017 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 5638602 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 08/02/2017 | Building final OK pending mechanical final complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), THE COLORADO COLLEGE Mechanical Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 5583856 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | C | 08/02/2017 | | NICK | NICK | | BFR | C | 5583855 |
EL PASO ELECTRIC, LLC. | BSP | T | 06/27/2017 | PAID (REC#1435050) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised to indicate Mid Clamp grounding. | BERTHA | BERTHA | | BSP | T | 5548518 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BLA | C | 06/15/2017 | | NICK | NICK | | BLA | C | 5536322 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 05/31/2017 | Frame OK / Still need to inspect 1/S2 detail for PV panel attachment / Need electrical and mechanical complete | NICK | NICK | | BFR | P | 5521254 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFN | C | 03/27/2017 | ufer is in | NATHAN | NATHAN | | BFN | C | 5456217 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFT | C | 03/17/2017 | Pictures of Eufer rod on file | NICK | NICK | | BFT | C | 5443637 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFT | P | 03/16/2017 | Need to install Eufer rod, can upload image / All other aspects of footing OK / Open hole on file / #2400psf / No drain required per Soils report already uploaded onto approved plans / | NICK | NICK | | BFT | P | 5442770 |
EL PASO ELECTRIC, LLC. | E= | C | 07/21/2017 | | BRET | BRET | | E= | C | 5571715 |
EL PASO ELECTRIC, LLC. | EP | C | 07/17/2017 | 100 amp 4/w to new sub panel ok | CRAIG | CRAIG | | EP | C | 5566138 |
EL PASO ELECTRIC, LLC. | E= | R | 07/17/2017 | gfi all outlets in garage addition | CRAIG | CRAIG | | E= | R | 5566123 |
EL PASO ELECTRIC, LLC. | ER | P | 05/16/2017 | Walls and ceilings ok to cover---Need plastic bushing on PVC at panel---No PV yet--- | ROB | ROB | | ER | P | 5507574 |
THE COLORADO COLLEGE | H= | C | 09/27/2017 | previous inspection was put in under different code, closing out per notes of 09/01/2017 | MINDY | MINDY | | H= | C | 5638601 |
THE COLORADO COLLEGE | HSP | C | 09/01/2017 | TAB REPORT RECEIVED - ALL COMPLETE | JERRYF | JERRYF | | HSP | C | 5613563 |
THE COLORADO COLLEGE | H= | L | 08/30/2017 | NO TAB REPORT ATTACHED | JERRYF | JERRYF | | H= | L | 5674262 |
THE COLORADO COLLEGE | HSP | L | 08/30/2017 | NO TAB REPORT ATTACHED | JERRYF | JERRYF | | HSP | L | 5610935 |
THE COLORADO COLLEGE | H= | P | 08/30/2017 | REGULATOR LETTER RECEIVED - STILL NEED TAB REPORT | JERRYF | JERRYF | | H= | P | 5610934 |
THE COLORADO COLLEGE | H= | P | 08/24/2017 | NEED THE FOLLOWING TO COMPLETE FINAL - LETTER VERIFYING GAS REGULATOR AND FURNACE VALVE ARE OK TO OPERATE DUE TO OVERPRESSURE AT TIME OF GAS PRESSURE TEST INSPECTION BOTH REGULATOR AND FURNACE WERE SUBJECTED TO 10 POUNDS OF PRESSURE - TAB REPORT - ATTACH TEST AND BALANCE REPORT AND LETTER TO NEXT INSPECTION REQUEST - ALL OTHER CORRECTIONS HAVE BEEN MADE | JERRYF | JERRYF | | H= | P | 5605818 |
THE COLORADO COLLEGE | H= | P | 08/16/2017 | NEED THE FOLLOWING - TAB REPORT - FREEZE PROTECT VINYL TUBING ON CONDENSATE PUMP - LETTER VERIFYING GAS REG. HAS BEEN REPLACED DUE TO OVER PRESSURE AT GAS TEST | JERRYF | JERRYF | | H= | P | 5597712 |
THE COLORADO COLLEGE | HI | P | 07/28/2017 | NEED REGULATOR REPLACED AT FURNACE REGULATOR WAS NOT ISOLATED AT PRESSURE TEST - NEED ALL LABELS INSTALLED - REST OK - PIPING PER PLAN | JERRYF | JERRYF | | HI | P | 5674261 |
THE COLORADO COLLEGE | HD | P | 07/28/2017 | ALL ABOVE CEILING OK TO WRAP - BY FINAL NEED ACCESS TO ROOF TO VERIFY CLEARANCE FROM OSA OPENING TO FURNACE EXHAUST - FREEZE PROTECT ALL DRAINS IN ATTIC | JERRYF | JERRYF | | HD | P | 5579288 |
THE COLORADO COLLEGE | HI | P | 05/26/2017 | 10 LB TEST OK ON GAS LINE FROM EAVE TO F-1 ONLY. INSTALLED AS PER PRINT. NO REGULATOR OR CONNECTION TO FURNACE YET. | NANCY | NANCY | | HI | P | 5518028 |
THE COLORADO COLLEGE | HD | P | 05/26/2017 | SUPPLY DUCTS ALL OK, OK TO WRAP. FURNACE CONDENSATE DRAIN IN WALL OK. | NANCY | NANCY | | HD | P | 5518022 |
THE COLORADO COLLEGE | HC | C | 02/01/2017 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5674260 |
THE COLORADO COLLEGE | HI | C | 02/01/2017 | 10 LB TEST OK. | NANCY | NANCY | | HI | C | 5674259 |
THE COLORADO COLLEGE | HI | P | 01/31/2017 | LOW TEST. BY FINAL INSTALL ALL REGULATORS AND MEDIUM PRESSURE LABELS. | NANCY | NANCY | | HI | P | 5674258 |
CLEAR WATER SERVICES LLC | P= | C | 07/27/2017 | | TAYLOR | TAYLOR | | P= | C | 5577572 |
CLEAR WATER SERVICES LLC | PTO | C | 05/30/2017 | VTR, check H2O and drain tie in's by final. | TAYLOR | TAYLOR | | PTO | C | 5519540 |
CLEAR WATER SERVICES LLC | PB | C | 04/07/2017 | per plan. | TAYLOR | TAYLOR | | PB | C | 5467356 |