WD CONSULTING LLC | B= | C | 09/28/2021 | | NATHAN | NATHAN | | B= | C | 7122261 |
WD CONSULTING LLC | B= | P | 09/03/2021 | With complete required final inspections B=okay. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ELECTRIC SERVICE OF COLORADO, LLC Electrical Final Inspection is not Completed yet, RAPID PLUMBING SERVICES, LLC Plumbing Final Inspection is not Completed yet, RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7097250 |
WD CONSULTING LLC | BIN | P | 07/27/2021 | Inspection for insulation in interior walls for sound not thermal envelope. inspection not required. | NATHAN | NATHAN | | BIN | P | 7050954 |
WD CONSULTING LLC | BFR | P | 07/23/2021 | with completed required inspections frame okay, Reviewed Accessible Elements / Toilet clear floor space to sink tight need 60" clear from side wall of toilet to sink minimum at final. | NATHAN | NATHAN | | BFR | P | 7047826 |
ELECTRIC SERVICE OF COLORADO, LLC | E= | C | 09/23/2021 | | JOHNN | JOHNN | | E= | C | 7117621 |
ELECTRIC SERVICE OF COLORADO, LLC | E= | P | 09/20/2021 | see previous comments, need site visit or pics of AIC of cb's/ splice not done. | JOHNN | JOHNN | | E= | P | 7112585 |
ELECTRIC SERVICE OF COLORADO, LLC | E= | P | 09/16/2021 | need the true aic rating and the date labeled on the panel / need label where the panel feeds from/ still need plans spliced to show al feeders / | BRIAN | BRIAN | | E= | P | 7109003 |
ELECTRIC SERVICE OF COLORADO, LLC | E= | P | 09/14/2021 | still need the plans spliced to show al feeders / need label on panel showing aic rating and where the panel feeds from / pics ok / other corrections made / | BRIAN | BRIAN | | E= | P | 7107135 |
ELECTRIC SERVICE OF COLORADO, LLC | E= | P | 09/07/2021 | need 30 amp cb for HWH/need 15 amp cb's for wall heaters/ 4 cb lockouts for center wall heaters/ splice plans: al feeders, plan shows cu/ | JOHNN | JOHNN | | E= | P | 7098215 |
ELECTRIC SERVICE OF COLORADO, LLC | ER | C | 08/16/2021 | grid ok, | JOHNN | JOHNN | | ER | C | 7073168 |
ELECTRIC SERVICE OF COLORADO, LLC | EP | C | 07/23/2021 | Panel A,ok/ SPLICE 250 al,4al,grd/ last one line shows copper/ | JOHNN | JOHNN | | EP | C | 7047247 |
ELECTRIC SERVICE OF COLORADO, LLC | ER | P | 07/23/2021 | walls and hard lids,ok | JOHNN | JOHNN | | ER | P | 7047241 |
ELECTRIC SERVICE OF COLORADO, LLC | ER | P | 07/15/2021 | partial walls --see plans marked with orange / Discussed accessibility requirements with contractor / | BRIAN | BRIAN | | ER | P | 7037274 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 09/07/2021 | Mechanical final ok. Test and balance report received, see images. / | MARKB | MARKB | | H= | C | 7097768 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 09/03/2021 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT / | MARKB | MARKB | | H= | P | 7097132 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | C | 09/01/2021 | FOR FINAL - Need to confirm CO2 fan/damper interlocks in both rooms. Provide test and balance report. FLEX, DIFFUSERS, GRILLS AND ROOF OK. | MARKB | MARKB | | HD | C | 7093883 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 07/21/2021 | CONTRACTOR TO CORRECT PERMIT SCOPE TO INCLUDE: 1 commercial duct, 4 exhaust fans and 10 electric heaters. ABOVE CEILING DUCT - SUPPLY/RETURN/EXHAUST, MAINS/BRANCHES INSTALLED PER PLAN OK TO WRAP. No flex, diffusers, intake hoods, electric heaters or roof this inspection. Will need proper service access provided for inline fans above bathroom ceilings. | MARKB | MARKB | | HD | P | 7043926 |
RAPID PLUMBING SERVICES, LLC | P= | C | 09/15/2021 | BOTH ITEMS LISTED HAVE BEEN CORRECTED | LEE | LEE | | P= | C | 7107537 |
RAPID PLUMBING SERVICES, LLC | PTO | C | 09/10/2021 | Photos reviewed of shower valve installation | FRANKM | FRANKM | | PTO | C | 7103492 |
RAPID PLUMBING SERVICES, LLC | P= | P | 09/10/2021 | Bathroom #1 needs lav moved over for 60" minimum clearance from toilet wall / bathroom #2 needs toilet tank switched to right hand flush | FRANKM | FRANKM | | P= | P | 7103481 |
RAPID PLUMBING SERVICES, LLC | P= | P | 09/03/2021 | Both lavs lacking side clearance to wall ( need 15" minimum / toilet wall to edge of sink need 60" minimum) / restroom 2 toilet needs to flush to open side and lav over 34" / no power to drinking fountains / PTO never completed / | DANR | DANR | | P= | P | 7096352 |
RAPID PLUMBING SERVICES, LLC | P= | P | 09/02/2021 | No hot water / re-inspect all | FRANKM | FRANKM | | P= | P | 7095088 |
RAPID PLUMBING SERVICES, LLC | PB | C | 07/23/2021 | Corrections completed (plans revised) | FRANKM | FRANKM | | PB | C | 7046901 |
RAPID PLUMBING SERVICES, LLC | PTO | P | 07/23/2021 | No shower valves installed / ok on dwv & water rough in Note : 1 - VTR | FRANKM | FRANKM | | PTO | P | 7046852 |
RAPID PLUMBING SERVICES, LLC | PB | P | 06/29/2021 | revise plans for new pipe sizing and layout, need engineer approval for cell-core DWV, note: test ok. | TAYLOR | TAYLOR | | PB | P | 7018688 |
ELECTRIC SERVICE OF COLORADO, LLC | XES | T | 09/21/2021 | PAID (REC#1808977): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: REvise panel feeder raceway | SHELBY | SHELBY | | XES | T | 7114098 |
ELECTRIC SERVICE OF COLORADO, LLC | XES | T | 07/22/2021 | PAID (REC#1792398): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised power. | BERTHA | BERTHA | | XES | T | 7045525 |
RAPID PLUMBING SERVICES, LLC | XPS | T | 06/30/2021 | PAID (REC#1786435): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 3 revisions: Adjusted sheet P-1 and P-2. | SHANEN | SHANEN | | XPS | T | 7020175 |
RAPID PLUMBING SERVICES, LLC | XPS | T | 06/29/2021 | PAID (REC#1785690): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: Adjusted sheet P-2. | SHANEN | SHANEN | | XPS | T | 7018616 |