CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | C | 07/18/2018 | | BERTW | BERTW | | B= | C | 5906752 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | P | 07/11/2018 | Temp CO: reup ( Expires: 8/10/2018 12:00:00 AM) | JANE | JANE | | B= | P | 5898972 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | P | 07/11/2018 | Temp CO: reup ( Expires: 8/10/2018 12:00:00 AM) | JANE | JANE | | B= | P | 5898971 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | P | 06/15/2018 | Temp CO: all partial ( Expires: 7/15/2018 12:00:00 AM) | JANE | JANE | | B= | P | 5876660 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | P | 06/15/2018 | need to complete core shell permit / all other items corrected -- Schedule a new Building Final when above items are complete. | DANE | DANE | | B= | P | 5876550 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | B= | P | 06/05/2018 | Core and shell needs to be completed, need to complete plumb, elec, mech and fire finals / need addressing on exterior -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection Z= by TOWNOFMON is not Completed yet (Contact: Tom Martinez at 884-8036), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ANYTHING HVAC, LLC. Mechanical Final Inspection is not Completed yet, CENTRAL PLUMBING INC Plumbing Final Inspection is not Completed yet, COOLING CUBED, LLC. Mechanical Final Inspection is not Completed yet, HERRON ELECTRIC Electrical Final Inspection is not Completed yet, R & R DITCHING, INC Mechanical Final Inspection is not Completed yet, ROGERS PLUMBING, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5864728 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | BSP | P | 05/17/2018 | pending all other required inspections, above ceiling components okay | BOBF | BOBF | | BSP | P | 5848034 |
CHRISTOFFERSON COMMERCIAL BUILDERS, INC. | BFR | P | 04/30/2018 | Reviewed Accessible Elements / pending all other required inspections, framing for soffits and pony walls okay | BOBF | BOBF | | BFR | P | 5831053 |
HERRON ELECTRIC COMPANY | E= | C | 06/05/2018 | rtu' s 1, 2 ok freezer / cooler / lobby ice / driver ice ok | CRAIG | CRAIG | | E= | C | 5864986 |
HERRON ELECTRIC COMPANY | EP | P | 05/22/2018 | 2 - 200 amp 4/w to panels A, B ok 100 amp 4/w to panel KA ok | CRAIG | CRAIG | | EP | P | 5852066 |
HERRON ELECTRIC COMPANY | ES | C | 05/22/2018 | Commercial Service: 600 - amp 4 Wire service, ok to set meter / | CRAIG | CRAIG | | ES | C | 5852062 |
HERRON ELECTRIC COMPANY | ER | C | 05/17/2018 | drop ceiling ok | CRAIG | CRAIG | | ER | C | 5847970 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 05/16/2018 | FIRE ALARM INSPECTION: | CRAIG | CRAIG | | E= | C | 5846531 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 05/16/2018 | FIRE ALARM INSPECTION: drop ceiling ok | CRAIG | CRAIG | | ER | C | 5846529 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 05/16/2018 | FIRE ALARM INSPECTION: drop ceiling ok | CRAIG | CRAIG | | E= | C | 5846530 |
HERRON ELECTRIC COMPANY | ER | P | 04/30/2018 | front counter top ok wall and hard lid in front of counter top of Arby' s ok | CRAIG | CRAIG | | ER | P | 5830771 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 04/17/2018 | FIRE ALARM INSPECTION: 3/4" emt for 2 pull station ok | CRAIG | CRAIG | | ER | P | 5818896 |
HERRON ELECTRIC COMPANY | ER | P | 04/10/2018 | Arby' s side walls and soffit ok | CRAIG | CRAIG | | ER | P | 5812510 |
ROGERS PLUMBING, INC. | HSP | P | 06/15/2018 | LETTER CHANGING EXISTING GAS LINE TO NEW LINE FROM ENGINEER, SEE IMAGES | BENH | BENH | | HSP | P | 5875534 |
ANYTHING HVAC, LLC. | H= | C | 06/15/2018 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5875526 |
ANYTHING HVAC, LLC. | H= | P | 06/14/2018 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. | NANCY | NANCY | | H= | P | 5875134 |
ROGERS PLUMBING, INC. | H= | C | 06/13/2018 | GAS FINAL OK PER MECHANICAL | BENH | BENH | | H= | C | 5873847 |
ALNOR INC. | H= | C | 06/13/2018 | REFRIGERANT FINAL OK PER MECHANICAL | BENH | BENH | | H= | C | 5873803 |
ANYTHING HVAC, LLC. | H= | P | 06/13/2018 | FIELD CANCELLED BY CONTRACTOR | BENH | BENH | | H= | P | 5873758 |
ALNOR INC. | H= | P | 06/12/2018 | PROVIDE INSTALLATION INSTRUCTIONS FOR REFRIGERANT LEAKAGE ALARMS AND RE-CALL FOR INSPECTION, ATTACH INSTRUCTIONS TO INSPECTION REQUEST | BENH | BENH | | H= | P | 5871864 |
ROGERS PLUMBING, INC. | H= | P | 06/08/2018 | PER INSPECTION COMMENTS ON 5/9/18 NEED REVISED APPROVED PRINTS OR LETTER FROM ENGINEER STATING GAS LINES ARE NEW NOT EXISTING,REST OK | BENH | BENH | | H= | P | 5869394 |
R & R DITCHING, INC | H= | C | 06/06/2018 | GAS FINAL FOR UNDERGROUND GAS LINES OK. | NANCY | NANCY | | H= | C | 5866440 |
ANYTHING HVAC, LLC. | H= | P | 06/01/2018 | INSTALL FACTORY EXTENSION ON GREASE FAN. VERIFY ALL UNITS HAVE BEEN CONVERTED TO PROPANE AND LABELED FOR PROPANE. PROVIDE TEST AND BALANCE REPORT. INTERLOCKS OK. | NANCY | NANCY | | H= | P | 5862730 |
ALNOR INC. | H= | P | 06/01/2018 | INSTALL REFRIGERATION LEAKAGE ALARMS PER KEYNOTE 5 SHEET M1.1. | NANCY | NANCY | | H= | P | 5862729 |
R & R DITCHING, INC | HO | C | 05/29/2018 | 10 LB TEST OK. OK TO COVER TRENCH. | NANCY | NANCY | | HO | C | 5858058 |
ANYTHING HVAC, LLC. | H= | P | 05/25/2018 | EF-2 IS LESS THAN 10 FEET FROM PARAPET WALL SEE IMC 506.3.12.3 (TERMINATION LOCATION) AND IMC 5060505 (TERMINATION LOCATION EXCEPTION). SEAL GREASE DUCT FLANGE TO CURB. INSTALL GREASE TRAY ON FAN. INSTALL GAS CUP ON HOODS. NEED TO VERIFY INTERLOCKS PER PLAN. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5856569 |
ROGERS PLUMBING, INC. | HI | C | 05/23/2018 | 10 LB TEST OK FOR DROP TO COOK LINE | BENH | BENH | | HI | C | 5853584 |
ANYTHING HVAC, LLC. | HD | P | 05/17/2018 | ABOVE HOOD OK ALL GAPS SEALED AND COVERED WITH METAL | BENH | BENH | | HD | P | 5847991 |
ANYTHING HVAC, LLC. | HV | C | 05/17/2018 | VENT TERMINATION OK, WENT WITH 2 PIPE SYSTEM INSTEAD OF CONCENTRIC KIT | BENH | BENH | | HV | C | 5847986 |
ANYTHING HVAC, LLC. | HV | P | 05/15/2018 | WATER HEATER VENTS TOO LONG PER MANUFACTURERS INSTRUCTIONS. SUPPORT VENT PIPES EVERY FOUR FEET. | NANCY | NANCY | | HV | P | 5845353 |
ANYTHING HVAC, LLC. | HD | P | 05/11/2018 | ABOVE CEILING ONLY INSPECTION TODAY. SEAL GAPS IN STAINLESS STEEL PANELS BEHIND HOOD. TOP OF CEMENT BOARD EXPOSED BEHIND HOOD. LARGE GAPS BETWEEN STAINLESS AND CEMENT BOARD. FSK PAPER WITHIN 18 INCHES OF TOP OF HOOD. REMOVE FIRST 18 INCHES OF INSULATION FROM MAKE-UP AIR DUCTS AT HOOD. REMOVE COMBUSTIBLES FROM TOP OF HOOD. INSTALL SUPPLY REGISTER IN VESTIBULE. CALL FOR INSPECTION OF WATER HEATER VENTS WHEN READY. REST OF ABOVE CEILING OK. STILL NEED CONTROLS, INTERLOCKS VERIFIED, AND ROOF. | NANCY | NANCY | | HD | P | 5843129 |
ROGERS PLUMBING, INC. | HI | P | 05/09/2018 | CONTRACTOR INSTALLING GAS LINE FROM PROPANE TANKS TO BUILDING MUST ATTACH TO PERMIT AND CALL FOR INSPECTION WHEN READY. IF EQUIPMENT/APPLIANCES DID NOT COME FROM FACTORY WITH PROPANE ORIFICES EITHER GAS OR MECHANICAL CONTRACTOR WILL NEED TO CHANGE ORIFICES AND PROPERLY LABEL EQUIPMENT/APPLIANCES. NEED REVISED/APPROVED PRINT OR LETTER FROM ENGINEER STATING GAS LINES ARE NEW NOT EXISTING. 10 LB TEST OK ON MEDIUM PRESSURE GAS LINES. INSTALLED AS PER PRINT. STILL NEED TO SEE ALL REGULAR PRESSURE LINES AND REGULATORS INSTALLED. FOR ALL FUTURE INSPECTIONS PLEASE DO A 10 LB TEST ON NO MORE THAN A 30 LB GAUGE. | NANCY | NANCY | | HI | P | 5840331 |
ANYTHING HVAC, LLC. | HD | P | 05/03/2018 | ALL GREASE DUCT CONNECTIONS OK, OK TO GREASE WRAP | BENH | BENH | | HD | P | 5835282 |
ANYTHING HVAC, LLC. | HD | P | 04/23/2018 | TYPE OF CO2 TANK? TANK LOCATED WHERE? GREASE DUCT INSPECTED ON GROUND AND OK. STILL NEED TO SEE MARKED BUTT WELDS. HOOD WALL OK, OK TO COVER PER MECHANICAL ONLY. PROVIDE PICTURE OF INSULATION IN WALL, INSULATION TO HAVE NO PAPER BACKING. | NANCY | NANCY | | HD | P | 5824419 |
ANYTHING HVAC, LLC. | HD | P | 04/18/2018 | NEED REFRIGERATION CONTRACTOR ATTACHED TO PERMIT, ADD WATER HEATER VENTS TO SCOPE OF WORK. PROTECT HOOD SHEAR WALL. RTU-1 AND RTU-2 SUPPLY/RETURN DUCTS AND LATERALS OK, OK TO WRAP. NOTE: SEE M1.1 FOR INTERLOCK SCHEDULE. RTU SMOKE DETECTORS BEING MONITORED BY PANEL, NO REMOTE INDICATORS REQUIRED. | NANCY | NANCY | | HD | P | 5820231 |
CENTRAL PLUMBING INC | P= | C | 06/13/2018 | engineer letter received for backflow at soda dispenser and sent to scanning | JOSEPHD | JOSEPHD | | P= | C | 5872732 |
CENTRAL PLUMBING INC | P= | P | 06/08/2018 | need engineer letter for backflow change at soda dispenser, other correction made | JOSEPHD | JOSEPHD | | P= | P | 5868934 |
CENTRAL PLUMBING INC | PTO | C | 06/08/2018 | Corrections made | SHANEN | SHANEN | | PTO | C | 5868523 |
CENTRAL PLUMBING INC | P= | P | 06/07/2018 | need verification on backflow to soda dispenser, 3 comp sink needs to be individually drained, will need to talk to prior inspector about PTO that was never completed | JOSEPHD | JOSEPHD | | P= | P | 5867569 |
CENTRAL PLUMBING INC | PB | C | 04/11/2018 | Correction made, DWV test OK | SHANEN | SHANEN | | PB | C | 5813584 |
CENTRAL PLUMBING INC | PTO | P | 04/10/2018 | Need to use approved primer on all PVC joints, need clean outs for all sink and urinals per plans, water distribution test OK | SHANEN | SHANEN | | PTO | P | 5812628 |