HAMMERS CONSTRUCTION, INC | B= | C | 08/15/2018 | External agencies are complete/ finalized | GITA | GITA | | B= | C | 5934736 |
HAMMERS CONSTRUCTION, INC | B= | P | 07/13/2018 | Temp CO: Extension ( Expires: 8/12/2018 12:00:00 AM) | GITA | GITA | | B= | P | 5901515 |
HAMMERS CONSTRUCTION, INC | B= | P | 07/13/2018 | Temp CO: Extension ( Expires: 8/12/2018 12:00:00 AM) | GITA | GITA | | B= | P | 5901514 |
HAMMERS CONSTRUCTION, INC | B= | P | 06/13/2018 | Temp CO: Extension ( Expires: 7/13/2018 12:00:00 AM) | GITA | GITA | | B= | P | 5872699 |
HAMMERS CONSTRUCTION, INC | B= | P | 05/16/2018 | Temp CO: Extension ( Expires: 6/15/2018 12:00:00 AM) | GITA | GITA | | B= | P | 5846106 |
HAMMERS CONSTRUCTION, INC | B= | P | 04/19/2018 | Temp CO: finals are done or partial. ( Expires: 5/19/2018 12:00:00 AM) | GITA | GITA | | B= | P | 5820983 |
HAMMERS CONSTRUCTION, INC | B= | P | 04/17/2018 | Third party observations on file / complete pending other Finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet, JLC ELECTRIC LLC Electrical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 5818518 |
HAMMERS CONSTRUCTION, INC | BSP | P | 04/17/2018 | Third party observations received | RICHB | RICHB | | BSP | P | 5818517 |
HAMMERS CONSTRUCTION, INC | B= | P | 04/13/2018 | Need copies of third party inspections - everything else OK pending other Finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), GOLD RUSH PLUMBING Plumbing Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet, JLC ELECTRIC LLC Electrical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 5816287 |
HAMMERS CONSTRUCTION, INC | BSP | P | 04/09/2018 | Above grid construction OK pending Electrical | RICHB | RICHB | | BSP | P | 5811796 |
HAMMERS CONSTRUCTION, INC | BFR | C | 04/09/2018 | Framing adjacent to coolers OK | RICHB | RICHB | | BFR | C | 5811792 |
HAMMERS CONSTRUCTION, INC | BFR | P | 02/09/2018 | Interior wall, hard lid & soffit framing in most areas OK pending other Roughs - still need to inspect framing at freezer & walk-in areas where walls are adjacent to cooler panels (Grids 2 & B.8 and also 1.3 & B.3) / discussed accessible elements and backing / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5762290 |
HAMMERS CONSTRUCTION, INC | BIN | P | 01/24/2018 | Thermal in wall cavities OK (R-36 in double-framed areas, R-19 everywhere else) / plans reviewed onsite | RICHB | RICHB | | BIN | P | 5746390 |
HAMMERS CONSTRUCTION, INC | BFR | P | 01/24/2018 | Framing for pony wall at SW corner OK | RICHB | RICHB | | BFR | P | 5746386 |
HVAC SOLUTIONS, INC. | BSP | T | 01/23/2018 | PAID (REC#1491234): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: mep 2 | DALEH | DALEH | | BSP | T | 5745647 |
JLC ELECTRIC LLC | BSP | P | 01/23/2018 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Revise panel schedule | SHELBY | SHELBY | | BSP | P | 5745619 |
GOLD RUSH PLUMBING | BSP | P | 01/23/2018 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice | TCRIPPEN | TCRIPPEN | | BSP | P | 5745544 |
HAMMERS CONSTRUCTION, INC | BFR | P | 01/04/2018 | Need third party observations for structural steel framing / need to complete BFT & BFN / need to complete other Roughs / walked with GC and framer (RMIC) - exterior framing OK except soffits and pony wall at SW corner / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5728904 |
HAMMERS CONSTRUCTION, INC | BFN | P | 01/04/2018 | OK TO USE THIRD PARTY | RICHB | RICHB | | BFN | P | 5728900 |
HAMMERS CONSTRUCTION, INC | BFT | P | 01/04/2018 | OK TO USE THIRD PARTY | RICHB | RICHB | | BFT | P | 5728890 |
HAMMERS CONSTRUCTION, INC | BSP | T | 11/27/2017 | PAID (REC#1468893): ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY Revise power plan | SHELBY | SHELBY | | BSP | T | 5695196 |
HAMMERS CONSTRUCTION, INC | BSP | P | 11/27/2017 | PLAN SPLICE: (No Fee) by: DANM for Construction: Remove and replace equipment on floor plan | DANM | DANM | | BSP | P | 5695123 |
GOLD RUSH PLUMBING | BSP | P | 11/27/2017 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice 11-27-17 | TCRIPPEN | TCRIPPEN | | BSP | P | 5694995 |
HAMMERS CONSTRUCTION, INC | BSP | P | 10/16/2017 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised sheet notes | JUSTINC | JUSTINC | | BSP | P | 5656963 |
HAMMERS CONSTRUCTION, INC | BSP | T | 10/16/2017 | PAID (REC#1468895): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Minor revisions | MICHAELA | MICHAELA | | BSP | T | 5656921 |
B & T ELECTRIC, INC. | BSP | P | 10/16/2017 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Multiple lighting and power revision. Updated panel schedules. | BERTHA | BERTHA | | BSP | P | 5656690 |
JLC ELECTRIC LLC | E= | C | 04/18/2018 | rtu 1 --175 --- rtu 2 -- 175 OK | CRAIGS | CRAIGS | | E= | C | 5820568 |
JLC ELECTRIC LLC | E= | P | 04/10/2018 | store area ---- kitchen --- coolers OK | CRAIGS | CRAIGS | | E= | P | 5812739 |
JLC ELECTRIC LLC | ER | C | 04/10/2018 | above ceilings OK | CRAIGS | CRAIGS | | ER | C | 5812726 |
JLC ELECTRIC LLC | ES | C | 04/04/2018 | Commercial Service: 1200 amp 4/w OK to set ct's , wire and energize the service | CRAIGS | CRAIGS | | ES | C | 5807910 |
JLC ELECTRIC LLC | EUG | P | 03/06/2018 | Site lighting on North, West, & South side. ----------- Also sign on SW corner --------- Notes: East side not ready | JOSEPH | JOSEPH | | EUG | P | 5780707 |
JLC ELECTRIC LLC | ER | P | 02/21/2018 | store canopy and front soffit OK---- trencher broke so no trench inspection today | CRAIGS | CRAIGS | | ER | P | 5770101 |
JLC ELECTRIC LLC | ER | P | 02/09/2018 | interior walls and hard ceiling OK | CRAIGS | CRAIGS | | ER | P | 5761767 |
JLC ELECTRIC LLC | ER | P | 01/23/2018 | Rough in ok for exterior walls only / | ROB | ROB | | ER | P | 5745171 |
JLC ELECTRIC LLC | ESL | P | 11/30/2017 | Entire store area slab complete / | ROB | ROB | | ESL | P | 5698666 |
HVAC SOLUTIONS, INC. | H= | C | 05/16/2018 | TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | C | 5846205 |
HVAC SOLUTIONS, INC. | H= | P | 04/16/2018 | FINAL PENDING - Glue condensate traps or RTU'S and provide a Test And Balance Report. | MARKB | MARKB | | H= | P | 5818186 |
HUSSMANN CORPORATION | H= | C | 04/12/2018 | NO REFRIGERATION ALARMS REQUIRED FOR CODE PER REFRIGERATION CALC'S PROVIDED ON PLAN SPLICE. | MARKB | MARKB | | H= | C | 5815159 |
HUSSMANN CORPORATION | HRP | C | 04/12/2018 | INSULATION, CONDENSATE LINES AND ROOF EQUIPMENT COMPLETE. | MARKB | MARKB | | HRP | C | 5815152 |
HVAC SOLUTIONS, INC. | H= | P | 04/03/2018 | INSPECTION OF ABOVE CEILING ONLY TODAY. ABOVE CEILING OK. STILL NEED ROOF, CONTROLS, CO2 ALARMS ETC. | NANCY | NANCY | | H= | P | 5806520 |
HUSSMANN CORPORATION | HRP | P | 03/28/2018 | 325 PSI PRESSURE TEST FOR ALL REFRIGERATION PIPING OK. Met with Hussmann installers on site to discuss install and talked about calling future inspections before piping is concealed. Will need a plan splice - contractor is working off a more current plan than the approved set and new splice will need to address changes in piping location. Plans show refrigeration alarms for each walk in on electrical pages. If alarms are not planned to go in, a plan splice will be needed removing alarms, refrigeration calc's for each walk in will be required showing alarms are not required per code. | MARKB | MARKB | | HRP | P | 5801645 |
HUSSMANN CORPORATION | HRP | R | 03/22/2018 | REFRIGERATION PIPING HAS BEEN CONCEALED UNDERGROUND AND IN WALLS WITHOUT PROPER INSPECTIONS. THERE WERE 2 PRESSURE GAUGES BUT PIPING DOES NOT MATCH PLANS. WILL NEED REFRIGERATION CONTRACTOR TO MEET INSPECTOR ON SITE TO EXPLAIN WHAT WAS UNDER TEST AND A REFRIGERATION PLAN SPLICE MAY BE REQUIRED. SENIOR MECHANICAL INSPECTOR IS WAITING FOR A CALL BACK FROM LICENSEE FOR HUSSMANN. SENIOR MECHANICAL INSPECTOR MADE A COURTESY CALL TO CHRIS ALLEN WITH HAMMERS CONSTRUCTION. | MARKB | MARKB | | HRP | R | 5796874 |
HVAC SOLUTIONS, INC. | HD | P | 02/20/2018 | REMOVE GAS PIPING FROM PERMIT SCOPE - NO GAS SERVICE IN BUILDING ABOVE CEILING DUCT - SUPPLY MAINS FOR RTU-1 OK TO WRAP - STILL NEED ALL FLEX AND DIFFUSERS. NO ROOF INSPECTION | MARKB | MARKB | | HD | P | 5769642 |
HVAC SOLUTIONS, INC. | HD | P | 02/15/2018 | ABOVE CEILING (GRID/HARD LIDS) DUCT FOR RTU-2 & EF-1 - SUPPLY/RETURN MAINS AND OUTRUNS INSTALLED PER PLAN OK TO WRAP. EF-2 - CONTINUE AT OWN RISK: WILL NEED A PLAN SPLICE FOR DUCT THAT DOES NOT MATCH GAUGE OR TYPE PER NOTE M9. NOTE ADDED 2/20/18: SPLICE ON FILE ADDRESSING EF-2 | MARKB | MARKB | | HD | P | 5767163 |
GOLD RUSH PLUMBING | P= | C | 04/13/2018 | | JOHNS | JOHNS | | P= | C | 5817128 |
GOLD RUSH PLUMBING | PTO | C | 02/09/2018 | corrections made. note: BY FINAL NEED ISO VALVE SERVING BATHS TO BE ACCESSIBLE | JOHNS | JOHNS | | PTO | C | 5761945 |
GOLD RUSH PLUMBING | PTO | P | 02/08/2018 | lost test @ west side dwv, low water test (x2), s-trap @ east side hand sink, isoloate pex from rough edges, strap pex (attic / walls), strap base of all vents, still need roof hydrant installed, need iso valves @ wall hydrant (x2), verify hwr @ next inspection, rest ok per plan. note: vtr (4), check all mech room fixtures / tie ins @ final, all lavs will require hammer aerestors by final (elec sensor lav faucets), all asse 1022 bfp will require drain lines ran to approved location by final, verify all tempering valves @ final | JOHNS | JOHNS | | PTO | P | 5760699 |
GOLD RUSH PLUMBING | PRD | C | 01/12/2018 | ok for test and design per plan | JOHNS | JOHNS | | PRD | C | 5736900 |
GOLD RUSH PLUMBING | PB | C | 11/15/2017 | Complete ok for G.W. and S.S., water stubbed into water entry and pex looped underground, test and design per plan. | JOHNS | JOHNS | | PB | C | 5685873 |