FLETCHER C.M. | B= | C | 10/16/2018 | All other required Final inspections are complete. (This is a computer generated result) | RICHB | RICHB | | B= | C | 5996192 |
FLETCHER C.M. | B= | P | 10/15/2018 | Remodel complete pending Fire. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | RICHB | RICHB | | B= | P | 5995037 |
FLETCHER C.M. | BFR | P | 06/21/2018 | need to pull mechanical permit and have inspections / new interior light gauge framing OK pending other roughs | DANE | DANE | | BFR | P | 5881716 |
TECHMASTERS ELECTRICAL LLC | E= | C | 10/11/2018 | | GARYL | GARYL | | E= | C | 5992524 |
TECHMASTERS ELECTRICAL LLC | E= | P | 10/05/2018 | Need prints, replace an existing recept by bar sink with gfci protection | GARYL | GARYL | | E= | P | 5988027 |
TECHMASTERS ELECTRICAL LLC | ER | P | 06/20/2018 | next inspection must have stamped set of plans on site, wall rough: based on electricians set of plans, 3 walls,ok--------1 switch in front needs to be lowered to 48" per ada, Discussed accessibility requirements with contractor / | JOHNN | JOHNN | | ER | P | 5879733 |
ROCKY MOUNTAIN AIR SYSTEMS | H= | C | 10/10/2018 | DISH HOOD INTERLOCKS ARE COMPLETE | JERRYF | JERRYF | | H= | C | 5991051 |
ROCKY MOUNTAIN AIR SYSTEMS | H= | P | 10/05/2018 | INTERLOCK LETTER RECEIVED DOES NOT ADDRESS DISH INTERLOCKS CALLED FOR ON SEQUENCE OF OPERATION ON PLANS | JERRYF | JERRYF | | H= | P | 5986854 |
ROCKY MOUNTAIN AIR SYSTEMS | HC | C | 10/04/2018 | OK TO RELEASE 2# METER | JERRYF | JERRYF | | HC | C | 5986373 |
ROCKY MOUNTAIN AIR SYSTEMS | HI | C | 10/04/2018 | PRESSURE TEST AND PIPING OK PER PLAN | JERRYF | JERRYF | | HI | C | 5986301 |
ROCKY MOUNTAIN AIR SYSTEMS | H= | P | 10/04/2018 | NEED LETTER FROM ENGINEER TO APPROVE EXISTING INTERLOCKS AT DISH HOOD AND KEF 1 AND 2 | JERRYF | JERRYF | | H= | P | 5986159 |
ROCKY MOUNTAIN AIR SYSTEMS | H= | P | 09/25/2018 | NEED GAS ATTACHED TO INCLUDE 6 STUBS AND INSPECTION CALLED WITH 10# ON 30# GAUGE - NEED INTERLOCKS AT DISH HOOD PER PLAN AND VERIFIED - REMOVE ALL SA DUCT IN DINING AREA FROM PLAN PER PREVIOUS NOTES - NEED OSA AIR HOODS SCREENED AND SEALED AT EXTERIOR NOTES: TAB REPORT RECEIVED - ROOF INSPECTION COMPLETE | JERRYF | JERRYF | | H= | P | 5975907 |
ROCKY MOUNTAIN AIR SYSTEMS | H= | R | 08/28/2018 | NEED CONSULT ON HOOD WALL WAIVED TRIP FEE THIS TIME ONLY - NOT READY - NEED ALL NEW SA DUCT IN SERVING AREA DELETED FROM PLAN OR INSTALL - INSTALL OR DELETE EXHAUST FAN AT MOP SINK - DELETE STAINLESS WALL BEHIND ALL HOODS OR COMPLETE - INSTALL MOTOR DAMPERS AT OSA DUCTS PER PLAN - SECURE EXHAUST FAN FOR HOOD ON ROOF - WILL NEED ROOF INSPECTION - NEED GAS CONTRACTOR ATTACHED AND INSPECTIONS CALLED - STOPPED INSPECTION - MAY BE MORE - CONTRACTOR REVIEW ALL PLANS INCLUDING SPLICES AND CONFIRM ITEMS ARE COMPLETED BEFORE CALLING INSPECTIONS OR TRIP FEE MAY BE ACCESSED - CONTRACTOR NEEDS TO SUPPLY CALL AHEAD NUMBER FOR ONSITE PERSONNEL - | JERRYF | JERRYF | | H= | R | 5948518 |
ROCKY MOUNTAIN AIR SYSTEMS | HD | P | 08/21/2018 | TYPE 2 HOOD DUCT OK - AT FUTURE INSPECTION VERIFY ALL WASH ABLE SURFACE BEHIND HOOD - VERIFY EQUIPMENT UNDER HOOD - REVISE PLAN DELETING WALL DETAIL FROM PLANS - VERIFY OSA MOTOR DAMPERS | JERRYF | JERRYF | | HD | P | 5941313 |
ROCKY MOUNTAIN AIR SYSTEMS | HSP | P | 08/14/2018 | NEED ENGINEER TO ADDRESS COMBUSTIBLES IN HOOD WALL PLAN SHOWS ZERO CLEARANCE HOOD / INSTALLED HOOD IS NOT ZERO CLEARANCE AND DOES NOT MATCH PLAN - METAL FASTENERS IN METAL WASH ABLE SURFACE HAVE COMPROMISED WALL CONSTRUCTION - NEED ENGINEER TO ADDRESS | JERRYF | JERRYF | | HSP | P | 5932926 |
ROCKY MOUNTAIN AIR SYSTEMS | HD | L | 08/13/2018 | NEED CONSULT WITH SENIOR INSPECTOR ON HOOD WALL HAS COMBUSTIBLES IN WALL AND QUESTION STAINLESS STEEL ON WALL - STILL NEED GREASE DUCT INSPECTION - CANNOT USE SCREWS TO FASTEN METAL TO WALLS - NEED ALL GAPS SEALED AND METAL EXTENDED 18" ABOVE HOOD - STOPPED INSPECTION | JERRYF | JERRYF | | HD | L | 5932438 |
ROCKY MOUNTAIN AIR SYSTEMS | HD | L | 08/08/2018 | NO CALL AHEAD INFORMATION GIVEN - BOTH FRONT AND BACK DOORS LOCKED AT 12:53 - CONTRACTOR PLEASE CALL THIS INSPECTOR BEFORE 8:15 AM ON 8/9 | JERRYF | JERRYF | | HD | L | 5927717 |
ROCKY MOUNTAIN AIR SYSTEMS | HSP | P | 07/26/2018 | PLAN CALLS FOR NON COMBUSTIBLE WALL PER NOTE #5 - ENGINEER TO ADDRESS THIS ISSUE | JERRYF | JERRYF | | HSP | P | 5914346 |
ROCKY MOUNTAIN AIR SYSTEMS | HD | R | 07/25/2018 | NEED CONSULT WITH SENIOR INSPECTOR AND PLAN REVIEW ON HOOD AND HOOD WALL CONSTRUCTION - PLANS CALL FOR ZERO CLEARANCE HOOD - HOOD DOES NOT MATCH PLANS - THIS IS NOT A ZERO CLEARANCE HOOD - HAS COMBUSTIBLE MATERIALS ON WALL - NEED MECHANICAL CONTRACTOR ONSITE FOR NEXT INSPECTION - NEED ALL GAPS INSIDE GREASE DUCT WELDED AND GROUND SMOOTH - NEED LIGHT FOR NEXT GREASE DUCT INSPECTION - COULD NOT LOCATE OUTSIDE AIR DAMPERS - STOPPED INSPECTION - RE INSPECT ALL | JERRYF | JERRYF | | HD | R | 5913746 |
TECHMASTERS PLUMBING LLC | P= | C | 10/11/2018 | Plans revised, correction made | SHANEN | SHANEN | | P= | C | 5992748 |
TECHMASTERS PLUMBING LLC | P= | P | 10/11/2018 | Need engineers letter to use hub drain in lieu of floor sink for ice machine drain, cannot use san-tee on horizontal drain, check valve and hammer arrestor installed | SHANEN | SHANEN | | P= | P | 5992274 |
TECHMASTERS PLUMBING LLC | P= | R | 10/05/2018 | Need floor sink and indirect waste for ice machine, need hammer arrestor and check valve for ice machine, no hot water, re-inspect all | SHANEN | SHANEN | | P= | R | 5987736 |
TECHMASTERS PLUMBING LLC | PTO | P | 06/20/2018 | Bar area OK, need water line for ice machine, attach mechanical permit | SHANEN | SHANEN | | PTO | P | 5880840 |
ROCKY MOUNTAIN AIR SYSTEMS | XMS | T | 09/26/2018 | PAID (REC#1541347) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new mechanical splice 9-26-18 | TCRIPPEN | TCRIPPEN | | XMS | T | 5976731 |
ROCKY MOUNTAIN AIR SYSTEMS | XMS | T | 09/06/2018 | PAID (REC#1534499) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised plan for inspector comments | JUSTINC | JUSTINC | | XMS | T | 5957235 |
ROCKY MOUNTAIN AIR SYSTEMS | XMS | P | 08/21/2018 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised for TYPE 2 hood | JUSTINC | JUSTINC | | XMS | P | 5940359 |
TECHMASTERS ELECTRICAL LLC | XES | T | 06/25/2018 | PAID (REC#1510308) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added three receptacles and revised panel schedule. | BERTHA | BERTHA | | XES | T | 5884215 |
FLETCHER C.M. | XPS | T | 06/15/2018 | PAID (REC#1509059) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 6-15-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5876351 |