BRYAN CONSTRUCTION, INC. | B= | C | 01/12/2021 | All other required Final inspections are complete. (This is a computer generated result) | ADAML | ADAML | | B= | C | 6833449 |
BRYAN CONSTRUCTION, INC. | B= | P | 12/18/2020 | Final items complete pending all other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, HARMON-BONDED PLUMBING & HEATING INC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 6813592 |
BRYAN CONSTRUCTION, INC. | BFR | P | 10/28/2020 | Attach mechanical permit and complete mechanical rough inspection / Light gauge steel framing at all partition walls ok / RC at sound walls ok / Infill at bay door ok / Frame complete pending other rough inspections | TIMOTHYS | TIMOTHYS | | BFR | P | 6757043 |
BIBLE ELECTRIC, INC. | E= | C | 12/17/2020 | Corrections made | BRETC | BRETC | | E= | C | 6812003 |
BIBLE ELECTRIC, INC. | E= | P | 12/15/2020 | Label mini split in panel / RTU-35 will need a fusible disconnect 15 amp or change brkr to 15 amps / Label RTU-35 in panel / Back area - Ok | BRETC | BRETC | | E= | P | 6808108 |
BIBLE ELECTRIC, INC. | ER | C | 12/15/2020 | Back ceiling - Ok | BRETC | BRETC | | ER | C | 6808101 |
BIBLE ELECTRIC, INC. | E= | P | 12/10/2020 | Check mini split and RTU on roof / Check back room receptacles | BRETC | BRETC | | E= | P | 6803698 |
BIBLE ELECTRIC, INC. | ER | P | 12/10/2020 | Front Ceilings - Ok / Check back ceiling | BRETC | BRETC | | ER | P | 6803695 |
COLORADO ELECTRICAL SYSTEMS, LLC | E= | C | 12/08/2020 | FIRE ALARM INSPECTION: | BRETC | BRETC | | E= | C | 6800157 |
COLORADO ELECTRICAL SYSTEMS, LLC | ER | C | 12/08/2020 | FIRE ALARM INSPECTION: All devices walls and ceiling rough - Ok | BRETC | BRETC | | ER | C | 6800155 |
BIBLE ELECTRIC, INC. | ER | P | 10/28/2020 | Walls only - Ok / There will be areas of wall that will be surface mounted receptacles / Discussed accessibility requirements with contractor / Discussed Conference rm requirements with contractor / | BRETC | BRETC | | ER | P | 6756285 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 01/06/2021 | CORRECTIONS MADE SEE IMAGES | JERRYF | JERRYF | | H= | C | 6826427 |
COLORADO SHEET METAL CO., INC. | H= | C | 12/21/2020 | TAB REPORT RECEIVED, SEE IMAGES | BENH | BENH | | H= | C | 6814411 |
HARMON - BONDED PLUMBING & HEATING, INC. | HSP | P | 12/11/2020 | DRAINS HAVE BEEN ADDED TO PERMIT AND HAVE BEEN PROTECTED IN RA PLENUM - STILL NEED OTHER NOTES ADDRESSED | JERRYF | JERRYF | | HSP | P | 6804847 |
COLORADO SHEET METAL CO., INC. | H= | P | 12/11/2020 | NEED TAB REPORT NOTES: ALL SA / RA GRILLES / CONTROLS / DRAINS / ROOF OK | JERRYF | JERRYF | | H= | P | 6804822 |
HARMON - BONDED PLUMBING & HEATING, INC. | HRP | P | 12/07/2020 | NEED TO PROTECT VINYL TUBING IN RETURN AIR PLENUM OR RUN PROPER MATERIAL (CONTRACTOR TO SUPPLY PICTURES OF CORRECTIONS) TO INSPECTION REQUEST | JERRYF | JERRYF | | HRP | P | 6798313 |
COLORADO SHEET METAL CO., INC. | HSP | P | 12/07/2020 | NEED TO LABEL CONDENSER ON ROOF BY FINAL - STILL NEED ALL OTHER INSPECTIONS | JERRYF | JERRYF | | HSP | P | 6798300 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | P | 12/07/2020 | PARTIAL PENDING PLAN REVISING DELETING MEDIUM PRESSURE SYSTEM ON PLAN BEFORE METER RELEASE NOTES: PRESSURE TEST OK AND PIPING PER PLAN | JERRYF | JERRYF | | HI | P | 6798296 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/19/2020 | NEED CONTRACTOR INSTALLING GAS LINE TO ATTACH TO PERMIT, AND PLUMBING CONTRACTOR TO ATTACH TO PERMIT, ALL ABOVE CEILING DUCT AND MAN BARS WITH ACCESS DOORS OK, NEEDED FOR FINAL: SEAL LAG BOLTS TO CURB ON ROOF FOR CONDENSER, MINI SPLIT COMPLETED,NEED CONDENSATE COMPLETED ON ROOF FOR RTU AND SECONDARY PROTECTION INSTALLED IN RTU, NEED THERMOSTATS MOUNTED AND TAB REPORT | BENH | BENH | | HD | P | 6783016 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/03/2020 | INSPECTION TODAY WAS FOR LATERAL SUPPLYS ABOVE CEILING, OK TO INSULATE, NO ROOF TODAY, STILL NEED TO SEE MINI SPLIT INSTALLED AND CONDENSATE DRAIN COMPLETED, RELOCATED THERMOSTATS TO BE NO HIGHER THAN 48" TO TOP OR PROVIDE LOCK BOXES, NEED MAN BARS INSTALLED AT ALL LOCATIONS WITH ACCESS DOORS INSTALLED IN DUCT | BENH | BENH | | HD | P | 6763449 |
COLORADO SHEET METAL CO., INC. | XMS | T | 01/05/2021 | PAID (REC#1918147): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds | DALEH | DALEH | | XMS | T | 6825029 |