HOMEOWNER | B= | C | 07/25/2019 | All other required Final inspections are complete. (This is a computer generated result) | JUSTINL | JUSTINL | | B= | C | 6276794 |
HOMEOWNER | B= | P | 07/17/2019 | Final inspection correction complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | JUSTINL | JUSTINL | | B= | P | 6266043 |
HOMEOWNER | B= | P | 07/16/2019 | 1. Missing posted address on house // Slab / No deck / Air Leakage Testing report (Blower Door) Per 2015 IECC Section R402.4.1 on file / -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | JUSTINL | JUSTINL | | B= | P | 6265823 |
HOMEOWNER | BIN | C | 06/06/2019 | Insulation at exterior walls and ceiling of habitable space OK / Reviewed Air Leakage Testing Requirements Per 2015 IECC Section R402.4.1.2 to be Provided by Final Inspection / | JUSTINL | JUSTINL | | BIN | C | 6223253 |
HOMEOWNER | BFR | C | 06/06/2019 | 3rd party observation for foundation insulation viewed on site - Provide copy for RBD record / Other frame corrections complete | JUSTINL | JUSTINL | | BFR | C | 6223252 |
HOMEOWNER | BFR | P | 06/03/2019 | 1. Provide foundation insulation observation / 2. Framing for fireplace bearing on slab and attached to roof trusses - Need 1 1/2" float / 3. Missing framing at under stair storage in garage - To be framed 24" OC max for 1/2" gyp / Previous inspection comments from first frame addressed / Plans reviewed electronically / Reviewed Air Leakage Testing Requirements Per 2015 IECC Section R402.4.1.2 to be Provided by Final Inspection / | JUSTINL | JUSTINL | | BFR | P | 6218622 |
HOMEOWNER | BFR | P | 03/22/2019 | 2017 PPRBC - Complete BFT - Complete all other rough inspections - Pole barn shell inspection only, interior residence not framed - Missing all required truss bracing, gable end and mid span - Missing nails in post caps for storage area above residence portion - Porch lids and posts ok - Pole barn framing aside from trusses ok - Reviewed requirements for 2015 IECC C402.5 Air Leakage and Air Barriers with site rep / | TIMOTHYS | TIMOTHYS | | BFR | P | 6141015 |
HOMEOWNER | BE | C | 03/18/2019 | | TERRI | TERRI | | BE | C | 6135069 |
HOMEOWNER | BFT | P | 09/28/2018 | piers ok, need open hole, soils report | DALE | DALE | | BFT | P | 5980754 |
HOMEOWNER | E= | C | 07/09/2019 | 25 a/c | TOMC | TOMC | | E= | C | 6257454 |
HOMEOWNER | ES | C | 07/09/2019 | Residential Underground: 200-amp 3-wire service upgrade, no action required by utility. / | TOMC | TOMC | | ES | C | 6257438 |
HOMEOWNER | ER | C | 05/31/2019 | ER OK -------CHECK PANELS AT FINAL INSP------ | GREGM | GREGM | | ER | C | 6216292 |
HOMEOWNER | ER | P | 05/22/2019 | PARTIAL ROUGH FOR LIVING AREA ------ | GREGM | GREGM | | ER | P | 6207455 |
HOMEOWNER | EUG | C | 04/08/2019 | 4/0-4/0-4/0-#2 | BRET | BRET | | EUG | C | 6158895 |
HOMEOWNER | EUG | P | 04/04/2019 | interior slab ok, (island feed) feeder from service 40' short of panel location | BRET | BRET | | EUG | P | 6155590 |
THE FURNACE GUY HEATING & COOLING | H= | C | 07/12/2019 | | TAYLOR | TAYLOR | | H= | C | 6261487 |
THE FURNACE GUY HEATING & COOLING | H= | P | 07/12/2019 | Cannot use permanent marker to identify whole house fan. Must use paint pen or a label. Picture of filter attached to permit images. | RANDYB | RANDYB | | H= | P | 6261172 |
THE FURNACE GUY HEATING & COOLING | H= | P | 07/09/2019 | Furnace is missing filter. Whole house ventilation switch needs to be installed and labeled. - Whole house ventilation provided by 110 CFM fan within the bathroom. - NOTES: Direct vent furnace. Attic area meets 50:1 for boiler. A/C Complete. | RANDYB | RANDYB | | H= | P | 6257849 |
THE FURNACE GUY HEATING & COOLING | HC | C | 06/05/2019 | RELEASE METER. | KYLEW | KYLEW | | HC | C | 6220225 |
HOMEOWNER | HI | C | 05/30/2019 | 10 LB TEST OK. 1" MAIN, 1 FURNACE, 1 BOILER, 1 FIREPLACE, 1 RANGE. | KYLEW | KYLEW | | HI | C | 6215368 |
HOMEOWNER | HWP | C | 05/29/2019 | 60 LB TEST OK FOR UNDER SLAB PIPE. | KYLEW | KYLEW | | HWP | C | 6213256 |
THE FURNACE GUY HEATING & COOLING | HRR | C | 05/23/2019 | CORRECTION MADE. SEE IMAGES. | KYLEW | KYLEW | | HRR | C | 6207897 |
THE FURNACE GUY HEATING & COOLING | HRR | P | 05/22/2019 | UPDATED NOTES FROM 5-21-19... NEED 4" BATH SUPPLY SEALED AT BOOT. AT FINAL WILL VERIFY INSULATED SUPPLY TRUNK LINES IN ATTIC AND COMPLETED BOILER VENT. WILL RELEASE METER ONCE PHOTO OF COMPLETED VENT IS RECEIVED WITH HC INSPECTION REQUEST. | KYLEW | KYLEW | | HRR | P | 6206554 |
FIREPLACE WAREHOUSE | HV | C | 05/22/2019 | FIREPLACE VENT AND FRAMING OK. WAS INSPECTED AT SAME TIME AS HRR. | KYLEW | KYLEW | | HV | C | 6206531 |
THE FURNACE GUY HEATING & COOLING | HRR | P | 05/21/2019 | SEAL 4" SUPPLY FOR BATHROOM AT BOOT. THE BOILER VENT WILL NEED TO BE CAPPED BEFORE METER CAN BE RELEASED. MORE RESEARCH REQUIRED. WILL UPDATE IN MORNING. WHOLE HOUSE VENTILATION WILL BE PROVIDED BY 110 CFM BATH FAN AND THE SWITCH LOCATION IS TO BE DETERMINED. NOTES: DIRECT VENT FURNACE. | KYLEW | KYLEW | | HRR | P | 6206124 |
HOMEOWNER | P= | C | 07/12/2019 | no irrigation, certificate of potable water ok, see images. | TAYLOR | TAYLOR | | P= | C | 6261488 |
HOMEOWNER | P= | L | 07/11/2019 | field cancelled. | TAYLOR | TAYLOR | | P= | L | 6260197 |
HOMEOWNER | PTO | C | 05/30/2019 | mixing valve in mech room. | TAYLOR | TAYLOR | | PTO | C | 6214657 |
HOMEOWNER | PTO | P | 05/29/2019 | need mixing valve rough for shower, can not crimp PE pipe at water service, need freeze protection at trap for dog wash, rest ok, aav's at kitchen and in wall behind dog wash, check vent termination by final. | TAYLOR | TAYLOR | | PTO | P | 6212936 |
HOMEOWNER | PWO | C | 04/04/2019 | need certificate of potable water and check connection at pressure tank pit by final. | TAYLOR | TAYLOR | | PWO | C | 6155231 |
HOMEOWNER | PB | C | 03/27/2019 | no water service at this time, note: will need PWO inspection. | TAYLOR | TAYLOR | | PB | C | 6145801 |
HOMEOWNER | XBS | T | 04/25/2019 | PAID (REC#1593969) PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised exterior wall framing | LBENNETT | LBENNETT | | XBS | T | 6177621 |