COLORADO COMMERCIAL CONTRACTING,INC | B= | C | 08/18/2017 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 5600893 |
COLORADO COMMERCIAL CONTRACTING,INC | B= | P | 08/11/2017 | . Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONINGF is not Completed yet (Contact: Janet at 322-2028), AMEN PLUMBING AND HEATING Mechanical Final Inspection is not Completed yet, AMEN PLUMBING AND HEATING Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5593525 |
COLORADO COMMERCIAL CONTRACTING,INC | B= | P | 08/10/2017 | post suite # (address) missing drain padding at both restrooms, complete MEP's and fire. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection Z= by ZONINGF is not Completed yet (Contact: Janet at 322-2028), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, AMEN PLUMBING AND HEATING Mechanical Final Inspection is not Completed yet, AMEN PLUMBING AND HEATING Plumbing Final Inspection is not Completed yet, DILLER ELECTRIC Electrical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5592232 |
COLORADO COMMERCIAL CONTRACTING,INC | BFR | P | 07/31/2017 | Pizza oven enclosure framing OK - no MEP roughs shown on drawings (see A-111 & A-401) / plans reviewed on-site | RICHB | RICHB | | BFR | P | 5580489 |
COLORADO COMMERCIAL CONTRACTING,INC | BFR | P | 05/23/2017 | Need to install bracing for all soffits at 48"oc per plans / All other framing OK / Need all MEP's complete / Reviewed accessible elements | NICK | NICK | | BFR | P | 5514735 |
DILLER ELECTRIC LLC | E= | C | 08/11/2017 | | TOMC | TOMC | | E= | C | 5593514 |
DILLER ELECTRIC LLC | ER | C | 08/09/2017 | GRID CEILING OK-----NOTE NEED DISCONNECT ON WATER RECERT PUMP LEAVE TILE OUT NEXT TO WATER HEATER------- | BRIAN | BRIAN | | ER | C | 5590755 |
DILLER ELECTRIC LLC | ER | P | 08/01/2017 | MILL WORK OK -----NOTE-- TESTED THE GFCI PROTECTION ON MILL WORK OUTLETS | BRIAN | BRIAN | | ER | P | 5582765 |
DILLER ELECTRIC LLC | ER | P | 06/22/2017 | HARD LIDS--OK | BRIAN | BRIAN | | ER | P | 5544462 |
DILLER ELECTRIC LLC | ER | P | 05/23/2017 | WALLS---OK | BRIAN | BRIAN | | ER | P | 5514539 |
AMEN PLUMBING- HEATING | H= | C | 08/14/2017 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 5594368 |
AMEN PLUMBING- HEATING | H= | P | 08/11/2017 | CO2 LETTER RECEIVED | JERRYF | JERRYF | | H= | P | 5592653 |
AMEN PLUMBING- HEATING | H= | P | 08/10/2017 | NEED LETTER FROM ARCHITECT SHOWING 300# CO2 TANK INSTALLED AND TAB REPORT - REST OK | JERRYF | JERRYF | | H= | P | 5591334 |
AMEN PLUMBING- HEATING | H= | P | 08/09/2017 | NEED PLAN REVISED AND APPROVED SHOWING 300# CO2 TANK INSIDE BUILDING WHEN PLAN CALLS FOR 20# TANK - NEED CLARIFICATION ON WHICH JURISDICTION INSPECTS TANK - TAB REPORT - REMOTE INDICATOR FOR SMOKE SHUTDOWN AND GAS SHUT OFF AT PIZZA OVEN -REST OK - INTERLOCKS VERIFIED AND IN OPERATION | JERRYF | JERRYF | | H= | P | 5590045 |
AMEN PLUMBING- HEATING | HD | P | 07/26/2017 | FACTORY GREASE DUCT AND SA / RA ABOVE HARD LID AREA OK ONLY | JERRYF | JERRYF | | HD | P | 5576174 |
AMEN PLUMBING- HEATING | HD | P | 05/23/2017 | Still need all mechanical inspections and scope of work corrected. THIS INSPECTION WAS TO CONFIRM THERE WILL BE NO MECHANICAL IN THE WALLS BEING COVERED UP BY DRYWALL. | MARKB | MARKB | | HD | P | 5514315 |
AMEN PLUMBING- HEATING | P= | C | 08/14/2017 | OK, corrections made | SHANEN | SHANEN | | P= | C | 5594328 |
AMEN PLUMBING- HEATING | P= | P | 08/09/2017 | Add 3 sinks to scope of work, need back-flow prevention at soda fountain, need water hammer arrestor at dishwasher, rest OK | SHANEN | SHANEN | | P= | P | 5590218 |
AMEN PLUMBING- HEATING | PTO | C | 05/23/2017 | Test OK, check water heater and recirc pump at final, AAV - floor sink, 4" VTR | SHANEN | SHANEN | | PTO | C | 5514030 |
AMEN PLUMBING- HEATING | PB | C | 05/01/2017 | per plan. | TAYLOR | TAYLOR | | PB | C | 5492486 |