E.G.C. SERVICES, INC | B= | C | 09/19/2018 | zoning was signed off. thanks | TERRI | TERRI | | B= | C | 5970573 |
E.G.C. SERVICES, INC | B= | P | 09/14/2018 | Temp CO: pending zoning and building finals ( Expires: 10/14/2018 12:00:00 AM) | NELIDA | NELIDA | | B= | P | 5965055 |
E.G.C. SERVICES, INC | B= | P | 09/12/2018 | Items corrected. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | NICK | NICK | | B= | P | 5963346 |
E.G.C. SERVICES, INC | BFR | C | 09/12/2018 | | NICK | NICK | | BFR | C | 5963345 |
E.G.C. SERVICES, INC | B= | P | 09/07/2018 | need restroom signs at correct height, soap dispenser at both restrooms over 48" for activation, frame items have been corrected. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), R D PLUMBING Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5958786 |
E.G.C. SERVICES, INC | BFR | P | 07/12/2018 | need restroom backing installed, discussed front door locks and above ceiling marking for final inspection / with completed required inspections frame okay, | NATHAN | NATHAN | | BFR | P | 5901164 |
ELECTRIC TECH INC. | E= | C | 08/28/2018 | NOTES---SIGN DISCO INSTALLED IN GRID CEILINGS | BRIAN | BRIAN | | E= | C | 5947715 |
ELECTRIC TECH INC. | ER | C | 08/14/2018 | REST OF THE GRID CEILINGS---OK | BRIAN | BRIAN | | ER | C | 5933214 |
ELECTRIC TECH INC. | ER | P | 08/10/2018 | DINING AREA--CEILING OK | BRIAN | BRIAN | | ER | P | 5930510 |
ELECTRIC TECH INC. | ER | P | 07/17/2018 | WALLS COMPLETE--- | BRIAN | BRIAN | | ER | P | 5905263 |
ELECTRIC TECH INC. | ER | P | 07/16/2018 | SOFFIT AND WALLS-- EXCEPT THE WALL WITH THE PANEL--- | BRIAN | BRIAN | | ER | P | 5903375 |
ELECTRIC TECH INC. | ER | P | 07/12/2018 | WALLS SEE PLANS----- | BRIAN | BRIAN | | ER | P | 5901422 |
ELECTRIC TECH INC. | ESL | C | 06/26/2018 | | JOHNN | JOHNN | | ESL | C | 5885215 |
AIRTECH MECHANICAL, INC. | H= | C | 09/06/2018 | TAB REPORT RECEIVED AND ALL ITEMS HAVE BEEN ADDRESSED | JERRYF | JERRYF | | H= | C | 5956221 |
AIRTECH MECHANICAL, INC. | H= | P | 09/05/2018 | LETTER FOR GREASE DUCT CHANGE RECEIVED - STILL NEED OTHER ITEMS ADDRESSED | JERRYF | JERRYF | | H= | P | 5954737 |
AIRTECH MECHANICAL, INC. | H= | P | 08/30/2018 | LABEL ALL ROOF EQUIPMENT - LABEL ALL MEDIUM PRESSURE PIPING - NEED INSTALL MANUAL FOR GAS REGULATORS TO VERIFY POSITION - TAB REPORT NOTES: INTERLOCKS ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5951269 |
AIRTECH MECHANICAL, INC. | HD | P | 08/09/2018 | ABOVE CEILING SA / RA / RESTROOM EXHAUST GRILLES AND FINAL CONNECTIONS ARE COMPLETE - STILL NEED INTERLOCKS - ROOF - TAB REPORT - CONTROLS - SOMEONE CLAIMING COOLER AND CALL INSPECTIONS | JERRYF | JERRYF | | HD | P | 5928819 |
AIRTECH MECHANICAL, INC. | HC | C | 08/09/2018 | RELEASE METER FOR 2# SYSTEM | JERRYF | JERRYF | | HC | C | 5928799 |
AIRTECH MECHANICAL, INC. | HI | C | 08/09/2018 | PRESSURE TEST AND PIPING OK PER PLAN - AT FINAL VERIFY ALL REGULATORS / VENTS / LABELS AND FINAL CONNECTIONS AND QUICK DISCONNECTS AT ALL COOKING APPLIANCES | JERRYF | JERRYF | | HI | C | 5928798 |
AIRTECH MECHANICAL, INC. | HSP | P | 08/02/2018 | NEED REFRIGERATION CONTRACTOR ATTACHED | JERRYF | JERRYF | | HSP | P | 5921487 |
AIRTECH MECHANICAL, INC. | H= | L | 08/01/2018 | NOT READY - TO MANY ITEMS TO LIST - NEED GAS CONTRACTOR ATTACHED TO PERMIT AND INSPECTIONS CALLED - DO NOT INSTALL CEILING TILES | JERRYF | JERRYF | | H= | L | 5920385 |
AIRTECH MECHANICAL, INC. | HD | P | 08/01/2018 | NEED GAS CONTRACTOR ATTACHED AND INSPECTIONS CALLED BEFORE CEILING CAN BE INSTALLED NOTES: GREASE DUCT OK TO WRAP / WILL NEED WRAP INSTALL MANUAL FOR NEXT INSPECTION | JERRYF | JERRYF | | HD | P | 5920377 |
AIRTECH MECHANICAL, INC. | HD | L | 07/31/2018 | CANCELED AT CALL AHEAD BY CONTRACTOR - ALREADY RESCHEDULED FOR 8/1 | JERRYF | JERRYF | | HD | L | 5918722 |
AIRTECH MECHANICAL, INC. | HD | P | 07/30/2018 | STILL HAVE LARGE HOLE ABOVE TEMPERATURE PROBE BOX - DO NOT COVER | JERRYF | JERRYF | | HD | P | 5917540 |
AIRTECH MECHANICAL, INC. | HD | P | 07/27/2018 | PATCH 3 HOLES ON WEST DUCT AT BOTTOM SIDE OF SQUARE TO ROUND COLLAR RECALL INSPECTION WHEN READY - LEAVE WRAP OFF AT THIS AREA REST OK FOR 2 LAYERS - NOTES ADDED AT 1:28 NEED PLANS REVISED FOR GREASE DUCT PLAN SHOWS FACTORY MADE DUCT HAS WELDED DUCT INSTALLED | JERRYF | JERRYF | | HD | P | 5916493 |
AIRTECH MECHANICAL, INC. | HD | P | 07/26/2018 | GREASE DUCT LIGHT TEST ON ALL MARKED WITH OK - STILL NEED CONNECTIONS AT CURD DROP TIE INS AND SQUARE TO ROUNDS AT HOOD NOTES: ALL ABOVE CEILING SA / RA MAINS AND RUN OUTS OK TO WRAP | JERRYF | JERRYF | | HD | P | 5914752 |
AIRTECH MECHANICAL, INC. | HD | P | 07/25/2018 | GREASE DUCT LIGHT TEST - LIGHT TEST AT SHOP FOR 2 CURB DROPS SIGNED AND DATED OK. | MARKB | MARKB | | HD | P | 5913359 |
AIRTECH MECHANICAL, INC. | HD | P | 07/13/2018 | HOOD WALL AND ABOVE CEILING SA / RA MAINS AND RUN OUTS OK IN BACK KITCHEN AREA ONLY | JERRYF | JERRYF | | HD | P | 5902391 |
R D PLUMBING LLC | P= | C | 09/12/2018 | Corrections made letter received, sent to scanning | SHANEN | SHANEN | | P= | C | 5962274 |
R D PLUMBING LLC | P= | P | 08/29/2018 | Need to complete PTO inspection. Need hammer arrester and check valve at ice machine. Need trap guard at floor drain next to mop sink. | SHANEN | SHANEN | | P= | P | 5949218 |
R D PLUMBING LLC | PTO | P | 07/11/2018 | Plans reflect type L copper water piping ( PEX installed ), cold water piping under sized per plans, plan notes require hot water re-circulated within two feet of hand sinks and public lavs, set and secure closet flanges, overhead vent piping under sized per plans, check water heater at final, | SHANEN | SHANEN | | PTO | P | 5898820 |
R D PLUMBING LLC | PB | C | 06/25/2018 | DWV sanitary and grease waste test OK | SHANEN | SHANEN | | PB | C | 5883934 |