BRECKENRIDGE CONSTRUCTION LLC | B= | C | 06/09/2020 | | LONNYS | LONNYS | | B= | C | 6598439 |
BRECKENRIDGE CONSTRUCTION LLC | BE | T | 05/05/2020 | PAID (REC#1678176): TCO fee | JANE | JANE | | BE | T | 6560574 |
BRECKENRIDGE CONSTRUCTION LLC | B= | P | 05/05/2020 | Temp CO: Need Mech. ( Expires: 6/4/2020 12:00:00 AM) | JANE | JANE | | B= | P | 6560571 |
BRECKENRIDGE CONSTRUCTION LLC | B= | P | 04/30/2020 | pending completion of other required inspections, building okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), MECHANICAL SYSTEMS OF COLORADO. CORP Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 6556498 |
BRECKENRIDGE CONSTRUCTION LLC | BFR | P | 03/25/2020 | Need Eng for floor in fills / Need to attach mechanical permit / Need all MEP's complete / All other interior framing OK / Reviewed accessible elements | NICK | NICK | | BFR | P | 6520852 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | C | 04/29/2020 | | CRAIGS | CRAIGS | | E= | C | 6555467 |
FOUNDERS FIRE AND ELECTRIC LLC | E= | C | 04/21/2020 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 6546439 |
FOUNDERS FIRE AND ELECTRIC LLC | ER | C | 04/21/2020 | FIRE ALARM INSPECTION: upper level OK | CRAIGS | CRAIGS | | ER | C | 6546437 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ER | C | 03/25/2020 | the gc tells me no fire alarm , it's sprinkler supervised | CRAIGS | CRAIGS | | ER | C | 6521559 |
MECHANICAL SYSTEMS OF COLORADO. CORP | H= | C | 05/28/2020 | Corrections made | MARKB | MARKB | | H= | C | 6585342 |
MECHANICAL SYSTEMS OF COLORADO. CORP | H= | P | 05/01/2020 | FINAL PENDING - Correct permit scope, Plan splice for removing EF-3 fan. | MARKB | MARKB | | H= | P | 6559072 |
MECHANICAL SYSTEMS OF COLORADO. CORP | H= | P | 04/29/2020 | FINAL PENDING - Correct permit scope, Plan splice for removing EF-3 fan. OTHER ITEMS ADDRESSED - TEST AND BALANCE REPORT RECEIVED, CONDENSATE PIPING AND SECONDARY PROTECTION COMPLETE, SUPPORT FOR BATH EXHAUST DUCT OK AND CONDENSERS MOVED APART FROM EACH OTHER. AMERICAN STANDARD EQUIPMENT IS SAME AS TRANE LISTED IN SCHEDULE. | MARKB | MARKB | | H= | P | 6555349 |
MECHANICAL SYSTEMS OF COLORADO. CORP | HD | P | 04/24/2020 | ----ENGINEER TO ADDRESS: Removal of economizers from units (still have outside air), revise equipment schedule with equipment used---- ----Will need a letter from condenser manufacture stating distance between condensers is OK---- Contractor to correct permit scope - replace 4 furnaces with 4 fan coil units. ABOVE CEILING DUCT - SUPPLY/RETURN/OUTSIDE AIR/EXHAUST, MAINS/BRANCHES/DIFFUSERS FOR ALL 4 FAN COIL UNITS COMPLETE EXCEPT need proper support on bath exhaust. Still need to complete condensate disposal and linesets. Provide test and balance report. | MARKB | MARKB | | HD | P | 6551728 |
AIM'S PLUMBING LLC | P= | C | 04/28/2020 | | JOSEPHD | JOSEPHD | | P= | C | 6553531 |
AIM'S PLUMBING LLC | PTO | C | 04/23/2020 | correction made note: check water heater at final, aav @ breakroom sink | JOSEPHD | JOSEPHD | | PTO | C | 6549181 |
AIM'S PLUMBING LLC | PTO | P | 04/13/2020 | cold water under sized, other corrections made | JOSEPHD | JOSEPHD | | PTO | P | 6538458 |
AIM'S PLUMBING LLC | PTO | P | 03/25/2020 | plans do not match work done, only called for new water piping to new sinks, need to splice changes at new water piping to all bathrooms, plans call for re-circ line, will need to remove existing bathroom from room 120 from plans, need to add aav at breakroom to plans or get engineer letter for it, ok for in-walls at sinks and drinking fountain note: AM&M for drinking fountain in images | JOSEPHD | JOSEPHD | | PTO | P | 6520842 |
MECHANICAL SYSTEMS OF COLORADO. CORP | XMS | T | 05/27/2020 | PAID (REC#1683470): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: New splice remove exhaust fan, | TCRIPPEN | TCRIPPEN | | XMS | T | 6583993 |
AIM'S PLUMBING LLC | XPS | P | 04/17/2020 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Delta 3 revisions: P3.0 adjusted level 2 plumbing plan | SHANEN | SHANEN | | XPS | P | 6543555 |
AIM'S PLUMBING LLC | XPS | T | 04/09/2020 | PAID (REC#1673109): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: P1.2 adjusted plumbing fixture schedule and sink with dishwasher standpipe diagram, P3.0 adjusted level 2 plumbing plan and drawing note 9 | SHANEN | SHANEN | | XPS | T | 6536607 |