PEAK PROFESSIONAL CONTRS INC | B= | C | 05/07/2019 | other final inspections complete | BRIANB | BRIANB | | B= | C | 6191233 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 04/25/2019 | Temp CO: H= and B= are partialed, everything else complete ( Expires: 5/25/2019 12:00:00 AM) | GITA | GITA | | B= | P | 6177906 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 04/24/2019 | pending other final inspections / corrections okay / received observation letter for ceiling clouds - structural steel. Additional Inspections Required (computer generated): AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 6177254 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 04/22/2019 | still need observation letter for structural beam - soffits over bar dining area per sheet S1.0 and welding / missing indicator at double keyed lock at single front entry door / reflect surface of mirror measures over 40" from floor in both restrooms / do not have min 32" of clear opening width per ANSI 404.2.2 at both restroom accessible water closets / need to complete other final inspections / Training with PPRBD inspector Justin / VB construction - A2 occupancy / interior finish final inspection / went through approved design and accessible elements / IBC 1010.1.2 - door swing / 1010.1.10 panic and fire exit hardware / 1010.1.9.3 locks and latches / also discussed accessible elements at restrooms and accessible route -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, ALPHALETE MECHANICAL LLC Mechanical Final Inspection is not Completed yet, ALPHALETE MECHANICAL LLC Plumbing Final Inspection is not Completed yet, ELECTRIC TECH INC. Electrical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 6174369 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 04/22/2019 | Training with Brian B on interior finish - Reviewed code study - Plan box - Sticker sheet of plans - Reviewed plans - accessible elements to include clear floor space - Turning radius - accessible rout - plumbing fixtures - reach range - Door hardware - occupant loads - sign height at restrooms and exit signs - plan reading - code interpretation and application - other required inspections including external departments | JUSTINL | JUSTINL | | BSP | P | 6174367 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 02/20/2019 | observed remaining non-load bearing stl wall framing in dining area / pending other rough inspections | BRIANB | BRIANB | | BFR | P | 6112464 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 01/28/2019 | observed fire treated plywood above dining area installed | SCOTTS | SCOTTS | | BSP | P | 6090107 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 01/10/2019 | observed soffit framing over bar - lounge area and light gauge wall framing at vestibule - waiting area / observation letter for structural beam - soffits over bar dining area per sheet S1.0 and welding to follow / pending other rough inspections | BRIANB | BRIANB | | BFR | P | 6075365 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 01/02/2019 | still need to inspect wall framing at dining area 102 and soffit framing over front dining - bar area / observed other light gauge wall and soffit framing including non-rated demising wall framing (see approved plan splice 21DEC18) / observation letter for structural beam - soffits over bar dining area per sheet S1.0 and welding to follow / need to complete other rough inspections including mechanical inspection for hood wall / discussed accessible elements with site superintendents | BRIANB | BRIANB | | BFR | P | 6066681 |
PEAK PROFESSIONAL CONTRS INC | BSP | R | 12/07/2018 | not ready/reviewed listing for Ul U412 at north wall | SCOTTS | SCOTTS | | BSP | R | 6046290 |
ELECTRIC TECH INC. | E= | C | 04/23/2019 | Electrical complete / | ROB | ROB | | E= | C | 6175770 |
ELECTRIC TECH INC. | E= | P | 04/18/2019 | Need GFCI protection at bar recpts. / Need disconnects for patio heaters / EF 1,2,3,5 need MOP 15 amp breakers / MUA 1 needs MOP 15 amp breaker / Panel A & B have 10K breakers and plan calls for 22K / | ROB | ROB | | E= | P | 6170336 |
ELECTRIC TECH INC. | ER | P | 03/12/2019 | Grid ceiling ok / NOTE: Need to check j box where kitchen lights are tied in to ext. cord at next inspection / | ROB | ROB | | ER | P | 6131738 |
ELECTRIC TECH INC. | ES | C | 02/27/2019 | Commercial Service: 800 amp 4 wire 3 phase new commercial service--okay to set meter | CHIPO | CHIPO | | ES | C | 6118932 |
ELECTRIC TECH INC. | ER | P | 02/21/2019 | Rough ok for half dining wall / | ROB | ROB | | ER | P | 6113541 |
ELECTRIC TECH INC. | ER | P | 01/22/2019 | Rough ok for hard lids / Vestibule wall rough ok / | ROB | ROB | | ER | P | 6084939 |
ELECTRIC TECH INC. | ER | P | 01/08/2019 | Rough ok for walls except booth and half wall in dining area / | ROB | ROB | | ER | P | 6071926 |
ELECTRIC TECH INC. | ER | P | 12/14/2018 | hood wall rough okay | CHIPO | CHIPO | | ER | P | 6053795 |
ELECTRIC TECH INC. | ER | P | 12/07/2018 | Rough fo exterior walls ok-- Discussed accessibility requirements with contractor / | ROB | ROB | | ER | P | 6046190 |
AIRTECH MECHANICAL, INC. | H= | C | 05/01/2019 | TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) N | LIDO | LIDO | | H= | C | 6183709 |
AIRTECH MECHANICAL, INC. | H= | P | 05/01/2019 | TEST AND BALANCE REPORT REVIEW: RTU-12 - 400 CFM'S WAS USED FOR THE DESIGN FOR THE OUTSIDE AIR / THE OUTSIDE AIR SCHEDULE ON PLAN PAGE M1.0 SHOWS THE DESIGN / CAPABLE CFM'S TO BE 4000 CFM'S . (RE-BALANCE FOR THE KITCHEN HOOD MAKE UP AIR OK .) | LIDO | LIDO | | H= | P | 6183404 |
AIRTECH MECHANICAL, INC. | HSP | P | 04/25/2019 | DUE TO THE KITCHEN HOOD INTERLOCK CHANGES A REVISED TEST AND BALANCE REPORT WILL BE REQUIRED. A SPLICE IS REQUIRED FOR THE INTERLOCK CHANGES. | LIDO | LIDO | | HSP | P | 6177608 |
AIRTECH MECHANICAL, INC. | HSP | P | 04/24/2019 | TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) | LIDO | LIDO | | HSP | P | 6176128 |
ALPHALETE MECHANICAL LLC | H= | C | 04/23/2019 | HEAT FINAL OK. | LIDO | LIDO | | H= | C | 6175909 |
AIRTECH MECHANICAL, INC. | HSP | P | 04/23/2019 | KITCHEN HOOD INTERLOCKS : PER PLAN PAGE M1.0 NOTE #3 MUA -1, MUA-2, EF-1,2,3,4,5, RTU - 10,11,12,13.BLOWERS TO OPERATE ON COMBINED HOOD SWITCH . THIS IS NOT HOW THE HOODS ARE INTERLOCKED. (CONTRACTOR TO ADDRESS.) CALL ME IF YOU HAVE QUESTIONS 719-327-2928. | LIDO | LIDO | | HSP | P | 6175269 |
AIRTECH MECHANICAL, INC. | H= | P | 04/23/2019 | TEST AND BALANCE REPORT REVIEW: RTU-12 - 400 CFM'S WAS USED FOR THE DESIGN FOR THE OUTSIDE AIR / THE OUTSIDE AIR SCHEDULE ON PLAN PAGE M1.0 SHOWS THE DESIGN / CAPABLE CFM'S TO BE 4000 CFM'S . MISSING RTU-13 OUTSIDE AIR CAPABLE REQUIREMENTS ON THE OUTSIDE AIR SCHEDULE / THIS WILL NEED TO BE SPICED INTO THE PLANS TO COMPLETE THE REVEIW OF THE TEST AND BALANCE REPORT . | LIDO | LIDO | | H= | P | 6174888 |
HAWKINS COMMERCIAL APPLIANCE SERVICE INC. | H= | C | 04/22/2019 | HEAT FINAL OK. | LIDO | LIDO | | H= | C | 6173625 |
AIRTECH MECHANICAL, INC. | H= | P | 04/22/2019 | PARTIAL PENDING: NEED TO RESEARCH KITCHEN HOOD ENTER LOCK SEQUENCE / MUA -1 AND EF-1 COMES ON WHEN HOOD- 1 TEMP CENSOR IS ACTIVATED/ MUA -2 AND EF-2,3,4 COME ON WHEN HOOD 2,3,4 TEMP CENSORS ARE ACTIVATED/ RTU-10,11,12,13 ARE IN AUTO AND COME ON AFTER 7:00 AM. NEED TEST AND BALANCE REPORT .
| LIDO | LIDO | | H= | P | 6173620 |
AIRTECH MECHANICAL, INC. | H= | P | 04/19/2019 | PARTIAL PENDING : NEED HOOD ENTER LOCKS VERIFIED, RTU-13 NEED THE CORRECT SQUARE INCHES FOR ABOVE CEILING RETURN AIR. NEED TO VERIFY ELECTRIC HEATERS, NEED TEST AND BALANCE REPORT. | LIDO | LIDO | | H= | P | 6172226 |
ALPHALETE MECHANICAL LLC | H= | P | 04/19/2019 | PARTIAL PENDING : MISSING SHUT OFF VALVES AHEAD OF THE GAS REGULATORS FOR ROOF TOP EQUIPMENT, ATTACH TWO WATER HEATER VENTS TO THE SCOPE OF WORK / WATER HEATER VENT TERMINATIONS ON ROOF ARE LESS THAN 10 FEET FROM PARAPET REFER TO INSTALLATION INSTRUCTIONS PAGE # 33 FOR TERMINATION CLEARANCE REQUIREMENTS . PER PAGE # 20 A MANUFACTURE PROVIDED CPVC STARTER LENGTH IS REQUIRED AT THE VENT PIPE CONNECTION TO THE WATER HEATERS . | LIDO | LIDO | | H= | P | 6172207 |
WESTERN FIREPLACE SUPPLY, INC. | H= | C | 04/02/2019 | FIREPLACE CONTRACTOR FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6152914 |
HAWKINS COMMERCIAL APPLIANCE SERVICE INC. | H= | P | 03/27/2019 | PARTIAL PENDING : NEED ICE MACHINE ADDED TO SCOPE OFF WORK . NEED TO SEE FINAL TIE-IN TO CONDENSER AND CONDENSATE DISPOSAL. | LIDO | LIDO | | H= | P | 6146907 |
HAWKINS COMMERCIAL APPLIANCE SERVICE INC. | HRP | P | 03/27/2019 | 3- 145 POUND TEST FOR THE THREE WALK IN COOLER/ FREEZERS OK . | LIDO | LIDO | | HRP | P | 6146906 |
AIRTECH MECHANICAL, INC. | HD | P | 03/07/2019 | NEED TO COMPLETE DISHWASHER HOOD AND DUCT INSTALL, RTU-13 NEED THE CORRECT SQUARE INCHES FOR ABOVE CEILING RETURN AIR,NEED SUPPLY AIR FOR ROOM # 108 AND 111, EF-1 PRE FABRICATED GREASE DUCT 2ND LAYER CONNECTION AT HOOD 1 IS NOT CORRECT / THE REST OF GREASE DUCT INSIDE BUILDING OK , EF-3 PRE FABRICATED GREASE DUCT 2ND LAYER CONNECTION AT HOOD 3 IS NOT CORRECT, ALL TYPE 1 HOODS AT WALL OK. RTU 10,11 DUCT INSTALL AND REGISTERS FINAL CONNECTIONS OK, MUA-1,2 CONNECTION TO ALL TYPE 1 HOODS OK . STILL NEED HOOD INTERLOCKS , ELECTRIC HEATERS, ROOF, AND FINAL WALK FOR ALL THERMOSTATS SENSORS , NEED TEST AND BALANCE. | LIDO | LIDO | | HD | P | 6126944 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 02/08/2019 | SHEET ROCK AROUND FIREPLACE OK . | LIDO | LIDO | | HV | C | 6101312 |
WESTERN FIREPLACE SUPPLY, INC. | HV | P | 02/01/2019 | ((NEED TO INSPECT AFTER ROCK INSTALLED TO VERIFY NO SCREWS HAVE PENETRATED FIREPLACE.)) FIREPLACE FRAME AND VENT OK. | LIDO | LIDO | | HV | P | 6095209 |
WESTERN FIREPLACE SUPPLY, INC. | HV | R | 01/31/2019 | THIS PERMIT ATTACHMENT WAS ORIGINALLY ON THE WRONG PERMIT NUMBER. WHEN THIS ATTACHMENT WAS TRANSFERRED TO THIS PERMIT THE INSPECTION HISTORY TRANSFERRED WITH IT, PLEASE DISREGARD. TRAINING WITH NANCY .THERE IS NO FIREPLACE ON THE PLANS FOR THIS PERMIT / THIS CONTRACTOR MAY BE ATTACHED TO THE WRONG PERMIT , IF SO CONTRACTOR WILL NEED TO BE REMOVED FROM THIS PERMIT. | LIDO | LIDO | | HV | R | 6094490 |
ALPHALETE MECHANICAL LLC | HC | C | 01/25/2019 | RELEASE FOR MEDIUM PRESSURE METER. | LIDO | LIDO | | HC | C | 6088637 |
ALPHALETE MECHANICAL LLC | HI | P | 01/24/2019 | ALL GAS FLEX CONNECTORS FOR EQUIPMENT ON ROOF ARE UNDERSIZED / EXCEPT FOR RTU-13 FINAL CONNECTION AND REGULATOR OK . ALL REGULATORS INSTALLED ON ROOF. | LIDO | LIDO | | HI | P | 6087377 |
ALPHALETE MECHANICAL LLC | HI | P | 01/18/2019 | STILL NEED TO SEE ANSUL , FINAL CONNECTIONS AND REGULATORS TO ALL THE EQUIPMENT INSIDE AND ON ROOF.10 LB TEST OK / THE REMAINING GAS PIPE INSTALL OK . ALL MEDIUM PRESSURE LABELS IN PLACE . | LIDO | LIDO | | HI | P | 6083333 |
AIRTECH MECHANICAL, INC. | HD | P | 01/02/2019 | NEED FIREPLACE CONTRACTOR FOR INSIDE AND OUTSIDE FIRE PLACE TO ATTACH TO PERMIT . MUA UNIT -1 AND 2 : ELEVEN 16 " ROUND TAPS ARE INSTALLED FOR THE RUN OUTS FOR THE MAKEUP AIR TO THE HOODS, PLAN SHOWS NINE 28 X 12 AND TWO 28 X 10 THE SQUARE INCHES ARE NOT THE SAME / INSTALL PER PLAN OR HAVE PLANS REVISED AND APPROVED. (TRUNK LINE OK , STILL NEED DROPS.) RTU-10 SUPPLY DUCT AND REGISTERS OK / STILL NEED RETURN . RTU-11 ABOVE CEILING SUPPLY AND RETURN DUCT ROUGH AND DROPS OK. RTU-12 ABOVE CEILING SUPPLY AND RETURN DUCT ROUGH AND DROPS OK . EX-6 ABOVE HARD LID DUCT ROUGH OK / STILL NEED DROP INSTALLED. HOOD WALL FOR ALL FOUR HOODS OK . | LIDO | LIDO | | HD | P | 6066929 |
ALPHALETE MECHANICAL LLC | HO | P | 12/20/2018 | 10 lb TEST OK /OK TO COVER. WHEN PASSING THROUGH A OUTSIDE WALL PIPING SHALL BE PROTECTED REFER TO 2009 IFGC CODE SECTION 404.7 | LIDO | LIDO | | HO | P | 6059872 |
ALPHALETE MECHANICAL LLC | HI | P | 12/11/2018 | GAS PIPE INSTALL IN WALL AND GAS STUB OUTS FOR COOK LINE ONLY - 10 lb TEST OK/ INSTALL OK. | LIDO | LIDO | | HI | P | 6049410 |
ALPHALETE MECHANICAL LLC | HI | P | 12/10/2018 | MISSING GAS STUB FOR GAS APPLIANCE #35 AND # 43 /NEED TO RE-INSPECT COOK LINE GAS PIPE . | LIDO | LIDO | | HI | P | 6048174 |
ALPHALETE MECHANICAL LLC | HI | P | 12/05/2018 | CONTRACTOR INSTALLING THE TWO WATER HEATER VENTS WILL NEED TO ADD VENTS TO THERE SCOPE OF WORK . CONTRACTOR INSTALLING WALK IN COOLER/FREEZER AND KEG COOLER NEEDS TO ATTACH TO PERMIT. 10 lb TEST AND FOR 1 1/2" GAS AND INSTALL IN EAST WALL ONLY OK . | LIDO | LIDO | | HI | P | 6043975 |
ALPHALETE MECHANICAL LLC | P= | C | 04/23/2019 | correction made | TED | TED | | P= | C | 6175330 |
ALPHALETE MECHANICAL LLC | P= | P | 04/19/2019 | need water hammers on front under counter dish washer and kitchen dish washer, need water hammer on ice maker, rest ok, fill and drain down valves in water heater room, | TED | TED | | P= | P | 6171905 |
ALPHALETE MECHANICAL LLC | PB | C | 02/05/2019 | base completed under core and shell Permit L50261 | TED | TED | | PB | C | 6097835 |
ALPHALETE MECHANICAL LLC | PTO | P | 01/14/2019 | need water lines run to roof top evap. units and fill/ drain down units installed, rest ok to cover | TED | TED | | PTO | P | 6077692 |
ALPHALETE MECHANICAL LLC | PTO | P | 01/11/2019 | field cancel | TED | TED | | PTO | P | 6075742 |
ALPHALETE MECHANICAL LLC | PTO | P | 12/10/2018 | In wall dwv and domestic water hood wall ok. | DANR | DANR | | PTO | P | 6047569 |
WESTERN FIREPLACE SUPPLY, INC. | XMS | T | 04/30/2019 | PAID (REC#1594490) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised interlocks and makeup air sequence | JUSTINC | JUSTINC | | XMS | T | 6182418 |
ELECTRIC TECH INC. | XES | T | 04/22/2019 | PAID (REC#1592331) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised feeder schedule, Panels A and B series rated, provided series rated listing, revised UH's disconnects. | BERTHA | BERTHA | | XES | T | 6173980 |
ELECTRIC TECH INC. | XES | T | 01/04/2019 | PAID (REC#1567357) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added UH's. | BERTHA | BERTHA | | XES | T | 6069193 |
AIRTECH MECHANICAL, INC. | XMS | P | 01/04/2019 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical | JUSTINC | JUSTINC | | XMS | P | 6069139 |
PEAK PROFESSIONAL CONTRS INC | XBS | T | 12/21/2018 | PAID (REC#1565425) PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Removed rating from clouded wall. Non-separated uses. | BPHILLIPS | BPHILLIPS | | XBS | T | 6060816 |