GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 12/01/2021 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 7194414 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 08/05/2021 | pending completion of mech and elec finals, building okay. Additional Inspections Required (computer generated): COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 7061651 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/18/2021 | Wall and soffit framing per plans with completed required inspections room 3067, 3070 | NATHAN | NATHAN | | BFR | P | 7007484 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/20/2021 | Wall frame at 3070 to back of staff toilet 3072 only per U 415 USG coreboard . | NATHAN | NATHAN | | BFR | P | 6976198 |
ENCORE ELECTRIC, INC. | E= | C | 11/16/2021 | | CRAIGS | CRAIGS | | E= | C | 7178250 |
ENCORE ELECTRIC, INC. | ER | P | 07/29/2021 | Above ceilings okay except 12 x 12 lighting j-box still needs make up | CHIPO | CHIPO | | ER | P | 7053566 |
ENCORE ELECTRIC, INC. | ER | P | 06/03/2021 | wall rough all in conduit | CRAIGS | CRAIGS | | ER | P | 6990335 |
COLORADO SHEET METAL CO., INC. | H= | C | 11/17/2021 | FLEX AND DIFFUSERS COMPLETE | MARKB | MARKB | | H= | C | 7181084 |
COLORADO SHEET METAL CO., INC. | H= | P | 11/17/2021 | ENGINEER APPROVED TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | P | 7179438 |
COLORADO SHEET METAL CO., INC. | HSP | R | 11/16/2021 | Test and balance report received still does not conform to note #3 on plans and is not stamped by engineer. | MARKB | MARKB | | HSP | R | 7178232 |
COLORADO SHEET METAL CO., INC. | HSP | R | 09/20/2021 | Test and balance report received not within 10% of required values and see note #3 on plans | MARKB | MARKB | | HSP | R | 7112289 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/20/2021 | ABOVE CEILING DUCT - NEW SUPPLY BRANCH DUCT INSTALLED PER PLAN OK TO WRAP. No flex, diffusers or medical equipment at this time | MARKB | MARKB | | HD | P | 7041896 |