HOMEOWNER | B= | C | 06/21/2021 | Item corrected | CHAD | CHAD | | B= | C | 7009331 |
HOMEOWNER | BE | C | 05/19/2021 | | VERONIKAP | VERONIKAP | | BE | C | 6974329 |
HOMEOWNER | B= | R | 11/30/2020 | Window added to bedroom not shown on plans, Splice required, please submit splice for changes in scope. If unfamiliar in submitting electronic splice, please click the following link: https://youtu.be/dG3kHpgDP0w / Net height of new egress window can only be opened 19 1/2 inches, Net clearance height of egress is to be 24 inches / Other bedroom window dimensions have not changed | TRENTP | TRENTP | | B= | R | 6790659 |
HOMEOWNER | B= | R | 11/16/2020 | Egress window and sill in bedroom still does not meet code per previous inspection / Drain and framing okay per engineer letters on file. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | TRENTP | TRENTP | | B= | R | 6777582 |
HOMEOWNER | B= | R | 10/27/2020 | Still need open hole report to clarify if perimeter drain is required / Inspector is unable to confirm if interior walls are floating per code / Window sill in bedroom measure 49 1/2 inches in height, max height per code is 44 inches / Egress window in bedroom only open 14 1/2 inches wide, minimum net clear width for egress window is 20 inches / Slab on grade, no deck. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | TRENTP | TRENTP | | B= | R | 6755340 |
HOMEOWNER | BE | C | 07/27/2020 | | JANE | JANE | | BE | C | 6650970 |
HOMEOWNER | BFD | P | 02/10/2020 | need open hole to verify that no perimeter drain is required per soils report | DANE | DANE | | BFD | P | 6477508 |
HOMEOWNER | BFN | C | 02/10/2020 | Engineer letter for foundation received / open hole received / bearing capacity verified | DANE | DANE | | BFN | C | 6477501 |
HOMEOWNER | E= | C | 08/14/2020 | | TOMC | TOMC | | E= | C | 6672948 |
HOMEOWNER | ES | C | 08/14/2020 | Residential Underground: 100-amp 3 wire service upgrade, no action required by utlity. / | TOMC | TOMC | | ES | C | 6672942 |
HOMEOWNER | ES | R | 08/06/2020 | pot hole underground in 3 location 1 at back of house, 1 10 from meter and 1 in between, expose ground rods or ufer | BRET | BRET | | ES | R | 6663179 |
HOMEOWNER | ES | R | 08/06/2020 | pot hole underground in 3 location 1 at back of house, 1 10 from meter and 1 in between, expose ground rods or ufer | BRET | BRET | | ES | R | 6663180 |
HOMEOWNER | E= | R | 08/06/2020 | install box extensions on exterior front and microwave receptacle, ground wire to all switches, missinr under cab lights right and left of range, afci protection required for all circuits except range, dyer, water heater,bath and furnace. install gfci /afci breaker for washer and dish, disposal receptacle. install bushing and ground metal box and vanity lighting outlet install bushing on bath fan. expose ground rods or ufer connection, install gfci protect receptacle back of home, install intersystem bond terminal . remove inter can of recessed light fixtures at 3 locations, over sink, living room and one in bedroom. it is ok to put receptacles back in boxes. | BRET | BRET | | E= | R | 6663168 |
HOMEOWNER | E= | R | 08/06/2020 | install box extensions on exterior front and microwave receptacle, ground wire to all switches, missinr under cab lights right and left of range, afci protection required for all circuits except range, dyer, water heater,bath and furnace. install gfci /afci breaker for washer and dish, disposal receptacle. install bushing and ground metal box and vanity lighting outlet install bushing on bath fan. expose ground rods or ufer connection, install gfci protect receptacle back of home, install intersystem bond terminal . remove inter can of recessed light fixtures at 3 locations, over sink, living room and one in bedroom. it is ok to put receptacles back in boxes. | BRET | BRET | | E= | R | 6663169 |
HOMEOWNER | ER | C | 08/06/2020 | | BRET | BRET | | ER | C | 6663142 |
HOMEOWNER | ER | C | 08/06/2020 | | BRET | BRET | | ER | C | 6663143 |
HOMEOWNER | H= | C | 09/22/2020 | NOTE / DIRECT VENT FURNACE / ELECTRIC WATER HEATER / | TREVORH | TREVORH | | H= | C | 6714898 |
HOMEOWNER | HO | C | 09/22/2020 | (LP SYSTEM) 10 LB TEST OK FOR 27' OF 1/2'' POLY WITH TRACER WIRE FROM TANK TO REGULATOR AT HOUSE. | TREVORH | TREVORH | | HO | C | 6714884 |
HOMEOWNER | HI | C | 09/22/2020 | 10 LB TEST 3/4'' MAIN / 1 FURNACE / | TREVORH | TREVORH | | HI | C | 6714881 |
HOMEOWNER | HI | P | 09/10/2020 | WILL NEED A 10 LB PRESSURE TEST FOR GAS LINE INSIDE HOME, AND A 10 LB TEST FOR YARD LINE FROM TANK TO THE RISER AT HOUSE. | TREVORH | TREVORH | | HI | P | 6701824 |
HOMEOWNER | H= | P | 09/10/2020 | NEED FURNACE INSTALLATION INSTRUCTIONS ON SITE, CONDENSATE DRAIN LINE REQUIRES TRAP. NOTE / DIRECT VENT FURNACE / ELECTRIC WATER HEATER / | TREVORH | TREVORH | | H= | P | 6701785 |
HOMEOWNER | HRR | C | 09/10/2020 | NOTE / DIRECT VENT FURNACE / ELECTRIC WATER HEATER / | TREVORH | TREVORH | | HRR | C | 6701781 |
HOMEOWNER | P= | C | 10/22/2020 | Potable water certificate received | MALYNDA | MALYNDA | | P= | C | 6750652 |
HOMEOWNER | P= | P | 10/09/2020 | Video of sewer line reviewed and ok
| MALYNDA | MALYNDA | | P= | P | 6736372 |
HOMEOWNER | PWO | C | 10/09/2020 | pictures and on-site inspection completed Note: need potable water certificate | MALYNDA | MALYNDA | | PWO | C | 6736017 |
HOMEOWNER | P= | P | 10/09/2020 | Unable to view video of sewer scope, need potable water certificate, rest ok Note: no irrigation | MALYNDA | MALYNDA | | P= | P | 6735990 |
HOMEOWNER | P= | P | 09/24/2020 | | MALYNDA | MALYNDA | | P= | P | 6717963 |
HOMEOWNER | PTO | P | 09/24/2020 | *Missing hammer arrestors at kitchen sink and washer box *Need clarification on how bathroom and laundry were vented, need aav at kitchen sink *Need to scope sewer line under slab *Need to see water lines above water heater in attic (freeze protected?) *Need to see water/dwv stubs under kitchen and bathroom sinks | MALYNDA | MALYNDA | | PTO | P | 6717962 |
HOMEOWNER | XBS | T | 02/08/2021 | PAID (REC#1774178) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add window | MICHAELA | MICHAELA | | XBS | T | 6863083 |