GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 04/24/2023 | | ADAML | ADAML | | B= | C | 7725352 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | R | 02/22/2023 | Spoke to contractor via phone / Not ready for a final / We still need to see the two layers of 5/8 drywall on the UL U438 in the mechanical shaft. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | R | 7666931 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 11/10/2022 | shaftwall drywall inspection of 2 layers needed, complete all final inspections, remaining portion of permit (pharmacy) okay. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ENCORE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Mechanical Final Inspection is not Completed yet, U.S.ENGINEERING CONSTRUCTION, LLC Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7579312 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/10/2022 | Shaft wall frame and 1" drywall per U438 | NATHAN | NATHAN | | BFR | P | 7579308 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 10/13/2022 | Drywall OK on UL U419 walls | ADAML | ADAML | | BSP | P | 7549757 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 08/26/2022 | Pending all other required inspections -
Metal framing OK throughout except for P-Tube station / Metal framing OK for UL U419 walls ( Note* U419 is a Proprietary USG drywall listing and American is the only drywall stocked on site / U438 uses USG 1" shaftliners as well which is verified on site / Discussed infill for rexisting rated walls that have had drywall removed on North and South perimeter walls / Reviewed accessible elements | ADAML | ADAML | | BFR | P | 7497267 |
ENCORE ELECTRIC, INC. | E= | C | 03/01/2023 | Remaining undercab lights deleted and whip removed - complete | CHIPO | CHIPO | | E= | C | 7673416 |
ENCORE ELECTRIC, INC. | E= | P | 11/03/2022 | All okay except two undercab light locations and wall with medicinal tube delivery sytem | CHIPO | CHIPO | | E= | P | 7571642 |
ENCORE ELECTRIC, INC. | E= | C | 10/28/2022 | FIRE ALARM INSPECTION: Fir Alarm okay | CHIPO | CHIPO | | E= | C | 7565819 |
ENCORE ELECTRIC, INC. | E= | C | 10/28/2022 | FIRE ALARM INSPECTION: Fir Alarm rough in okay | CHIPO | CHIPO | | E= | C | 7565820 |
ENCORE ELECTRIC, INC. | ER | C | 10/28/2022 | rough in okay | CHIPO | CHIPO | | ER | C | 7565809 |
ENCORE ELECTRIC, INC. | EP | P | 10/19/2022 | Choke both side of GEC EMT to ground bar in both elec. rooms / Transformer feed TEBBCL2 will need 45 amp brkr, 50 amp installed / Panels and transformers ok | BRETC | BRETC | | EP | P | 7555804 |
ENCORE ELECTRIC, INC. | ER | P | 10/07/2022 | some walls and hard lids ---see plans / | BRIAN | BRIAN | | ER | P | 7543847 |
ENCORE ELECTRIC, INC. | ER | P | 08/23/2022 | walls to include f/a contractor to call in f/a 8/24/22 | CRAIGS | CRAIGS | | ER | P | 7492795 |
ENCORE ELECTRIC, INC. | ESL | C | 07/12/2022 | floor boxes and pvc conduit ------- non patient care ----OK | CRAIGS | CRAIGS | | ESL | C | 7443549 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | C | 03/08/2023 | NO WORK BEING PERFORMED UNDER THIS PERMIT SCOPE ON 1ST FLOOR - 1ST FLOOR MECHANICAL SPLICE HAS BEEN REMOVED FROM PLAN SET. CONTRACTOR SCOPE COMPLETE FOR THIS PERMIT. | MARKB | MARKB | | H= | C | 7681656 |
U.S. ENGINEERING CONSTRUCTION, LLC | HSP | P | 03/07/2023 | TEST AND BALANCE REPORT RECEIVED FOR BASEMENT PHARMACY ONLY - SEE IMAGES | MARKB | MARKB | | HSP | P | 7678837 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 12/07/2022 | FINAL PENDING - Complete work and inspections for 1st floor spliced into plans. Provide test and balance report. PHARMACY EXHAUST FAN COMPLETE. | MARKB | MARKB | | H= | P | 7604138 |
U.S. ENGINEERING CONSTRUCTION, LLC | H= | P | 11/15/2022 | PHARMACY FINAL PENDING - Need to inspect EF-HD on roof. Provide test and balance report. FLEX AND DIFFUSERS COMPLETE IN B114. THERMOSTATS COMPLETE. | MARKB | MARKB | | H= | P | 7584238 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 10/21/2022 | BASEMENT: ABOVE CEILING DUCT - FLEX AND DIFFUSERS COMPLETE EXCEPT: Still need to finish in room B114. 3M DUCT WRAP PINNING IN TRASH ROOM COMPLETE. | MARKB | MARKB | | HD | P | 7558937 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 10/06/2022 | FLEX AND DIFFUSERS OK FOR ROOMS B109, 108, 107 AND 106 / DUCT WRAP OK FOR 3RD FLOOR RISER ROOM / Need to pin 3M insulation on bottom of duct on 1st floor / | MATTM | MATTM | | HD | P | 7542177 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 10/03/2022 | 3X FIRE DAMPER ALONG CORRIDOR OK FOR ANNULAR SPACING / | MATTM | MATTM | | HD | P | 7537712 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 09/29/2022 | 30X8 EXHAUST OK FROM DATA ROOM TO ROOF / OK TO APPLY FIRE WRAP FIRST AND SECOND LAYER IF PICTURES OF FIRST WRAP CAN BE PROVIDED TO INSPECTOR AT NEXT INSPECTION / | MATTM | MATTM | | HD | P | 7534260 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 09/27/2022 | Need to address annular spacing for 3 fire dampers along corridor / Provide damper installation instructions at next inspection / | MATTM | MATTM | | HD | P | 7531954 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 08/29/2022 | ABOVE CEILING DUCT - ROUGH DUCT COMPLETE FOR EAV-2, SAV-PH35 & VAV-16. Still need annular space inspections for 3 fir dampers. No flex or diffusers this inspection. | MARKB | MARKB | | HD | P | 7499340 |
U.S. ENGINEERING CONSTRUCTION, LLC | HWP | P | 08/23/2022 | 3 x 100 PSI PRESSURE TEST OK FOR ALL VAV'S & SAV. ALL FINAL CONNECTIONS COMPLETE - Piping not per plan continue at own risk. | MARKB | MARKB | | HWP | P | 7492629 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 08/16/2022 | FIRE DAMPER FRAMING OK FOR: 18X12 & 22X16 DAMPERS AT ROOM B117, 30X12 DAMPER AT ROOM B104. ANNULAR SPACE OK FOR 28X12 FIRE DAMPER AT ROOM B114. ABOVE CEILING DUCT - ALL MAINS/BRANCHES OK TO WRAP EXCEPT: Still need duct installed for EAV-2, SAV-PH35 & VAV - 16. | MARKB | MARKB | | HD | P | 7484847 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 08/09/2022 | FIRE DAMPER - 16X16 DAMPER FRAMING, ANNULAR SPACE AND ANGLES COMPLETE AT B114. ANGLES FOR 28X12 DAMPER AT B114 COMPLETE BUT Still need to confirm annular space on back side of wall. | MARKB | MARKB | | HD | P | 7476982 |
U.S. ENGINEERING CONSTRUCTION, LLC | HD | P | 08/03/2022 | INSPECTED FROM PLAN SPLICE 7/20/22 SHEET M1.1.1 ABOVE CEILING DUCT - EXHAUST DUCT OFFSET ABOVE CORRIDOR CEILING OK TO COVER. 20"X12" AND 12" ABOVE BATHROOMS TO B100 OK TO COVER. PER NOTE #8, ENGINEER IS USING 2015 IBC SECTION 717.5.2 EXCEPTION 3 AND FOR PENETRATION AT B100 WALL AND THESE DUCTS WILL NEED TO BE METAL TO THE DIFFUSERS TO MEET THE EXCEPTION - NO FLEX ALLOWED. 20"X12" MAIN IN NEW WORK AREA OK TO COVER. FRAMING FOR 28X12 FIRE DAMPER AT ROOM B113 COMPLETE. | MARKB | MARKB | | HD | P | 7470200 |
U.S. ENGINEERING CONSTRUCTION, LLC | HWP | P | 07/21/2022 | Inspection for HWP sheet M2.1.1-- PIPING NOT PER PLANS & INSPECTION WAS DONE OFF OF UN-APPROVED ON SITE PLANS (RED LINE/CONTRACTOR STATES THAT SPLICE HAS BEEN SUBMITTED/CONTRACTOR IS PROCEEDING AT OWN RISK). Note / 100 lb. test x3 ok. | PAULO | PAULO | | HWP | P | 7455741 |
U.S. ENGINEERING CONSTRUCTION, LLC | P= | C | 11/15/2022 | Correction made see images | CODYP | CODYP | | P= | C | 7583111 |
U.S. ENGINEERING CONSTRUCTION, LLC | P= | P | 11/03/2022 | CLEAN AIR ROOM SINK LACKS LISTED TEMPERING DEVICE -- OTHER OK | LEE | LEE | | P= | P | 7572437 |
U.S. ENGINEERING CONSTRUCTION, LLC | PTO | C | 08/17/2022 | | CODYP | CODYP | | PTO | C | 7485459 |
U.S. ENGINEERING CONSTRUCTION, LLC | PTO | P | 07/20/2022 | --Need plan revision showing new tie in location for sink in room B107 and vent tie in location in mech room,
--Need plan revision showing water tie in location changes
NOTE/ Over head domestic water o.k. | CODYP | CODYP | | PTO | P | 7453358 |
U.S. ENGINEERING CONSTRUCTION, LLC | PTO | P | 07/11/2022 | --Need plan revision showing new tie in location for sink in room B107 and vent tie in location in mech room,
NOTE/ Only DWV o.k./ Will need accessibility measurements, water lines and flanges | CODYP | CODYP | | PTO | P | 7441196 |
U.S. ENGINEERING CONSTRUCTION, LLC | PB | P | 07/11/2022 | --Need plan revision showing new tie in location for sink in room B107 and vent tie in location in mech room, NOTE/ Rest o.k. | CODYP | CODYP | | PB | P | 7441192 |
U.S. ENGINEERING CONSTRUCTION, LLC | XMS | P | 03/09/2023 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised for field applied shaft with duct wrap | JUSTINC | JUSTINC | | XMS | P | 7682534 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 03/09/2023 | PAID (REC#1941911) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Shaft wrap continuity. | SHELLEY | SHELLEY | | XBS | T | 7682450 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 12/22/2022 | PAID (REC#1930645): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised details for duct from basement through roof, and minor floor plan change. | SHELLEY | SHELLEY | | XBS | T | 7618924 |
U.S. ENGINEERING CONSTRUCTION, LLC | XMS | P | 12/05/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: exhaust revisions | JUSTINC | JUSTINC | | XMS | P | 7599848 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 10/26/2022 | PAID (REC#1913520) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Added gas fireplace | SHELLEY | SHELLEY | | XBS | T | 7563886 |
ENCORE ELECTRIC, INC. | XES | P | 09/17/2022 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: As builts | SHELBY | SHELBY | | XES | P | 7520649 |
U.S. ENGINEERING CONSTRUCTION, LLC | XMS | T | 09/09/2022 | PAID (REC#1898344): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout revisions | JUSTINC | JUSTINC | | XMS | T | 7511082 |
U.S. ENGINEERING CONSTRUCTION, LLC | XMS | T | 08/25/2022 | PAID (REC#1894931): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout revisions | JUSTINC | JUSTINC | | XMS | T | 7495034 |
ENCORE ELECTRIC, INC. | XES | P | 07/30/2022 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: As builts | SHELBY | SHELBY | | XES | P | 7465676 |
U.S. ENGINEERING CONSTRUCTION, LLC | XPS | P | 07/20/2022 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Delta 5 revisions: Adjusted sheet PD1.1.1, P1.1.1 and P2.1.1. | SHANEN | SHANEN | | XPS | P | 7454021 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XBS | T | 07/20/2022 | PAID (REC#1889199) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Removed furred wall, misc. details, and framing for penetration. | SHELLEY | SHELLEY | | XBS | T | 7453990 |