WD CONSULTING LLC | B= | C | 08/02/2023 | | ERAMIREZ | ERAMIREZ | | B= | C | 7814984 |
WD CONSULTING LLC | B= | P | 07/07/2023 | Temp CO: Pendin required finals ( Expires: 8/6/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7791815 |
WD CONSULTING LLC | B= | T | 06/09/2023 | PAID (REC#1960659): Trip fee assessed for TCO fee. Additional Inspections Required (computer generated): EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, HOLBROOK SERVICE LLC Mechanical Final Inspection is not Completed yet. | RITA | RITA | | B= | T | 7767790 |
WD CONSULTING LLC | B= | P | 06/09/2023 | Temp CO: Pending mechanical, electrical and building finals ( Expires: 7/9/2023 12:00:00 AM) | RITA | RITA | | B= | P | 7767763 |
WD CONSULTING LLC | B= | P | 05/12/2023 | Temp CO: Pending required inspections. ( Expires: 6/11/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7743513 |
WD CONSULTING LLC | B= | P | 04/13/2023 | Temp CO: Pending required inspections. ( Expires: 5/13/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7715337 |
WD CONSULTING LLC | B= | P | 03/17/2023 | Temp CO: Pending mechanical, electrical and building finals ( Expires: 4/16/2023 12:00:00 AM) | RITA | RITA | | B= | P | 7690772 |
WD CONSULTING LLC | B= | P | 02/16/2023 | Temp CO: Pending required inspections ( Expires: 3/18/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7663103 |
WD CONSULTING LLC | B= | P | 01/19/2023 | Temp CO: Pending required inspections ( Expires: 2/18/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7638791 |
WD CONSULTING LLC | B= | P | 12/21/2022 | Temp CO: Pending required inspections ( Expires: 1/20/2023 12:00:00 AM) | AMYP | AMYP | | B= | P | 7618177 |
WD CONSULTING LLC | B= | P | 11/22/2022 | Temp CO: Pending required inspections. ( Expires: 12/22/2022 12:00:00 AM) | AMYP | AMYP | | B= | P | 7590421 |
WD CONSULTING LLC | B= | P | 11/16/2022 | Attain elevator permit or attached to permit. / Provide door locking hardware or partition walls for bathroom per IBC 1210.3. / Handrail to return back to wall or ground by rear exist. / Complete other final inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by WOODLAND PARK is not Completed yet (Contact: Dave Burgess at 719-687-5202), EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, HOLBROOK SERVICE LLC Mechanical Final Inspection is not Completed yet, RAPID PLUMBING SERVICES, LLC Plumbing Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7585401 |
WD CONSULTING LLC | B= | P | 10/25/2022 | Temp CO: Pending required inspections ( Expires: 11/24/2022 12:00:00 AM) | AMYP | AMYP | | B= | P | 7560982 |
WD CONSULTING LLC | B= | P | 09/26/2022 | Temp CO: pending Z, P, H, E, B='s ( Expires: 10/26/2022 12:00:00 AM) | BRITNEY | BRITNEY | | B= | P | 7529214 |
WD CONSULTING LLC | B= | P | 08/30/2022 | Incomplete handrail extensions for ramp on main level. / Provide a code compliant handrail on both sides at rear exit door. / Missing visible sign stating: "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED" at front egress doors. / Both bathroom doors lock hardware exceed maximum height of 48" (currently 49"). Complete other final inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet, External Agency Inspection Z= by WOODLAND PARK is not Completed yet (Contact: Dave Burgess at 719-687-5202), EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, HOLBROOK SERVICE LLC Mechanical Final Inspection is not Completed yet, RAPID PLUMBING SERVICES, LLC Plumbing Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7500870 |
WD CONSULTING LLC | BSP | P | 08/24/2022 | Observed steel framing for upper level at south windows. / Provide 3rd party observation report for welding and bolting structural connections / | ERAMIREZ | ERAMIREZ | | BSP | P | 7494419 |
WD CONSULTING LLC | BSP | P | 07/21/2022 | Engineer observation letter for welds on file. | ERAMIREZ | ERAMIREZ | | BSP | P | 7454411 |
WD CONSULTING LLC | BLA | C | 07/05/2022 | | JEREMYA | JEREMYA | | BLA | C | 7434645 |
WD CONSULTING LLC | BFR | P | 06/30/2022 | Framing for headers at 2nd floor, north wall OK per approved splice | JEREMYA | JEREMYA | | BFR | P | 7431298 |
WD CONSULTING LLC | BSP | P | 06/22/2022 | Reviewed accessible elements. / Reviewed requirements for exterior stairway to rooftop deck. / | ERAMIREZ | ERAMIREZ | | BSP | P | 7421059 |
WD CONSULTING LLC | BIN | P | 06/17/2022 | Complete BFR inspection. / Insulation okay. | ERAMIREZ | ERAMIREZ | | BIN | P | 7415509 |
WD CONSULTING LLC | BFR | R | 06/17/2022 | No inspection performed due to changes not spliced in. | ERAMIREZ | ERAMIREZ | | BFR | R | 7415486 |
WD CONSULTING LLC | BFR | P | 06/07/2022 | Observed rear bathrooms, retail framing on 1st floor and chimney framing for Bvent at roof. / Observed bracing at south wall, roof 4x4 and lag screws for dog house at roof per engineer plans provided on site. Contractor to submit changes in plans for splice. / | ERAMIREZ | ERAMIREZ | | BFR | P | 7402118 |
WD CONSULTING LLC | BSP | P | 05/25/2022 | Observed pad footing and reinforcement for exterior stair landing per plans. | ERAMIREZ | ERAMIREZ | | BSP | P | 7388800 |
WD CONSULTING LLC | BFR | P | 05/25/2022 | Still need engineer stamped details and to splice for upper level window and door frame to roof due to not matching plans. / Observed sleeper floor and interior stair framing. / | ERAMIREZ | ERAMIREZ | | BFR | P | 7388797 |
WD CONSULTING LLC | BFT | C | 05/16/2022 | Observed piers for patio cover. | ERAMIREZ | ERAMIREZ | | BFT | C | 7377099 |
WD CONSULTING LLC | BFR | P | 05/09/2022 | Need mechanical to observe clearance of Bvent to roof decking. / Reviewed need engineer stamped details and to splice for upper level window and door frame to roof due to not matching plans. / Attach mechanical to permit and complete other required rough inspections. / Observed roof decking and corrections of H2.5 for TJI. | ERAMIREZ | ERAMIREZ | | BFR | P | 7368741 |
WD CONSULTING LLC | BIN | P | 05/03/2022 | Complete BFR. / Observed R30 between roof rafters. / | ERAMIREZ | ERAMIREZ | | BIN | P | 7361060 |
WD CONSULTING LLC | BFR | P | 04/14/2022 | Incorrect fastening of H2.5 for TJI at main level. Rest of floor framing rear second floor okay. / Observed framing for new roof access. / Attach mechanical to permit. / Complete other rough inspections. / Reviewed Accessible Elements / | ERAMIREZ | ERAMIREZ | | BFR | P | 7338741 |
EL PASO ELECTRIC, LLC. | E= | C | 07/10/2023 | | JOHNN | JOHNN | | E= | C | 7792818 |
EL PASO ELECTRIC, LLC. | E= | R | 05/09/2023 | need splice still. | JOHNN | JOHNN | | E= | R | 7740082 |
EL PASO ELECTRIC, LLC. | E= | P | 11/10/2022 | still need plan splice, rest is ok. | JOHNN | JOHNN | | E= | P | 7580062 |
EL PASO ELECTRIC, LLC. | E= | P | 08/31/2022 | missing black outlet in front room/ need gfci low, behind bar/ missing some fixtures through out/ splice 1 line: keeping original disco's at meters, removed 2nd floor panel, only added 1 new sub panel inside/ field verify splice later/ | JOHNN | JOHNN | | E= | P | 7502801 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 07/26/2022 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | E= | C | 7460694 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 07/26/2022 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | ER | C | 7460685 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 07/26/2022 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | E= | C | 7460686 |
EL PASO ELECTRIC, LLC. | ER | P | 06/07/2022 | 1st floor and 2nd floor exit hall to roof patio --ok / walls only / | BRIAN | BRIAN | | ER | P | 7402895 |
HOLBROOK SERVICE LLC | H= | C | 08/01/2023 | RECEIVED TEST AND BALANCE REPORT, SEE IMAGES / | MATTM | MATTM | | H= | C | 7813368 |
HOLBROOK SERVICE LLC | H= | L | 07/19/2023 | ***PAGE 9 OF TEST AND BALANCE REPORT SHOWS 429 CFM FOR REQUIRED OUTSIDE AIR AS NATURAL VENTILATION, BUT PLANS SHOW THE REQUIRED VENTILATION COMING FROM EXISTING FURNACE. IF SWITCHING TO NATURAL VENTILATION, THIS WILL NEED TO BE SHOWN ON PLANS.*** FALL PROTECTION ANCHOR IN PLACE, FALL PROTECTION HARNESS AND LANYARD INSIDE MECH ROOM DOORWAY. | BILLS | BILLS | | H= | L | 7802134 |
HOLBROOK SERVICE LLC | HE | L | 07/14/2023 | Renewed online for Half Fee at Jul 14 2023 1:18PM (RECEIPT #: 1969531) | WEBSITE | WEBSITE | | HE | L | 7798528 |
MORNING STAR ELEVATOR, LLC. | HE= | C | 12/30/2022 | WITNESSED ACCEPTANCE TESTS WITH MORNING STAR ELEVATOR. GARAVENTA OK FOR USE | MIKEM | MIKEM | | HE= | C | 7622730 |
HOLBROOK SERVICE LLC | H= | L | 12/12/2022 | MECHANICAL ROOM DOOR NOW SELF-CLOSING / Need to address the following: Correct test and balance report. Provide code compliant working space/platform and fall protection or guards around mechanical equipment on top of stairway / | MATTM | MATTM | | H= | L | 7608292 |
HOLBROOK SERVICE LLC | H= | P | 11/18/2022 | PAGE 9 OF TEST AND BALANCE REPORT SHOWS 429 CFM FOR REQUIRED OUTSIDE AIR AS NATURAL VENTILATION, BUT PLANS SHOW THE REQUIRED VENTILATION COMING FROM EXISTING FURNACE. IF SWITCHING TO NATURAL VENTILATION, THIS WILL NEED TO BE SHOWN ON PLANS. | MATTM | MATTM | | H= | P | 7587541 |
HOLBROOK SERVICE LLC | H= | P | 11/16/2022 | PROVIDE TEST AND BALANCE REPORT / MECHANICAL ROOM DOOR NEEDS TO COMPLY WITH 2015 IFGC 303.3/2017 PPRBC / FURTHER RESEARCH REQUIRED FOR FALL PROTECTION / ****UPDATE: FALL PROTECTION PROVIDED OFFERS INADEQUATE PROTECTION**** | MATTM | MATTM | | H= | P | 7585294 |
HOLBROOK SERVICE LLC | HSP | P | 09/02/2022 | REQUIREMENT FOR PERMANENT LADDER WILL NOT APPLY TO THIS PROJECT / ALL OTHER ITEMS WILL NEED TO BE ADDRESSED / | MATTM | MATTM | | HSP | P | 7505454 |
HOLBROOK SERVICE LLC | H= | P | 08/24/2022 | PROVIDE TEST AND BALANCE REPORT / MECHANICAL ROOM LACKS COMBUSTION AIR / MECHANICAL ROOM DOOR NEEDS TO COMPLY WITH 2015 IFGC 303.3/2017 PPRBC / ENGINEER TO ADDRESS: How will equipment on top of stairwell comply with the 2015 IMC SECTIONS 304.11, 306.5, 306.5.1. and 306.1? / Will need to conduct roof top inspection when ready / | MATTM | MATTM | | H= | P | 7493820 |
HOLBROOK SERVICE LLC | HD | P | 08/01/2022 | ****UPDATE BY MLM ON 8/2/22---ENGINEER TO ADDRESS: How will equipment on top of stairwell comply with the 2015 IMC SECTIONS 304.11, 306.5, 306.5.1. and 306.1?**** ENGINEER TO ADDRESS: How will FURNACE 1 obtain combustion air per the 2015 IFGC SECTION 304? How will FURNACE 1 comply with the 2015 IFGC PROHIBITED LOCATIONS SECTION 303.3/2017 PPRBD? / FURNACE 1 DUCT PER PLANS. Still need to see supply taps cut in. / EF-1 DUCT PER PLANS. DOAS-1 DUCT PER PLANS. Still need to see final tie in for DOAS-1 / more notes to follow / | MATTM | MATTM | | HD | P | 7466158 |
HOLBROOK SERVICE LLC | HRP | C | 06/20/2022 | | MATTM | MATTM | | HRP | C | 7417265 |
HOLBROOK SERVICE LLC | HD | P | 06/20/2022 | BOTH BATHROOM SUPPLY AND EXHAUST PER PLANS. | MATTM | MATTM | | HD | P | 7417259 |
HOLBROOK SERVICE LLC | HRP | P | 06/08/2022 | LINESET SUPPORT AND NAIL PROTECTION OK. Still need test on lineset. cannot conceal vinyl tubing / | MATTM | MATTM | | HRP | P | 7403671 |
HOLBROOK SERVICE LLC | HV | C | 06/08/2022 | | MATTM | MATTM | | HV | C | 7403665 |
HOLBROOK SERVICE LLC | HC | C | 05/17/2022 | RELEASE METER | MATTM | MATTM | | HC | C | 7378705 |
HOLBROOK SERVICE LLC | HI | C | 05/17/2022 | 10 LB TEST OK / GAS PER PLAN / | MATTM | MATTM | | HI | C | 7378697 |
HOLBROOK SERVICE LLC | HV | P | 05/16/2022 | INSPECTION WAS FOR VENT ONLY: VENT OK FOR EXISTING EQUIPMENT. STILL NEED TO INSPECT VENT CHASE ABOVE ROOF LINE WHEN CONSTRUCTED / | MATTM | MATTM | | HV | P | 7376909 |
HOLBROOK SERVICE LLC | HV | P | 05/11/2022 | THIS INSPECTION IS FOR THE RELOCATED VENT ONLY: VENT REQUIRES 1 INCH CLEARANCE TO ROOF DECK / VENT MUST COMPLY WITH THE 2015 IRC SECTION 503.6.3 AND 504.2.9. VENT CHASE WILL REQUIRE INSPECTION BY BOTH MECHANICAL AND BUILDING INSPECTORS. AN INSULATION VALUE OF R-8 MUST BE ACHIEVED AND INSPECTED PRIOR TO CHASE BEING COVERED / COMMON WYE MUST BE UPGRADED TO DOUBLE WALL PER 504.3.9.1 / RELOCATED VENT IS UNDERSIZED PER 504.3.6 AND TABLE 504.3(2) / | MATTM | MATTM | | HV | P | 7371958 |
RAPID PLUMBING SERVICES, LLC | P= | C | 12/15/2022 | | TRAVISR | TRAVISR | | P= | C | 7612016 |
RAPID PLUMBING SERVICES, LLC | P= | T | 11/09/2022 | PAID (REC#1914792): Call Ahead Completed @ 9:15 / No Answer @ All 3 Doors @ 10:18 | TRAVISR | TRAVISR | | P= | T | 7577442 |
RAPID PLUMBING SERVICES, LLC | P= | T | 09/16/2022 | PAID (REC#1900246): All 3 Doors Locked Call Ahead Completed @ 9:43 / | TRAVISR | TRAVISR | | P= | T | 7519758 |
RAPID PLUMBING SERVICES, LLC | P= | P | 09/07/2022 | Can Not Use San Tee On Back / Same As Before | TRAVISR | TRAVISR | | P= | P | 7508365 |
RAPID PLUMBING SERVICES, LLC | P= | P | 08/25/2022 | Leak glass washer sink and cannot use santees on back for drainage / rest okay. | DANR | DANR | | P= | P | 7495678 |
RAPID PLUMBING SERVICES, LLC | PTO | C | 06/20/2022 | | TRAVISR | TRAVISR | | PTO | C | 7417255 |
RAPID PLUMBING SERVICES, LLC | PTO | P | 06/17/2022 | DWV Lost Test / Re-Inspect All DWV
Note: H20 OK | TRAVISR | TRAVISR | | PTO | P | 7415474 |
RAPID PLUMBING SERVICES, LLC | PB | C | 05/09/2022 | Note: OK / SK2 Running Indirect To Floor Sink | TRAVISR | TRAVISR | | PB | C | 7368732 |
HOLBROOK SERVICE LLC | XMS | T | 07/26/2023 | PAID (REC#1972901): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised ventilation strategy | JUSTINC | JUSTINC | | XMS | T | 7808321 |
EL PASO ELECTRIC, LLC. | XES | P | 07/06/2023 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised power plan, revised schedules, revised one-line | BERTHA | BERTHA | | XES | P | 7791335 |
HOLBROOK SERVICE LLC | XMS | T | 08/23/2022 | PAID (REC#1894630): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised for combustion air changes | JUSTINC | JUSTINC | | XMS | T | 7492688 |
WD CONSULTING LLC | XBS | T | 07/27/2022 | PAID (REC#1886627): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Additional structural detail | MICHAELA | MICHAELA | | XBS | T | 7462176 |
EL PASO ELECTRIC, LLC. | XES | T | 06/27/2022 | PAID (REC#1884218): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added humidor. | BERTHA | BERTHA | | XES | T | 7425996 |
HOLBROOK SERVICE LLC | XMS | P | 06/27/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised backgrounds | JUSTINC | JUSTINC | | XMS | P | 7425690 |
RAPID PLUMBING SERVICES, LLC | XPS | P | 06/27/2022 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Delta 4 revisions: Adjusted sheet P1.1. | SHANEN | SHANEN | | XPS | P | 7425506 |
EL PASO ELECTRIC, LLC. | XES | T | 06/22/2022 | PAID (REC#1889678): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised service. | BERTHA | BERTHA | | XES | T | 7421032 |
WD CONSULTING LLC | XBS | T | 05/06/2022 | PAID (REC#1864834): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Updated scope of work. | MICHAELA | MICHAELA | | XBS | T | 7366049 |