TANDEM ENTERPRISES INC | B= | C | 03/30/2018 | open hole on file 2000# | BOBF | BOBF | | B= | C | 5803246 |
TANDEM ENTERPRISES INC | B= | P | 03/27/2018 | letter for observation of pool installation and anchor bolt installation on file / still need open hole and observation letter for footing and pads -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911). | BOBF | BOBF | | B= | P | 5800189 |
TANDEM ENTERPRISES INC | BFR | P | 01/26/2018 | reviewed accessible elements including door hardware / pending other required inspections wall and ceiling framing for mech room okay / need all eng letters for required foundation inspections | BOBF | BOBF | | BFR | P | 5749208 |
TANDEM ENTERPRISES INC | BSP | T | 12/22/2017 | PAID (REC#1475271) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: Splice to add mua and exhaust fan | DALEH | DALEH | | BSP | T | 5721019 |
PROWEST ELECTRIC, INC. | BSP | P | 12/21/2017 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Add panel pool 2 on pool structure | SHELBY | SHELBY | | BSP | P | 5719793 |
TANDEM ENTERPRISES INC | BSP | T | 12/21/2017 | PAID (REC#1475271) PLAN SPLICE FEE: $50 by: DANM for Construction: Add Makeup Air Unit and increase egress width with double entry door | DANM | DANM | | BSP | T | 5719608 |
PROWEST ELECTRIC, INC. | EP | C | 03/23/2018 | 200 amp 4/w to sub ok 100 amp 4/w to sub ok | CRAIG | CRAIG | | EP | C | 5797622 |
PROWEST ELECTRIC, INC. | E= | C | 03/23/2018 | | CRAIG | CRAIG | | E= | C | 5797621 |
PROWEST ELECTRIC, INC. | E= | R | 03/21/2018 | gfci wet niche lighting fixtures,gfci pool cover motor, verify ef-1 breaker 40 amp name plate 6.5 amps ?, working space at panel, verify egress lighting at east door. bond all sections of metal building to electrical system | BRET | BRET | | E= | R | 5795418 |
PROWEST ELECTRIC, INC. | EUG | P | 02/20/2018 | encapsulation of both wet niche lights ok | CRAIG | CRAIG | | EUG | P | 5768917 |
PROWEST ELECTRIC, INC. | EUG | P | 02/16/2018 | bonding around pool ok ------------ wet niche lights not ready | CRAIG | CRAIG | | EUG | P | 5767793 |
PROWEST ELECTRIC, INC. | EUG | P | 02/15/2018 | bonding of pool electric cover rail only | CRAIG | CRAIG | | EUG | P | 5766698 |
PROWEST ELECTRIC, INC. | EUG | P | 01/23/2018 | 2 - 1/2 inch PVC for new 200 amp panel -------- 1 - 1/2 PVC for AH. --------- Gave consultation and went over bonding / grounding / gfci protection / required inspections / corrosive environments / deck boxes / lighting / disconnecting means | JOSEPH | JOSEPH | | EUG | P | 5745066 |
PROWEST ELECTRIC, INC. | EUG | P | 11/30/2017 | conduit for lights and receptacles from pool panel location, address deck boxes with contractor | BRET | BRET | | EUG | P | 5699071 |
PROWEST ELECTRIC, INC. | ESL | P | 11/15/2017 | 9 area' s around pool including wet - niche lights --------- equipotential bonding | CRAIG | CRAIG | | ESL | P | 5686479 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 03/26/2018 | MECHANICAL FINAL OK. CORRECTIONS MADE, SEE IMAGES. | NANCY | NANCY | | H= | C | 5798857 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 03/23/2018 | NEED 1 INCH CLEARANCE FROM B-VENT TO COMBUSTIBLES AT CEILING. SUPPORT VENT AT BOILER. OK TO TAKE PICTURES OF CORRECTIONS AND ATTACH TO INSPECTION REQUEST. | NANCY | NANCY | | H= | P | 5797596 |
FRONT RANGE AQUATECH | H= | C | 03/16/2018 | POOL HEATER FINAL OK. | NANCY | NANCY | | H= | C | 5791097 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 03/16/2018 | PROPERLY VENT POOL HEATER WITH A MINIMUM OF 8 INCH ROUND B-VENT PER MANUFACTURERS INSTRUCTIONS, SEE PAGE 20. PROPERLY SEAL AND SUPPORT VENT PER INSTRUCTIONS. INSTALL 8 INCH DUCT FROM 6 INCHES ABOVE FINISHED FLOOR TO EXHAUST FAN INLET PER PLAN. UV PROTECT FLEX DUCT CONNECTOR ON MAKE-UP AIR UNIT. SEAL DUCTS AT OUTSIDE WALL OF POOL BUILDING. | NANCY | NANCY | | H= | P | 5791095 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 03/16/2018 | ENGINEER LETTER REGARDING LOCATION OF EXHAUST MAKE-UP AIR INTAKE AND COMBUSTION AIR LOCATION RECEIVED AND SCANNED, SEE IMAGES. | NANCY | NANCY | | H= | P | 5790764 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 03/16/2018 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. | NANCY | NANCY | | H= | P | 5790762 |
FRONT RANGE PLUMBING CO., INC. | H= | C | 03/01/2018 | CONTRACTOR INSTALLING POOL HEATER MUST ATTACH TO PERMIT AND CALL FOR INSPECTION WHEN READY. GAS FINAL OK. | NANCY | NANCY | | H= | C | 5777857 |
FRONT RANGE PLUMBING CO., INC. | HC | C | 01/19/2018 | 600,000 BTU'S ADDED TO EXISTING 2 LB METER. | NANCY | NANCY | | HC | C | 5742670 |
FRONT RANGE PLUMBING CO., INC. | HO | C | 01/19/2018 | NEED MECHANICAL CONTRACTOR ATTACHED TO PERMIT. CONTRACTOR INSTALLING POOL BOILER EQUIPMENT MUST ATTACH TO PERMIT OR ADD IT TO THEIR SCOPE OF WORK. 10 LB TEST OK ON THE UNDERGROUND GAS LINE TO MAKE-UP AIR UNIT. INSTALLED AS PER PRINT. STILL NEED TO SEE REGULATORS AND CONNECTIONS TO ALL EQUIPMENT. | NANCY | NANCY | | HO | C | 5742665 |
FRONT RANGE PLUMBING CO., INC. | P= | C | 03/01/2018 | | SHANEN | SHANEN | | P= | C | 5777208 |
FRONT RANGE PLUMBING CO., INC. | PTO | P | 01/30/2018 | DWV in wall test OK | SHANEN | SHANEN | | PTO | P | 5751260 |
FRONT RANGE PLUMBING CO., INC. | PB | P | 01/16/2018 | Corrections made, reopened for vent inspections. | SHANEN | SHANEN | | PB | P | 5738319 |
FRONT RANGE PLUMBING CO., INC. | PB | P | 01/10/2018 | low test @ water, floor sink and mop sink not sized per plan, re inspect all. note: 1" water under footer **use spliced plans dated 12/22/17** | JOHNS | JOHNS | | PB | P | 5734903 |
FRONT RANGE PLUMBING CO., INC. | XMS | P | 02/05/2018 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised combustion air louver sizes | JUSTINC | JUSTINC | | XMS | P | 5757247 |