GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 08/20/2019 | all dampers installed and walls returned to existing fire or smoke ratings per plan at 5th floor | NATHAN | NATHAN | | B= | C | 6306960 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 04/16/2019 | damper framing at 5668 okay with completed required inspections. | NATHAN | NATHAN | | BFR | P | 6166749 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/22/2019 | | BRIAN | BRIAN | | E= | C | 6311372 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/22/2019 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 6311362 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/22/2019 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 6311360 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | R | 08/21/2019 | need to strap the mc / label the j box circuit # and what it serves / | BRIAN | BRIAN | | E= | R | 6309714 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 07/24/2019 | FIRE ALARM INSPECTION: electric for fire damp complete | CHIPO | CHIPO | | E= | C | 6274777 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 07/24/2019 | FIRE ALARM INSPECTION: complete for FA | CHIPO | CHIPO | | E= | C | 6274758 |
MECHONE, INC. | H= | C | 08/13/2019 | NO TAB REQUIRED | JERRYF | JERRYF | | H= | C | 6298084 |
MECHONE, INC. | H= | P | 08/12/2019 | PARTIAL PENDING : INSPECTION REQUEST BY MECHANICAL CONTRACTOR . | LIDO | LIDO | | H= | P | 6296429 |
MECHONE, INC. | H= | P | 07/26/2019 | THE REMAINING FIRE DAMPERS, ANGLES AND ACCESS DOORS OK . PARTIAL PENDING : FIRE DAMPERS INSTALLED IN ROOMS 5605, 5623 , 5625 INSTEAD IN OF FIRE/ SMOKE DAMPERS SHOWN ON PLANS.((NEED PLANS REVISED AND APPROVED FOR FIRE/ SMOKE DAMPERS CHANGED TO FIRE DAMPERS IN THE ROOMS LISTED .)) | LIDO | LIDO | | H= | P | 6278475 |
MECHONE, INC. | HD | P | 07/19/2019 | 1 - FIRE DAMPER FRAME IN FOR 12 X 10 DUCT IN ROOM # 5625 OK . | LIDO | LIDO | | HD | P | 6269726 |
MECHONE, INC. | HSP | P | 07/19/2019 | RECEIVED STAMPED ENGINEER LETTER AND DETAIL FOR SUPPORTING THE FIRE DAMPERS .THIS LETTER IS ADDING THE 16X12 DAMPER IN ROOM # 5625 TO THE STAMPED LETTER AND DETAIL ORIGINALLY RECEIVED ON 5/31/19 . | LIDO | LIDO | | HSP | P | 6269363 |
MECHONE, INC. | HD | P | 07/08/2019 | FIRE DAMPER FRAMING INSPECTION : ((ROOM # 5623 -10 X 10 SUPPLY FIRE DAMPER FRAME OK . COMMUNICATED BY CONTRACTOR A FIRE DAMPER IS BEING INSTALLED, PLANS SHOW THIS TO BE A FIRE/ SMOKE DAMPER .NEED PLANS REVISED AND APPROVED.)) ((36 X 12 TRANSFER AIR FIRE / SMOKE DAMPER FRAMING PER STAMPED LETTER AND DETAIL IN IMAGES OK / PLANS SHOW THIS DAMPER TO BE A FIRE SMOKE DAMPER , COMMUNICATED BY CONTRACTOR A FIRE DAMPER IS BEING INSTALLED / NEED PLANS REVISED AND APPROVED.)) ((ROOM # 5625 -16 X 12 FIRE DAMPER FOR DUCTED TRANSFER OPENING FRAMING IS NOT PER INSTALLATION INSTRUCTIONS. NEED STAMPED ENGINEER LETTER AND DETAIL DRAWING FOR THIS FRAMING. COMMUNICATED BY CONTRACTOR A FIRE DAMPER IS BEING INSTALLED, PLANS SHOW THIS TO BE A FIRE/ SMOKE DAMPER .NEED PLANS REVISED AND APPROVED.)) | LIDO | LIDO | | HD | P | 6255574 |
MECHONE, INC. | HD | P | 06/06/2019 | 18 X 12 DAMPER RETAINAGE AND ACCESS DOOR OK - STILL NEED LABEL | JERRYF | JERRYF | | HD | P | 6222888 |
MECHONE, INC. | HD | P | 06/04/2019 | FIRE DAMPER FRAMING OK AT 18 X 12 IN ROOM 5623 | JERRYF | JERRYF | | HD | P | 6219688 |
MECHONE, INC. | HSP | P | 05/31/2019 | DAMPER SUPPORT LETTER RECEIVED | JERRYF | JERRYF | | HSP | P | 6215492 |
MECHONE, INC. | HD | P | 05/23/2019 | STILL NEED DAMPER SUPPORT DETAIL FROM ENGINEER - THIS INSPECTION WAS FOR THE FOLLOWING - 40 X 20 FIRE DAMPER AND ACCESS DOOR IN ROOM 5605 - DAMPER GAP AND RETAINAGE OK | JERRYF | JERRYF | | HD | P | 6208907 |
MECHONE, INC. | HD | P | 05/17/2019 | THIS INSPECTION WAS ROOM 5605 - FRAMING OK AT ADDED 40 X 20 DAMPER NEED LETTER FROM ENGINEER FOR SUPPORT - 12 X 12 / 8 X 8 36 X 20 DAMPER GAP AND RETAINAGE OK - AT FUTURE INSPECTION VERIFY DUCT AND CEILING ACCESS DOORS AND LABELS | JERRYF | JERRYF | | HD | P | 6203097 |
MECHONE, INC. | HD | P | 05/06/2019 | THIS INSPECTION WAS FOR THE FOLLOWING - ROOM 5605 - NEED STRUCTURAL ENGINEERING DETAIL FOR SUPPORTING 36 X 10 DAMPER AND REVISE PLAN SHOWING THIS DAMPER - FRAMING OK FOR 8 X 8 AND 12 X 12 DAMPERS | JERRYF | JERRYF | | HD | P | 6188623 |
MECHONE, INC. | HD | P | 04/30/2019 | DAMPER FRAMING OK AT ROOM 5605 A - 12 X 10 | JERRYF | JERRYF | | HD | P | 6182761 |
MECHONE, INC. | HD | P | 04/22/2019 | ABOVE CEILING F/SD DAMPERS / RETAINAGE / ACCESS DOORS AND LABELS OK AT 24 X 12 AND 10 X 10 DAMPERS | JERRYF | JERRYF | | HD | P | 6174014 |
MECHONE, INC. | HD | P | 04/18/2019 | 24 X 12 AND 10 X 10 OPENING FOR 8" ROUND DAMPER FRAMING AT STORAGE ROOM 5606 ON PAGE M105-6 OK | JERRYF | JERRYF | | HD | P | 6170766 |
MECHONE, INC. | HSP | P | 04/17/2019 | AFTER CONSULT WITH CONTRACTOR / ENGINEER TO SUPPLY STAMPED LETTER ON COMPANY LETTER HEAD ADDRESSING CORRECTION OF KEY NOTES ON PLAN PAGE M105-6 | JERRYF | JERRYF | | HSP | P | 6168584 |
MECHONE, INC. | HD | P | 04/12/2019 | FIRE SMOKE DAMPER ACCESS DOOR / GAP AND RETAINAGE OK AT DAMPER MARKED ON APPROVED ONSITE PLANS PAGE 105.6 | JERRYF | JERRYF | | HD | P | 6164570 |
MECHONE, INC. | HD | P | 04/10/2019 | fire smoke damper framing ok on damper on approved plans page m105.6 | JERRYF | JERRYF | | HD | P | 6161829 |
MECHONE, INC. | XMS | T | 08/06/2019 | PAID (REC#1620046) PLAN SPLICE FEE: $50 by: SHANEN for Mechanical: clouded revisions only | SHANEN | SHANEN | | XMS | T | 6289622 |