BALDWIN ENTERPRISES | B= | C | 11/14/2019 | | TIMOTHYS | TIMOTHYS | | B= | C | 6399841 |
BALDWIN ENTERPRISES | B= | P | 11/06/2019 | Seal hole over shower - Per sheet A2 Door D1 (Accessible entrance) to have single action hardware and key operated deadbolt with signage that reads "This door to remain unlocked when occupied" - Per sheet A2 Door D2 to have single action hardware and key operated deadbolt - Per sheet A2 all D3 doors to have single action hardware and no keyed bolt -- Schedule a new Building Final when above items are complete. | TIMOTHYS | TIMOTHYS | | B= | P | 6390699 |
BALDWIN ENTERPRISES | BIN | C | 10/07/2019 | 5/8" rock and attachments at interior of U379 assembly ok - Insulation ok | TIMOTHYS | TIMOTHYS | | BIN | C | 6360354 |
BALDWIN ENTERPRISES | BFR | P | 10/01/2019 | 2nd layer type x rock ok above ceiling at U379 assembly - 2nd layer type x rock ok at rim at U379 assembly - U379 insulated - Need to see Type x rock interior side U379 assembly to complete frame - Other items corrected | TIMOTHYS | TIMOTHYS | | BFR | P | 6353884 |
BALDWIN ENTERPRISES | BFR | P | 09/25/2019 | First layer of 5/8 gyp above trusses at U379 wall ok - First layer of 5/8 gyp at rim in crawlspace at U379 wall ok - Exterior 5/8 gyp at exterior portion of U379 wall ok - Need to complete draftstop throughout - Other items from previous BFR complete - Complete reinspection done | TIMOTHYS | TIMOTHYS | | BFR | P | 6347680 |
BALDWIN ENTERPRISES | BFN | C | 09/20/2019 | Foundation reinforcement observation received - foundation design already on file. | CHUCK | CHUCK | | BFN | C | 6343508 |
BALDWIN ENTERPRISES | BFT | C | 09/20/2019 | Open ex. and footing observation received - soils report already on file - 1000# (design verified) / 5% / no drain required. | CHUCK | CHUCK | | BFT | C | 6343505 |
BALDWIN ENTERPRISES | BFR | R | 09/20/2019 | Many items from previous inspection not addressed / Received updated truss packet - trusses OK. | CHUCK | CHUCK | | BFR | R | 6343503 |
BALDWIN ENTERPRISES | BFR | R | 09/06/2019 | missing roof jacks / trusses do not match truss details / west wall is rated for proximity to lot line and is to be built per the UL U379 / need studs 16" OC need all pre rock above trusses to have joints backed and rock not attached per listed assembly / rock at exterior of assembly is covered with siding with no inspection / rock needs to extend through sub-floor to foundation / interior non-bearing walls not installed per listing to stop and start rock / all joists ae in contact with foundation as they were attached to the mud set sill plate and there was not another one added on top / all work at existing portion of building where addition is connected can not be seen at this time / discussed accessible elements / need all engineer observations for footing and foundation and open hole to complete BFT and BFN / porch on north side need to nail off concealed flange hangers at beams / need complete reinspection | DANE | DANE | | BFR | R | 6327485 |
INTERMOUNTAIN POWER SERVICES INC | E= | C | 10/31/2019 | | TOMC | TOMC | | E= | C | 6384621 |
INTERMOUNTAIN POWER SERVICES INC | EP | C | 08/28/2019 | 100 amp sub-panel change out | TOMC | TOMC | | EP | C | 6316957 |
INTERMOUNTAIN POWER SERVICES INC | ER | C | 08/28/2019 | walls and ceiling , Discussed accessibility requirements with contractor / | TOMC | TOMC | | ER | C | 6316956 |
ASPEN VIEW MECHANICAL LLC | H= | C | 11/06/2019 | REVISED TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6389692 |
ASPEN VIEW MECHANICAL LLC | H= | P | 11/05/2019 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. TEST AND BALANCE REPORT NEEDS TO SHOW EACH SUPPLY SEPARATELY, NOT BY ROOM. READINGS ON TEST AND BALANCE REPORT NEED TO BE WITHIN +/- 10% OF DESIGN AND MULTIPLE READINGS ARE OUTSIDE OF +/- 10%. NEED REVISED TEST AND BALANCE REPORT OR ENGINEER APPROVAL OF READINGS. | DUSTINS | DUSTINS | | H= | P | 6388034 |
ASPEN VIEW MECHANICAL LLC | H= | P | 11/01/2019 | MECHANICAL FINAL PENDING TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6385637 |
PEAK VIEW PLUMBING, INC. | H= | C | 10/25/2019 | GAS FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6380459 |
PEAK VIEW PLUMBING, INC. | HC | C | 10/25/2019 | ADDING 40K TO EXISTING LOAD. | DUSTINS | DUSTINS | | HC | C | 6380456 |
PEAK VIEW PLUMBING, INC. | HI | C | 10/25/2019 | ALL GAS PIPING OK. | DUSTINS | DUSTINS | | HI | C | 6380451 |
ASPEN VIEW MECHANICAL LLC | H= | P | 10/23/2019 | STILL NEED CONTRACTOR TO CORRECT SCOPE OF WORK TO CLAIM FURNACE, VENT, EXHAUST FAN, CONDENSER. STILL NEED TO PROPERLY SUPPORT THE FURNACE PER MANUFACTURERS INSTALLATION INSTRUCTIONS AND HAVE INSTALL MANUAL ON SITE AT NEXT INSPECTION. INSTALL GROMMET FOR GAS PIPING ENTERING FURNACE CABINET. INSTALL REGISTER IN CRAWLSPACE FOR THE CONDITIONED CRAWLSPACE. LOWER THERMOSTAT TO NO HIGHER THAN 48" ABOVE FINISHED FLOOR OR INSTALL LOCK BOX. PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6377612 |
PEAK VIEW PLUMBING, INC. | HI | P | 09/25/2019 | CSST INSULATION SLEEVE IS STRIPED BACK TOO FAR AT THE CONNECTION BY THE FURNACE / REFER TO THE INSTALL INSTRUCTIONS TABLE 4-3 PAGE # 27. PROPERLY SUPPORT CSST ABOVE FURNACE . | LIDO | LIDO | | HI | P | 6347581 |
ASPEN VIEW MECHANICAL LLC | HD | P | 09/25/2019 | CONTRACTOR TO ADD TO THERE SCOPE OF WORK 1- FURNACE , 1- EXHAUST FAN ,1- VENT AND 1- CONDENSER . PROPERLY SUPPORT FURNACE PER THE MANUFACTURER . CONDITION CRAWL SPACE. INSTALL RUBBER COUPLER FOR VENT CONNECTION AT FURNACE PER THE MANUFACTURER. INLET PLATE AT THE FURNACE IS CRACKED , THIS WILL NEED TO BE REPLACED. INSTALL GROMMET FOR GAS PIPE PENETRATION INTO THE FURNACE CABINET. CONCENTRIC TERMINATION ON ROOF OK. | LIDO | LIDO | | HD | P | 6347580 |
ASPEN VIEW MECHANICAL LLC | HV | C | 08/26/2019 | FURNACE VENT OK. NEED PROPER TERMINATION BY FINAL. | DUSTINS | DUSTINS | | HV | C | 6313808 |
ASPEN VIEW MECHANICAL LLC | HD | P | 08/26/2019 | NEED ELECTRICAL CONTRACTOR TO ATTACH TO PERMIT. ALL SUPPLY/RETURN AIR DUCTS IN CRAWLSPACE OK, OK TO WRAP. EXHAUST FAN AND DUCT OK. | DUSTINS | DUSTINS | | HD | P | 6313803 |
PEAK VIEW PLUMBING, INC. | HI | P | 08/22/2019 | NEED MECHANICAL AND ELECTRICAL CONTRACTORS TO ATTACH TO PERMIT. NEED REVISED/APPROVED PLANS MATCHING INSTALL ON SITE. PLANS CALL FOR ALL GAS PIPING TO BE MEDIUM PRESSURE WITH REGULATORS AT EACH APPLIANCE AND THERE IS ONE REGULATOR AT EXTERIOR WITH ALL INSIDE GAS PIPING AS LOW PRESSURE. PLANS CALL FOR 1/2" TIE IN TO NEW FURNACE AND CSST EHD 25 INSTALLED TO NEW FURNACE. CAN NOT COMPLETE HI INSPECTION UNTIL PLANS HAVE BEEN REVISED/APPROVED. 10 LB TEST OK. | DUSTINS | DUSTINS | | HI | P | 6310177 |
PEAK VIEW PLUMBING, INC. | P= | C | 10/31/2019 | | TAYLOR | TAYLOR | | P= | C | 6384757 |
PEAK VIEW PLUMBING, INC. | P= | P | 10/25/2019 | need shutoff at hand held for shower and power supply for recirc pump, rest ok, | TAYLOR | TAYLOR | | P= | P | 6380635 |
PEAK VIEW PLUMBING, INC. | PTO | C | 09/05/2019 | check backwater valve in crawl space and recirc pump by final. | TAYLOR | TAYLOR | | PTO | C | 6325308 |
PEAK VIEW PLUMBING, INC. | PTO | L | 08/22/2019 | field cancelled. | TAYLOR | TAYLOR | | PTO | L | 6311253 |
PEAK VIEW PLUMBING, INC. | PB | C | 08/01/2019 | **LOCAL WASTE WATER DEPT to check outside structure bldg drain / cleanouts**
need to revise plans to show new 3" drain with **seperate tie in outside the structure** in lieu of inside existing structure bldg drain tie in, rest ok | JOHNS | JOHNS | | PB | C | 6285093 |
BALDWIN ENTERPRISES | XBS | T | 09/18/2019 | PAID (REC#1631475) PLAN SPLICE FEE: $50 by: DANM for Construction: Listed assemblies provided for 1-hr fire-resistance-rated exterior wall | DANM | DANM | | XBS | T | 6340008 |
PEAK VIEW PLUMBING, INC. | XMS | T | 08/29/2019 | PAID (REC#1627381) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice see sheet notes using CSST gas pipe | TCRIPPEN | TCRIPPEN | | XMS | T | 6318486 |
PEAK VIEW PLUMBING, INC. | XPS | P | 08/29/2019 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: 8/29/19: Delta 1 revisions reroute 3" drain to outside POC | SHANEN | SHANEN | | XPS | P | 6318442 |
INTERMOUNTAIN POWER SERVICES INC | XES | P | 08/29/2019 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised one-line to include combiner. | BERTHA | BERTHA | | XES | P | 6318409 |