GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 05/13/2020 | All other required Final inspections are complete. (This is a computer generated result) | DAKOTAB | DAKOTAB | | B= | C | 6569638 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/09/2020 | Building final for phase 1 OK pending other final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Mechanical Final Inspection is not Completed yet. | DAKOTAB | DAKOTAB | | B= | P | 6505014 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/25/2020 | Above lid at restroom 2249 and 2250 OK -- Door infill frame at 2 door in 2256 OK | DAKOTAB | DAKOTAB | | BFR | P | 6491875 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/18/2020 | Need to patch hole at fire barrier in ANTE 2269 -- Rest of Above lid inspection at 2nd floor area 122 OK | DAKOTAB | DAKOTAB | | BFR | P | 6485022 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/06/2020 | Gypsum attachment and firestopping at penetrations at restrooms 2249 and 2250 OK per UL U419 -- Training with Dave | DAKOTAB | DAKOTAB | | BSP | P | 6475866 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/06/2020 | Steel stud framing at 1hr fire barrier in room 2256, 2251, and 2258 OK per UL U419 - Interior light gauge framing in rooms 2251 and 2258 OK -- Training with Dave | DAKOTAB | DAKOTAB | | BFR | P | 6475859 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 01/28/2020 | Light gauge framing at 1 hr fire barrier wall at restroom 2249 and 2250 OK per UL U419 -- Light gauge framing at rear wall of compressor room 2260 OK | DAKOTAB | DAKOTAB | | BFR | P | 6466513 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 12/04/2019 | Firespray at slab edge in AHU 3038 OK | DAKOTAB | DAKOTAB | | BSP | P | 6416047 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 12/03/2019 | Mineral wool firestop at slab edge in at AHU 3038 OK -- Still need to inspect firespray at bottom track | DAKOTAB | DAKOTAB | | BSP | P | 6414760 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/27/2019 | Remainder of interior light gauge framing at area 122 OK pending other roughs | DAKOTAB | DAKOTAB | | BFR | P | 6411705 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 11/12/2019 | Fire spray at bottom track of trash room 2001 OK | DAKOTAB | DAKOTAB | | BSP | P | 6396184 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 11/08/2019 | Spray foam insulation at grid line 1 from grid line M to grid line W OK per detail | DAKOTAB | DAKOTAB | | BSP | P | 6393752 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 11/08/2019 | Mineral wool firestop at slab edge in trash room 2001 OK per engineer judgement recieved -- Still need to inspect firespray at bottom track | DAKOTAB | DAKOTAB | | BSP | P | 6393751 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/05/2019 | Interior light gauge framing at corridor wall 2294 down to door 2265 OK pending other roughs -- Interior light guage framing at trash room 2001 OK -- Still need to do above lid inspection in room 3038 and discussed engineer judgment at shaft infill in room 3038 per detail 2 on sheet A300 | DAKOTAB | DAKOTAB | | BFR | P | 6388848 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/30/2019 | Air handler 16 interior light gauge wall framing OK | DAKOTAB | DAKOTAB | | BFR | P | 6383649 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/25/2019 | Light gauge framed wall at corridor 2294 OK -- Reviewed upcoming inspections | DAKOTAB | DAKOTAB | | BFR | P | 6381146 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 09/25/2019 | partial framing for common 01 room interior framing and section of framing at corridor to outside of stairwell along matchline/framing is per plan | SCOTTS | SCOTTS | | BFR | P | 6347772 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 09/10/2019 | SPD wall framing is per plan and listing U419 | SCOTTS | SCOTTS | | BFR | P | 6330647 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/03/2019 | PHASE 1 FRAMING INSPECTION -- 2nd floor wall framing for smoke barrier per UL U419 along corridor 2600 at rooms 2601/2261A/framing per listing | SCOTTS | SCOTTS | | BFR | P | 6253434 |
ENCORE ELECTRIC, INC. | E= | C | 05/13/2020 | FIRE ALARM INSPECTION: | RANDY | RANDY | | E= | C | 6569637 |
ENCORE ELECTRIC, INC. | E= | C | 05/13/2020 | | RANDY | RANDY | | E= | C | 6569635 |
ENCORE ELECTRIC, INC. | E= | P | 03/09/2020 | phase 1 instrument storage-----phase 2 SPD | RANDY | RANDY | | E= | P | 6504872 |
ENCORE ELECTRIC, INC. | ER | P | 02/18/2020 | FIRE ALARM INSPECTION: FA with electric | RANDY | RANDY | | ER | P | 6485348 |
ENCORE ELECTRIC, INC. | ER | P | 02/18/2020 | sterile processing ceilings-----marked on plans | RANDY | RANDY | | ER | P | 6485136 |
ENCORE ELECTRIC, INC. | ER | P | 12/17/2019 | FIRE ALARM INSPECTION: FA wih electric | RANDY | RANDY | | ER | P | 6430400 |
ENCORE ELECTRIC, INC. | ER | P | 12/17/2019 | SPD sterile process ceiling marked on plans | RANDY | RANDY | | ER | P | 6430399 |
ENCORE ELECTRIC, INC. | ER | P | 10/09/2019 | SPD walls marked on plans | RANDY | RANDY | | ER | P | 6363915 |
ENCORE ELECTRIC, INC. | ER | P | 07/24/2019 | 2nd fl walls marked on plans | RANDY | RANDY | | ER | P | 6275716 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | C | 04/06/2020 | PHASE -1- MECHANICAL HEAT FINAL COMPLETE / ENGINEER STAMPED TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6531621 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 03/25/2020 | PHASE-1 : HYDRONIC ( HEAT WATER), HEAT FINAL OK . | LIDO | LIDO | | H= | C | 6520475 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 03/05/2020 | PHASE -1 - PARTIAL HEAT FINAL PENDING - NEED TEST AND BALANCE REPORT | LIDO | LIDO | | H= | P | 6501759 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 02/11/2020 | 2ND FLOOR MH-122 ( BDA 84) SUPPLY AIR FLEX CONNECTIONS TO GRILLS OK / 2 - SMOKE DAMPER LOCKED OPEN PER NOTE # 1 OK . | LIDO | LIDO | | HD | P | 6479555 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 12/16/2019 | 2ND FLOOR ( SPD ) MH-122 ( BDA 84) VESTIBULE ROOM # 2601 ONLY FINAL OK . | LIDO | LIDO | | HD | P | 6428340 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 12/09/2019 | 2ND FLOOR MH-122 ( BDA 84 SPLICE ) 1- DAMPER COMPLETE . | LIDO | LIDO | | HD | P | 6421643 |
OLSON PLUMBING & HEATING COMPANY | HWP | C | 10/23/2019 | 2ND FLOOR MP-122 ( BDA 33) ALL VAV HEAT WATER SUPPLY AND RETURN FINAL CONNECTIONS OK . | LIDO | LIDO | | HWP | C | 6378116 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 10/17/2019 | 2ND FLOOR MH-122 ( BDA 113 ) PER PLAN SPLICE DATED 9/18/19 THE TWO FIRE DAMPER INSPECTED PER NOTE - 11 WHERE DELETED - REMOVE DAMPERS PER PER PLAN SPLICE OR HAVE PLANS REVISED AND APPROVED SHOWING FIRE DAMPERS TO BE INSTALLED (TWO FIRE DAMPERS COMPLETE) | LIDO | LIDO | | HD | P | 6372526 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 10/10/2019 | 2ND FLOOR MH-122 ( BDA 113 ) PLAN SPLICE DATED 9/18/19 SHOWS 5- FIRE SMOKE DAMPER AND TWO FIRE DAMPER PER NOTE - 11 NOT REQUIRED / THE 5- FIRE SMOKE DAMPERS ARE ALREADY INSTALLED AND INSPECTED. 2- DAMPERS FRAMES INSPECTED ARE OK BUT THESE TWO FIRE DAMPERS ARE DELETED PER THE SPLICE PLAN . | LIDO | LIDO | | HD | P | 6365226 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 10/08/2019 | NEED FIELD CONSULT WITH MECHANICAL CONTRACTOR ABOUT DAMPER FRAMING. NOT READY | LIDO | LIDO | | HD | P | 6362287 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 10/06/2019 | (( PHASE -1)) ( HD ) DUCT ROUGH INSPECTIONS DONE ON PERMIT M34809 AND ON THIS PERMIT NUMBER. THERE ARE STILL INSPECTIONS REMAINING ON THIS PHASE-1 PERMIT. PLEASE CALL DUCT INSPECTIONS ON THIS PHASE -1 UNDER THIS PERMIT NUMBER WHEN READY. | LIDO | LIDO | | HD | P | 6359055 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 09/16/2019 | 2ND FLOOR MH-122 ( BDA 32) VAV-2-243 - LOW PRESSURE DUCT ROUGH AND SUPPLY BRANCHES OK/ OK TO WRAP. VAV-2-244 - LOW PRESSURE DUCT OK / OK TO WRAP. | LIDO | LIDO | | HD | P | 6336592 |
OLSON PLUMBING & HEATING COMPANY | HD | P | 08/16/2019 | 2nd FLOOR ( BDA 32) MH-122 : ((Note added 8/19/19 by LM. This inspection comment was copied to this permit by me on 8/19/19. Wrong permit called in by contractor. This comment is for this permit. 5- DAMPER FRAMES BY ELEVATOR OK .)) 5 - FIRE SMOKE DAMPERS COMPLETE . VAV-2-247, VAV-2-248 LOW PRESSURE DUCT OK / OK TO WRAP/STILL NEED VAV'S INSTALLED. | LIDO | LIDO | | HD | P | 6303662 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 08/15/2019 | 2ND FLOOR ( BDA 33) MP-122: VAV-2-247 / VAV-2-248 SUPPLY AND RETURN HEAT WATER PIPING UNDER OPERATING PRESSURE- NO VISIBLE LEAKS / INSTALLED PER PLAN / OK TO WRAP AND LABEL. STILL NEED FINAL CONNECTION TO VAV'S. | LIDO | LIDO | | HWP | P | 6302214 |
ENCORE ELECTRIC, INC. | XES | P | 09/18/2019 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Added temporary mobile equipment. | BERTHA | BERTHA | | XES | P | 6339092 |
OLSON PLUMBING & HEATING COMPANY | XMS | P | 09/18/2019 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Mechanical: changed smoke Dampers to Fire /smoke Dampers | TCRIPPEN | TCRIPPEN | | XMS | P | 6339038 |
OLSON PLUMBING & HEATING COMPANY | XPS | P | 09/13/2019 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: 9/13/19: Delta ASI-12 revisions PP101 key notes 1 - 7, PP112 DWV up to FS-1, PP122 water piping to FS-1 | SHANEN | SHANEN | | XPS | P | 6335186 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 09/11/2019 | PAID (REC#1630794) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Minor floor plan revisions | SHELLEY | SHELLEY | | XBS | T | 6331862 |
OLSON PLUMBING & HEATING COMPANY | XPS | P | 08/28/2019 | PLAN SPLICE FEE: $0 by: SHANEN for Plumbing: PLUMBING SPLICE 8/28/19: Delta ASI-09 revisions PP121 Reconfigure men's room, remove restroom, change women's restroom lav to L-2, P600 adjusted fixture schedule | SHANEN | SHANEN | | XPS | P | 6317681 |
OLSON PLUMBING & HEATING COMPANY | XMS | P | 08/28/2019 | PLAN SPLICE FEE: $0 by: JUSTINC for Mechanical: Revised to change restroom into nurse station and delete supply air | JUSTINC | JUSTINC | | XMS | P | 6317240 |
ENCORE ELECTRIC, INC. | XES | T | 08/28/2019 | PAID (REC#1630202) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised for background change. Added card readers. | BERTHA | BERTHA | | XES | T | 6316836 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 08/22/2019 | PAID (REC#1627026) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add wall assembly - revise layout some location - | MICHAELA | MICHAELA | | XBS | T | 6310046 |