INDEPENDENT CONSTRUCTION & REMODEL, INC. | B= | C | 06/19/2018 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 5879102 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | B= | P | 06/19/2018 | final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), CORNERSTONE PLUMBING INC Plumbing Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5878505 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | B= | P | 06/12/2018 | need to install restroom signs / need minimum 1 1/2" finger clearance at both accessible toilet rear grab bars / missing vertical grab bars at both transfer showers / valves at women's transfer shower are not between 38" and 48" above the floor -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CORNERSTONE PLUMBING INC Plumbing Final Inspection is not Completed yet, EAGLE HEATING & AIR COND. INC. Mechanical Final Inspection is not Completed yet, O.M.A.G.M., INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5872408 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | B= | R | 06/08/2018 | inspection not done as not ready for final inspection / did courtesy walk for accessible items in bathrooms and discussed accessible elements / transfer showers are currently wider than 36" and vanities are higher than 34" to the rim of the sinks / still need to check all other accessible elements of whole suite. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CORNERSTONE PLUMBING INC Plumbing Final Inspection is not Completed yet, EAGLE HEATING & AIR COND. INC. Mechanical Final Inspection is not Completed yet, J2D ELECTRIC, INC. Electrical Final Inspection is not Completed yet, O.M.A.G.M., INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | R | 5869453 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | BFR | P | 06/08/2018 | platform framing OK / this completes the frame inspection pending other roughs | DANE | DANE | | BFR | P | 5869447 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | BFR | P | 05/03/2018 | interior light gauge wall framing OK pending other roughs / still need to install and inspect platform / discussed panic hardware at rear exit per plans / discussed accessible elements including valve placement at transfer showers as currently the mens shower valve in wrong wall for the clear floor space | DANE | DANE | | BFR | P | 5835614 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | BSP | P | 04/17/2018 | plan shows north and south demising walls as an existing U419 / no inspection for rated demising walls has been done / building is a non-separated use building / the existing demising walls have been overlayed with QuietRock brand drywall and penetrations have been sealed with acoustical sealant neither of which are allowed on what has been called an existing U419 rated assembly on the plans / need to splice into plans a revised wall plan for the demising walls / need to attach an electrical permit / 3 5/8 stud wall built over existing walls are built per plan | DANE | DANE | | BSP | P | 5819174 |
J2D ELECTRIC, INC. | E= | C | 06/11/2018 | | BRET | BRET | | E= | C | 5870188 |
J2D ELECTRIC, INC. | E= | P | 06/08/2018 | no power to stag receptacle, bath exhaust fan not working no breaker labeled for it should be a 15 amp breaker, attach to sign permit | BRET | BRET | | E= | P | 5869068 |
J2D ELECTRIC, INC. | ER | C | 06/01/2018 | all suspended ceilings ok | BRET | BRET | | ER | C | 5861861 |
SAWYER ELECTRIC, INC | E= | C | 04/30/2018 | relocate panels only branch circuits by j2d | BRET | BRET | | E= | C | 5831662 |
SAWYER ELECTRIC, INC | ES | C | 04/30/2018 | Commercial Service: 200 amp meter set for unit 120. | BRET | BRET | | ES | C | 5831661 |
J2D ELECTRIC, INC. | ER | P | 04/30/2018 | front half walls back area( training area) not ready | BRET | BRET | | ER | P | 5831656 |
EAGLE HEATING AND AIR CONDITIONING, INC. | H= | C | 06/18/2018 | TEST BALANCE REPORT ATTACHED, SEE IMAGES | BENH | BENH | | H= | C | 5876821 |
O.M.A.G.M., INC. | H= | C | 06/13/2018 | GAS FINAL OK PER MECHANICAL | BENH | BENH | | H= | C | 5873910 |
EAGLE HEATING AND AIR CONDITIONING, INC. | H= | P | 06/12/2018 | NEED TO SUPPORT DRYER VENT EVERY 4 FT, OK TO ATTACH PICTURE OF CORRECTIONS MADE TO IMAGES , REST OK PENDING TAB REPORT | BENH | BENH | | H= | P | 5872489 |
EAGLE HEATING AND AIR CONDITIONING, INC. | H= | P | 06/08/2018 | NOTES AND STATUS CHANGED 6/12/18: Dryer duct still lacks support in ceiling, Can not locate Remote Smoke Indicator, Still need to verify vent connection to water heater in room 103 (could not enter because of wet floor) and provide Test And Balance Report. | MARKB | MARKB | | H= | P | 5869627 |
EAGLE HEATING AND AIR CONDITIONING, INC. | HD | P | 06/01/2018 | Added to notes 6/3/18 (LM) dyer vent was covered up by sheet rock before it was inspected / support dryer vent every 4ft .11" X 11" DUCT DROP WAS INSTALLED FOR EF-1 PLAN CALLS FOR 14" ROUND INSTALL PER PLAN OR HAVE PLANS REVISED AND APPROVED . ((STILL NEED ROOF INSPECTION. )) DUCT DETECTOR INSTALLED FOR RTU-1 .SUPPLY AND RETURN DUCT ROUGH AND SUPPLY / RETURN / EXHAUST GRD FINAL CONNECTIONS ABOVE DROP CEILING IN ROOMS 104 , 105, 106 OK / UTILITY ROOM # 103 NOT READY . EXPOSED DUCT AND TRIM IN ROOMS 101,102 OK . BY FINAL WILL NEED REMOTE SMOKE INDICATOR INSTALLED / TEST AND BALANCE REPORT . | LIDO | LIDO | | HD | P | 5862728 |
O.M.A.G.M., INC. | HC | C | 04/30/2018 | OK TO SET METER. | NANCY | NANCY | | HC | C | 5831633 |
O.M.A.G.M., INC. | HI | C | 04/30/2018 | 10 LB TEST OK. INSTALLED AS PER PRINT. FOR FINAL NEED TO SEE CONNECTIONS TO WATER HEATER AND DRYER. | NANCY | NANCY | | HI | C | 5831632 |
EAGLE HEATING AND AIR CONDITIONING, INC. | HD | P | 04/26/2018 | NEED GAS CONTRACTOR ATTACHED TO PERMIT TRUNK LINES AND LATERALS OK, OK TO INSULATE, NO ROOF, FLEX OR DIFFUSERS AT THIS TIME | BENH | BENH | | HD | P | 5828590 |
CORNERSTONE PLUMBING INC | P= | C | 06/19/2018 | Corrections made. | DANR | DANR | | P= | C | 5879056 |
CORNERSTONE PLUMBING INC | P= | P | 06/12/2018 | Both transfer showers over 36" wide (woman's 36-1/2" - mens 37"), both transfer showers missing vertical (ANSI 608.3.1.2), woman's hand held diverter valve over 48" above floor ( at 48-3/8"), men's accessible toilet lacking side clearance (at 18-3/8"), rest ok. | DANR | DANR | | P= | P | 5871902 |
CORNERSTONE PLUMBING INC | P= | P | 06/05/2018 | Not ready need partitions installed - shower seats / bars installed, re-inspect all. | DANR | DANR | | P= | P | 5864564 |
CORNERSTONE PLUMBING INC | PTO | C | 05/08/2018 | Corrections made. Note: shower floor not poured in at time of inspection shower controls need to comply with ANSI A117.1-2003 - 608.5.1, shower compartment 608.2.1. | DANR | DANR | | PTO | C | 5838571 |
CORNERSTONE PLUMBING INC | PTO | P | 05/02/2018 | Need to install and inspect shower valves, need vent roof penetration, rest OK | SHANEN | SHANEN | | PTO | P | 5833669 |
CORNERSTONE PLUMBING INC | PTO | P | 05/01/2018 | Low test on water, DWV test OK | SHANEN | SHANEN | | PTO | P | 5832475 |
CORNERSTONE PLUMBING INC | PB | C | 04/02/2018 | Corrections made, DWV test OK | SHANEN | SHANEN | | PB | C | 5805235 |
CORNERSTONE PLUMBING INC | PB | R | 03/29/2018 | Size and install underground DWV per plan | SHANEN | SHANEN | | PB | R | 5802613 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | XBS | T | 04/27/2018 | PAID (REC#1496631) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: bike platforms | SHELLEY | SHELLEY | | XBS | T | 5829262 |
SAWYER ELECTRIC, INC | XES | P | 04/27/2018 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised 400A Panel La to two section 225A Panel LA. | BERTHA | BERTHA | | XES | P | 5829246 |
INDEPENDENT CONSTRUCTION & REMODEL, INC. | XBS | T | 04/18/2018 | PAID (REC#1494468) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised plan to remove rated demising walls. | SHELLEY | SHELLEY | | XBS | T | 5819808 |