PRO.COM HOME SERVICES COLORADO, INC. | BSP | P | 04/16/2020 | Rock and rock attachment at 1hr fire resistance rated walls ok all rooms and hallway, both sides | TIMOTHYS | TIMOTHYS | | BSP | P | 6542943 |
PRO.COM HOME SERVICES COLORADO, INC. | BFR | P | 04/16/2020 | Top of wall bracing ok / Light gauge steel framing for hallway lid ok | TIMOTHYS | TIMOTHYS | | BFR | P | 6542938 |
PRO.COM HOME SERVICES COLORADO, INC. | BIN | C | 04/03/2020 | | TIMOTHYS | TIMOTHYS | | BIN | C | 6531348 |
PRO.COM HOME SERVICES COLORADO, INC. | BFR | P | 04/03/2020 | Missing diagonal braces at top of walls 48oc many locations / Rest of light gauge steel framing ok | TIMOTHYS | TIMOTHYS | | BFR | P | 6531339 |
JLC ELECTRIC LLC | E= | C | 06/01/2020 | | BRETC | BRETC | | E= | C | 6589047 |
JLC ELECTRIC LLC | E= | P | 05/28/2020 | need to move 2 gfci receptacles from behind washer / Label everthing, Panels and ciruits / Change MUA grounding, look at MAU jbox in ceiling / Label MUA at disconnect / | BRETC | BRETC | | E= | P | 6585693 |
JLC ELECTRIC LLC | ER | C | 05/27/2020 | | JOHNN | JOHNN | | ER | C | 6584460 |
JLC ELECTRIC LLC | ER | P | 03/20/2020 | Three switches in hallway need to drop 48" to top / will look at on final / ok to sheet rock | BRETC | BRETC | | ER | P | 6517370 |
JLC ELECTRIC LLC | ER | R | 03/16/2020 | All switches need to be 48" to top (ADA) / back left room missing mud ring. | BRETC | BRETC | | ER | R | 6511374 |
JACKS OF ALL TRADES, INC. | H= | C | 06/19/2020 | AFTER FURTHER REVIEW TAB REPORT IS OK | JERRYF | JERRYF | | H= | C | 6610248 |
JACKS OF ALL TRADES, INC. | H= | P | 06/18/2020 | NEED TO REVIEW TAB REPORT WITH SENIOR INSPECTOR MAY NEED TO PROVIDE CERTIFIED TAB REPORT - MORE NOTES TO FOLLOW ON 6 / 19 NOTES ; ROOF / GRILLES AND CONTROLS OK / | JERRYF | JERRYF | | H= | P | 6609871 |
JACKS OF ALL TRADES, INC. | H= | L | 06/17/2020 | CANCELED AT CALL AHEAD - RESCHEDULED FOR 6/18 WITH CALL AHEAD | JERRYF | JERRYF | | H= | L | 6608162 |
JACKS OF ALL TRADES, INC. | H= | L | 06/15/2020 | CALLED CONTACT NO ANSWER NO MAIL BOX SET UP | DAVIDH | DAVIDH | | H= | L | 6604911 |
JACKS OF ALL TRADES, INC. | H= | L | 06/12/2020 | FIELD CANCELLED BY CONTRACTOR | BENH | BENH | | H= | L | 6603109 |
JACKS OF ALL TRADES, INC. | HD | P | 12/20/2019 | DRYER VENT OK | JERRYF | JERRYF | | HD | P | 6434537 |
JACKS OF ALL TRADES, INC. | HD | P | 12/19/2019 | NEED TO ADD DRYER VENT TO PERMIT WORK SCOPE - STILL NEED THE FOLLOWING - DRYER VENT INSPECTION / ROOF INSPECTION EQUIPMENT NOT INSTALLED YET. NOTES: ABOVE CEILING SA / EXHAUST MAINS AND RUN OUTS OK | JERRYF | JERRYF | | HD | P | 6433108 |
GOLD RUSH PLUMBING | P= | C | 06/26/2020 | | SAMH | SAMH | | P= | C | 6619175 |
GOLD RUSH PLUMBING | P= | P | 06/19/2020 | Complete mechanical room insulation. | SAMH | SAMH | | P= | P | 6610813 |
GOLD RUSH PLUMBING | PTO | C | 04/03/2020 | Check ceiling insulation and Water heater at final. | SAMH | SAMH | | PTO | C | 6531029 |
GOLD RUSH PLUMBING | PTO | P | 03/19/2020 | Rooms 103, 105, 107, 109, 111, 113, 115 complete. | SAMH | SAMH | | PTO | P | 6516212 |
GOLD RUSH PLUMBING | PB | C | 11/05/2019 | | SAMH | SAMH | | PB | C | 6388326 |
PRO.COM HOME SERVICES COLORADO, INC. | XMS | T | 11/14/2019 | PAID (REC#1644438) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice pages changed room names removed exhaust system for nails | TCRIPPEN | TCRIPPEN | | XMS | T | 6399069 |
PRO.COM HOME SERVICES COLORADO, INC. | XES | P | 11/06/2019 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Add MAU | SHELBY | SHELBY | | XES | P | 6389932 |
GOLD RUSH PLUMBING | XPS | P | 11/06/2019 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: 11/06/19: Delta R1 revisions P1 revised plumbing plan, P3 revised water isometric | SHANEN | SHANEN | | XPS | P | 6389880 |