GERALD H PHIPPS INC | B= | C | 06/15/2018 | Room 1207 (including steel below) OK | RICHB | RICHB | | B= | C | 5876576 |
GERALD H PHIPPS INC | B= | P | 01/08/2018 | Room 1207 not complete - will need to reinspect once work is complete (including structural reinforcement below) / all other areas complete pending other Finals / plans reviewed onsite -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 5731828 |
GERALD H PHIPPS INC | BFR | P | 11/08/2017 | Corrections in 1207A complete / fire barrier continuity OK at Amico box (in Rm 1205) / wall framing OK pending other roughs including damper OK from Mechanical / reviewed proposed horizontal assembly per previous notes - Contractor to use AER-09038 - framing & sheetock verified / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5680458 |
GERALD H PHIPPS INC | BFR | P | 11/06/2017 | Need framing repair & door frame in 207A / need to address Amico zone control box in fire barrier / discussed fire barrier continuity at wall jog / need listing for rated assembly at soffit (Detail B6/A-590) / walls OK pending above items and other roughs / plans reviewed onsite / training with Justin | RICHB | RICHB | | BFR | P | 5678221 |
GERALD H PHIPPS INC | BSP | P | 11/06/2017 | Training with Rich on reading plans and commercial framing | JUSTINL | JUSTINL | | BSP | P | 5678215 |
GERALD H PHIPPS INC | BSP | P | 10/20/2017 | Partial framing for rated soffit at ductwork - OK to begin shaft liner for horizontal assembly / plans reviewed onsite | RICHB | RICHB | | BSP | P | 5662776 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 06/14/2018 | | GARYL | GARYL | | E= | C | 5875303 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 12/20/2017 | FIRE ALARM INSPECTION: signed red card | CRAIGS | CRAIGS | | E= | C | 5718430 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 12/20/2017 | FIRE ALARM INSPECTION: signed red card | CRAIGS | CRAIGS | | ER | C | 5718429 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 12/20/2017 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 5718428 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 12/20/2017 | everything except 2nd CT equipment ---- need paper work showing max over current protection for the chiller equipment and that these are ordered as a package and the ul listing is covering all the components | CRAIGS | CRAIGS | | E= | P | 5718417 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/05/2017 | FIRE ALARM INSPECTION: cat scan room 1 , hall way and bathroom --OK | CRAIGS | CRAIGS | | ER | P | 5702429 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/05/2017 | cat scan room 1 , hall and bathroom above ceiling OK | CRAIGS | CRAIGS | | ER | P | 5702424 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 11/06/2017 | FIRE ALARM INSPECTION: wall stubs OK | CRAIGS | CRAIGS | | ER | P | 5677110 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 11/06/2017 | walls OK | CRAIGS | CRAIGS | | ER | P | 5677101 |
MECHONE, INC. | H= | C | 06/15/2018 | TAB REPORT AND ENGINEER LETTER RECEIVED | JERRYF | JERRYF | | H= | C | 5875413 |
MECHONE, INC. | H= | P | 05/23/2018 | PARTIAL PENDING TAB REPORT - ALL RETAINAGE / ACCESS DOORS AND GRID LABELS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5853575 |
MECHONE, INC. | HD | P | 05/10/2018 | ABOVE CEILING SA DUCT OK - DAMPER RETAINAGE AND BREAK AWAY OK | JERRYF | JERRYF | | HD | P | 5841423 |
MECHONE, INC. | HD | P | 05/02/2018 | FIRE DAMPER FRAMING OK PER PLAN DELTA NUMBER PR002 | JERRYF | JERRYF | | HD | P | 5833791 |
MECHONE, INC. | HD | L | 04/26/2018 | WRONG PERMIT CALLED FOR INSPECTION | JERRYF | JERRYF | | HD | L | 5827931 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 12/20/2017 | ALL OK ALL FINAL CONNECTIONS ARE COMPLETE | JERRYF | JERRYF | | H= | C | 5718421 |
MECHONE, INC. | H= | P | 12/06/2017 | PARTIAL PENDING THE FOLLOWING - TAB REPORT AND STAMPED APPROVED ENGINEER LETTER SHOWING F/SD DAMPER SUPPORT AT SOFFIT - REST OK - ALL SA / RA GRILLES ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5705234 |
MECHONE, INC. | HD | P | 11/14/2017 | LOW / MEDIUM PRESSURE RUN OUTS AND MAINS OK TO WRAP - 50 X 20 AND 60 X 20 DAMPER GAP OK - AT FUTURE INSPECTION VERIFY PROPER SUPPORT PER ENGINEER LETTER AT 2 DAMPERS PER PREVIOUS NOTES | JERRYF | JERRYF | | HD | P | 5684347 |
OLSON PLUMBING & HEATING COMPANY | HD | C | 11/13/2017 | PRESSURE TEST AND PIPING OK TO 4 VAV BOXES - OTHER 2 BOXES ARE ELECTRIC - OK TO INSULATE | JERRYF | JERRYF | | HD | C | 5682809 |
MECHONE, INC. | HD | P | 11/07/2017 | 26 X 16 DAMPER OK THE 60 X 20 AND THE 50 X 20 DAMPERS ARE FRAMED TO TIGHT, NEED INSTRUCTIONS FOR EXPANSION ROOM. OTHER THREE DAMPERS NEED ENGINEER LETTER CONFIRMING THAT THE DAMPER WILL MEET THE INTENT FROM THE DAMPER MANUFACTURER FOR BREAK AWAY SUPPORT AND STRUCTURE SUPPORT | JON | JON | | HD | P | 5678985 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 12/11/2017 | | JOHNS | JOHNS | | P= | C | 5708608 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 11/29/2017 | ok for test and design per plan. note: vtr (existing) | JOHNS | JOHNS | | PTO | C | 5697551 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 11/06/2017 | ok for in wall DWV ONLY, test and design per plan **STILL NEED CEILING AND UNDER BELLY**
ok for in wall / ceiling water ONLY up to iso's in adjacent hall way, hammer aerestor above ceiling @ water closet, test and design per plan **STILL NEED HALLWAY TIE INS
**PLANS MARKED @ GC OFFICE PER ANDREWS REQUEST** | JOHNS | JOHNS | | PTO | P | 5677556 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | XES | P | 04/04/2018 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Move location of C/T equipment room | SHELBY | SHELBY | | XES | P | 5807430 |
OLSON PLUMBING & HEATING COMPANY | XMS | P | 04/04/2018 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Mechanical: mechanical splice 4-4-18 | TCRIPPEN | TCRIPPEN | | XMS | P | 5807381 |
GERALD H PHIPPS INC | XBS | T | 04/04/2018 | PAID (REC#1491699) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised floor plan | SHELLEY | SHELLEY | | XBS | T | 5807319 |