LONE STAR BUILDERS, LLC | BIN | P | 03/22/2024 | Insulation ok on break room and bathroom exterior walls / | ERIKK | ERIKK | | BIN | P | 8030297 |
LONE STAR BUILDERS, LLC | BFR | P | 03/18/2024 | exterior decorative column framing around building okay | BOBF | BOBF | | BFR | P | 8024518 |
LONE STAR BUILDERS, LLC | BFR | P | 03/13/2024 | exterior arch on west side okay | BOBF | BOBF | | BFR | P | 8022444 |
LONE STAR BUILDERS, LLC | BIN | P | 03/07/2024 | r-10 rigid in mech and elec rooms okay | BOBF | BOBF | | BIN | P | 8017067 |
LONE STAR BUILDERS, LLC | BFR | P | 03/07/2024 | framing for exterior arches parapets west tower, okay , interior wall framing at breakroom, mech room, elec room and hardlid framing throughout okay , Reviewed Accessible Elements / | BOBF | BOBF | | BFR | P | 8017066 |
LONE STAR BUILDERS, LLC | BIN | P | 03/06/2024 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | INTERNET | INTERNET | | BIN | P | 8015409 |
LONE STAR BUILDERS, LLC | BSP | P | 02/06/2024 | Site consultation with GC regarding site inspections and permit questions / | ERIKK | ERIKK | | BSP | P | 7988178 |
LONE STAR BUILDERS, LLC | BSP | P | 12/27/2023 | Third party observations approved / Discussed inspection procedures with superintendent / | ERIKK | ERIKK | | BSP | P | 7953941 |
LONE STAR BUILDERS, LLC | BSP | P | 11/20/2023 | damp proofing okay | BOBF | BOBF | | BSP | P | 7923320 |
SUTTON ELECTRIC, LLC | ER | R | 04/26/2024 | pvc must be secured within 3' of every box and light fixture and every 3' | BRET | BRET | | ER | R | 8066219 |
SUTTON ELECTRIC, LLC | EUG | C | 04/05/2024 | PVC Meets cover requirements / north and south vacuum enclosures. / | LARRYT | LARRYT | | EUG | C | 8044334 |
SUTTON ELECTRIC, LLC | ER | P | 03/12/2024 | break room and bath rough only, home runs not pulled at time of rough | BRET | BRET | | ER | P | 8021912 |
SUTTON ELECTRIC, LLC | ER | P | 02/29/2024 | do not need to call inspection in for l.v wiring | BRET | BRET | | ER | P | 8010597 |
SUTTON ELECTRIC, LLC | EUG | P | 02/21/2024 | Underground for Qb shack and vacuum enclosures. | RANDY | RANDY | | EUG | P | 8001041 |
SUTTON ELECTRIC, LLC | EUG | P | 01/10/2024 | 3 4" pcv conduits from transformer to building ok to cover | BRET | BRET | | EUG | P | 7964698 |
SUTTON ELECTRIC, LLC | ESL | C | 12/19/2023 | pvcs under slab ok---ufer stubbed out | RANDY | RANDY | | ESL | C | 7949292 |
WESTERN PEAK PLUMBING LLC | HD | P | 04/24/2024 | PLAN SHEET M 1.1 RADIANT TUBE HEATERS RE INSPECT ALL, NEED ADDITIONAL SUPPORT ON BOTH THE INLET AND DISCHARGE SIDE OF ALL THREE HEATERS , ON THE DISCHARGE END ALL SINGLE WALL VENTING HAS BEEN RAN BACK WARDS , NEED TO SECURE ALL INLET PIPING WITH THREE SCREWS, END CAPS MISSING ON ALL THREE UNITS. NO ROOF ACCESS AT THIS TIME RECALL INSPECTION WHEN READY. | TREVORH | TREVORH | | HD | P | 8063478 |
WESTERN PEAK PLUMBING LLC | HRP | P | 04/15/2024 | CONTRACTORS INTERNAL POLICY 400 PSI TEST OK ON CONCEALED LINE SET F-1 CONDENSER , | TREVORH | TREVORH | | HRP | P | 8052788 |
WESTERN PEAK PLUMBING LLC | HD | P | 04/15/2024 | (DUCT ROUGH) OUTSIDE AIR DAMPER HAS NOW BEEN INSTALLED,OK AT NEXT REQUEST WILL VERIFY CONDENSATE DRAIN LINES WHEN READY. | TREVORH | TREVORH | | HD | P | 8052777 |
WESTERN PEAK PLUMBING LLC | HD | P | 04/03/2024 | PLAN SHEET M1.1 BDA PG. 92. FURNACE CHAMPION INSTALLED. NEED REVISED EQUIPMENT SCHEDULE OR ENGINEER APPROVED STAMPED LETTER. (DUCT ROUGH) FURNACE F1.5 NEED TO SEE HANGERS ON SUPPLY PLENUM. NEED TO SEE OUTSIDE AIR MOTORIZED AND MANUAL DAMPERS INSTALLED . NEED TO SEE COMPLETE CONDENSATE DRAIN PIPE ABOVE LID. NEED TO SEE SUPPLY OPENING IN BATHROOM TO CEILING HARD LID. AT NEXT INSPECTION REQUEST WILL VERIFY CORRECTIONS. AC LINESET NOT CONNECTED AT THIS TIME. NO ROOF ACCESS AT THIS TIME. | JOSHH | JOSHH | | HD | P | 8041391 |
WESTERN PEAK PLUMBING LLC | HI | P | 03/26/2024 | GAS INSTALL DOES NOT MATCH PLANS ON FILE WILL NEED PLAN SPLICE REFLECTING CURRENT INSTALL AND METER LOCATION. CAN NOT RELEASE METER UNTIL PLAN SPLICE IS ON FILE. (PARTIAL) 10 LB TEST OK, GAS SIZING PER PLAN , PIPING JUST STUBBED INTO WASHBAY AT THIS TIME.OK. WILL VERIFY REMAINING GAS PIPING WHEN READY. | TREVORH | TREVORH | | HI | P | 8033820 |
WESTERN PEAK PLUMBING LLC | HD | P | 03/13/2024 | PLAN SHEET M1.1 (BDA PAGE 92 ) (DUCT ROUGH) EXHAUST FAN CEF-1 INSTALLED IN HARD LID BATH ROOM CEILING OK VERIFY SIDE WALL TERMINATION AT NEXT INSPECTION REQUEST. | TREVORH | TREVORH | | HD | P | 8023004 |
WESTERN PEAK PLUMBING LLC | HWP | P | 12/19/2023 | THE FOLLOWING IS NOT SHOWN ON PLANS WILL NEED RADIANT HWS/HWR LINES ON PLANS , IF SNOW MELT BOILER IS TO BE INSTALLED THE BOILER WILL ALSO NEED TO BE INCLUDED IN THE PLAN SPLICE OR SHOWN ON PLANS AS FUTURE. 50 LB TEST OK FOR THE 1'' HWS/ HWR LINES SERVING THE SNOW MELT OK TO PROVIDE PICTURES OF COMPLETED INSULATION UP TO THE EDGE OF THE BUILDING. OK TO COVER PIPING UPON INSULATION COMPLETION | TREVORH | TREVORH | | HWP | P | 7948643 |
WESTERN PEAK PLUMBING LLC | PRD | C | 04/10/2024 | VERIFY DOMES, COLLARS AND LAMBS TONGUE AT FINAL | ADRIANM | ADRIANM | | PRD | C | 8048238 |
WESTERN PEAK PLUMBING LLC | PB | C | 03/25/2024 | | ADRIANM | ADRIANM | | PB | C | 8031917 |
WESTERN PEAK PLUMBING LLC | PTO | P | 03/25/2024 | EMPLOYEE LOUNGE AND RESTROOM IN-WALL/OVERHEAD H2O/DWV: SECURE CLOSET FLANGE / REST OK /// WEST FLOOR DRAIN NEAR ELECTRICAL ROOM AND ASSOCIATED VENTS: OK /// | ADRIANM | ADRIANM | | PTO | P | 8031915 |
WESTERN PEAK PLUMBING LLC | PTO | L | 01/17/2024 | Cancelled per contractor | ADRIANM | ADRIANM | | PTO | L | 7969808 |
WESTERN PEAK PLUMBING LLC | PB | P | 12/28/2023 | need to see closet wrap for all risers at restroom / rest ok | TREBORB | TREBORB | | PB | P | 7955389 |
WESTERN PEAK PLUMBING LLC | PB | T | 12/27/2023 | PAID (REC#2019954): lost test, can not mound piping at floor drain. | TAYLOR | TAYLOR | | PB | T | 7954137 |
WESTERN PEAK PLUMBING LLC | PB | L | 12/26/2023 | field cancelled. | TAYLOR | TAYLOR | | PB | L | 7953043 |
WESTERN PEAK PLUMBING LLC | PB | P | 12/05/2023 | Water service stub-in inspection: OK | ADRIANM | ADRIANM | | PB | P | 7936322 |
WESTERN PEAK PLUMBING LLC | PB | P | 11/27/2023 | dwv ok less 2" to floor drains in equip room/ marked plans ok site | TREBORB | TREBORB | | PB | P | 7927614 |
WESTERN PEAK PLUMBING LLC | PRD | P | 11/20/2023 | stub in and riser ok less closet wrap | TREBORB | TREBORB | | PRD | P | 7923930 |
WESTERN PEAK PLUMBING LLC | PB | P | 11/17/2023 | sewer stub in ok. | TAYLOR | TAYLOR | | PB | P | 7921911 |